background image

1

 

Safety considerations

Logamax plus GB162-80 kW/100 kW - We reserve the right to make any changes due to technical modifications!

3

1

Safety considerations

For use in Canada the conversion kit shall be carried out 
in accordance with the requirements of the provincial 
authorities having jurisdiction and in accordance with the 
requirements of the CAN-B149.1 and CAN1-B149.2 
Installation Code. See also E.I.V.

Please observe the following safety instructions.

1.1

Application purpose

This kit and instructions are for converting the Logamax 
plus GB162-80 kW/100 kW from Natural gas to Liquid 
Propane.

1.2

Hazard definitions

The following defined terms are used throughout the 
documentation to bring attention to the presence of 
hazards of various risk levels. Notices give important 
information concerning the operation of the product.

1.3

Observe the following symbols

DANGER: 

Indicates the presence of hazards that will 
cause severe personal injury, death or 
substantial property damage.

WARNING: 

Indicates the presence of hazards that can 
cause severe personal injury, death or 
substantial property damage.

CAUTION: 

Indicates presence of hazards that will out 
cause minor personal injury or property 
damage.

CAUTION: 

Indicates presence of hazards due to electric 
shock.

Indicates special instructions on installation, 
operation or maintenance that are important 
but not related to personal injury or property 
damage.

DANGER: 

due to explosion of gas.

B

Work only on gas components when you 
have a license to do so.

B

Note that the assembly of gas and vent 
connections, the initial start-up, the 
electrical connections, the maintenance 
and service can only be performed by a 
licensed service contractor or technican.

DANGER: 

Electric shock.

Live components are present inside the 
boiler.

B

Isolate the electrical mains supply before 
working on the boiler.

B

Lock-out the mains supplies to prevent 
accidental activation.

Содержание GB162-80 kW

Страница 1: ...requirements of the authority having jurisdiction The information in these instructions must be followed to minimize the risk of fire or explosion or to prevent property damage personal injury or deat...

Страница 2: ...following symbols 3 2 Parts list for converting the boiler to propane 4 3 Liquid Propane conversion 5 3 1 Shut down the boiler 5 3 2 Changing the gas valve assembly 5 3 3 Testing for gas leaks 7 3 4...

Страница 3: ...ollowing symbols DANGER Indicates the presence of hazards that will cause severe personal injury death or substantial property damage WARNING Indicates the presence of hazards that can cause severe pe...

Страница 4: ...rts list for converting the boiler to propane Conversion kit propane for the GB162 80 kW 100 kW 7746900499 includes assembly 774601703A 1 gas valve propane venturi orifice 774600958A these instruction...

Страница 5: ...tion anti clockwise fig 2 Fig 2 Opening the boiler door 3 2 Changing the gas valve assembly B Loosen the screw connection on the gas valve fig 3 1 and pull the plugs fig 3 2 from the gas valve Fig 3 U...

Страница 6: ...rews and gas valve with venturi B Install the venturi and gas valve of the conversion kit on the fan unit using a new O ring fig 9 and follow the instructions above in reverse order Fig 9 Placing a ne...

Страница 7: ...onduit sections up to and including the direct sealing point on the gas burner fitting The maximum test pressure allowed on the input of the gas burner fitting is 60 inch W C 150 mbar B Check the inpu...

Страница 8: ...in 3 5 Checking and adjusting the gas air ratio B Switch off the boiler using the main switch B Loosen the screw plug on the measuring nipple for the burner pressure by 2 rotations fig 15 1 B Set the...

Страница 9: ...Carrying out a tightness test in operating conditions B Check all gaskets and joints in the burner gas circuit for leaks while the burner is operational using a leak detection agent 3 7 Measuring the...

Страница 10: ...ly call a qualified service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under water DANGER What to do if you smell gas B No open f...

Страница 11: ...as Then smell for gas including near the floor If you smell gas STOP and see the safety information on page 10 If you do not smell gas go to the next step B Install the casing again B Open the gas shu...