Servicing
5
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 11S/19S/24S/24C • 02/2006
43
Subject to modifications resulting from technical improvements!
Buderus • http://www.buderus-domestic.co.uk
Code
Meaning
8Y
Gas fault
Possible
cause
Action
1
External switching contact (e.g. temperature-
monitoring device for underfloor heating has been
tripped or gas pressure too low
Check gas pressure detector is defective or the wires have
not been properly connected to the back of the UBA (see
subsection 5.3.6)
Code
Meaning
9A
System error
Possible
cause
Action
1
Regulating device may have to cope with interference
– Check if for example induction fields interfere with the
regulating device
– Check if the are any peaks in the electrical network
caused by maybe windmills or a power generator
– Check for dripping hot water taps on the combination
boiler only
2
UBA may be defective
Press reset. If fault code remains then try to temporarily
connect a different UBA
Code
Meaning
9C
KIM error
Possible
cause
Action
1
KIM connected incorrectly or KIM defective
Check the KIM connector and fan connector.
If the connectors are fine then contact Buderus
Code
Meaning
9F/H
System error
Possible
cause
Action
1
Regulating device may have to cope with interference
– Check if for example induction fields interfere with the
regulating device
– Check if the are any peaks in the electrical network
caused by maybe windmills or a power generator
2
UBA may be defective
Press reset. If fault code remains then try to temporarily
connect a different UBA (see subsection 5.3.3)
Code
Meaning
9L
Gas valve assembly error
Possible
cause
Action
1
Wiring to the gas valve incorrect, or loose wiring
connections in UBA
– Check the electrical connections of the gas valve.
– Measure the resistance of the gas valve (18-55 Ohm)
– Check if for example induction fields interfere with the
regulating device
2
UBA may be defective
– Press reset. If fault code remains then try to temporarily
connect a different UBA (see subsection 5.3.3)
3
Peaks in the electrical network
– Check if the are any peaks in the electrical network
caused by maybe windmills or a power generator