Liquid Propane conversion

Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!

7

B

Replace the seal under the gas flange with a new seal 
(

Æ

fig. 10,[2]).

Fig. 11 Installing a new seal on the gas pipe

B

Replace the seal from the gas pipe with a new seal 
(

Æ

fig. 11).

B

Refit all parts in reverse order. When re-installing the 
burner plate, make sure that the notch is on the 
right-hand side (

Æ

fig. 12).

Fig. 12 Re-installing the burner plate

B

Carry out the start-up activities and complete a new 
start-up report.

B

Check all joints and gaskets affected by the installation 
activities while carrying out the tightness test in 
operating conditions.

B

Place a new sticker underneath the existing rating plate 
sticker indicating the type of gas supply installed.

B

Fill out the required information on the conversion label.

B

Close the boiler door and lock the fastener by turning 
the vent key through ¼ rotation in a clockwise 
direction.

3.3

Testing for gas leaks

Prior to start-up of the boiler you must check the external 
tightness of the gas supply valve and confirm this in the 
start-up report.

B

Disconnect the boiler from the power supply.

B

Check the exterior tightness of new conduit sections 
up to and including the direct sealing point on the gas 
burner fitting. The maximum test pressure allowed on 
the input of the gas burner fitting is 60 inch W.C. 
(150 mbar).

B

Check the input rates after converting the boiler to LPG 
to the values on the front page.

3.4

Inlet gas pressure

B

Open at least 1thermostatic radiator valve if present to 
allow water to flow through the boiler. Do not switch on 
the boiler.

B

Close the gas shut-off valve. Loosen the screw plug on 
the inlet gas pressure testing nipple by 2 turns 
(

Æ

fig. 13, [1]).

B

Connect the pressure gauge connection hose to the 
testing nipple (

Æ

fig. 13, [2]).

B

Slowly open the gas shut-off valve.

The boiler and its individual shutoff valve must be 
disconnected from the gas supply piping system during 
any pressure testing of that system at test pressures in 
excess of 60 inch W.C. (150 mbar).

The boiler must be isolated from the gas supply piping 
system by closing its individual manual shutoff valve 
during any pressure testing of the gas supply piping 
system at test pressures equal to or less than 60 inch 
W.C. (150 mbar).

6720615033-015.1TD

6720615033-016.1TD

DANGER: 

Risk of explosion

B

Check for leaks before working on gas-
carrying components.

CAUTION: 

due to a short circuit.

B

Cover damageable parts before leak 
testing.

B

Do not spray the leak detection agent onto 
cables, plugs or electrical connection 
lines. Do not allow it to drip onto them 
either.

Содержание GB162-80 kW

Страница 1: ...requirements of the authority having jurisdiction The information in these instructions must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or deat...

Страница 2: ...following symbols 3 2 Parts list for converting the boiler to propane 4 3 Liquid Propane conversion 5 3 1 Shut down the boiler 5 3 2 Changing the gas valve assembly 5 3 3 Testing for gas leaks 7 3 4...

Страница 3: ...ollowing symbols DANGER Indicates the presence of hazards that will cause severe personal injury death or substantial property damage WARNING Indicates the presence of hazards that can cause severe pe...

Страница 4: ...rts list for converting the boiler to propane Conversion kit propane for the GB162 80 kW 100 kW 7746900499 includes assembly 774601703A 1 gas valve propane venturi orifice 774600958A these instruction...

Страница 5: ...tion anti clockwise fig 2 Fig 2 Opening the boiler door 3 2 Changing the gas valve assembly B Loosen the screw connection on the gas valve fig 3 1 and pull the plugs fig 3 2 from the gas valve Fig 3 U...

Страница 6: ...rews and gas valve with venturi B Install the venturi and gas valve of the conversion kit on the fan unit using a new O ring fig 9 and follow the instructions above in reverse order Fig 9 Placing a ne...

Страница 7: ...onduit sections up to and including the direct sealing point on the gas burner fitting The maximum test pressure allowed on the input of the gas burner fitting is 60 inch W C 150 mbar B Check the inpu...

Страница 8: ...in 3 5 Checking and adjusting the gas air ratio B Switch off the boiler using the main switch B Loosen the screw plug on the measuring nipple for the burner pressure by 2 rotations fig 15 1 B Set the...

Страница 9: ...Carrying out a tightness test in operating conditions B Check all gaskets and joints in the burner gas circuit for leaks while the burner is operational using a leak detection agent 3 7 Measuring the...

Страница 10: ...ly call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water DANGER What to do if you smell gas B No open f...

Страница 11: ...as Then smell for gas including near the floor If you smell gas STOP and see the safety information on page 10 If you do not smell gas go to the next step B Install the casing again B Open the gas shu...

Страница 12: ...6720615033 0004...

Отзывы: