Installation
1
10
Installation and maintenance instructions for wall-mounted condensing gas boiler 600 - 11S/19S/24S/24C • 02/2006
Buderus • http://www.buderus-domestic.co.uk
Subject to modifications resulting from technical improvements!
1.3.2
Air supply and flue gas exhaust in a closed
installation
A ventilation cover is integrated into the 600 Series condensing
gas boilers. This cover houses a number of components, such
as the burner and the heat exchanger. Since this ventilation
cover is part of the air supply system, it is vital that it is always
installed correctly.
To ensure optimal operation, the 600 Series appliances must
be connected to a Buderus wall-mounted or roof-mounted flue
terminal. These terminals have been developed specifically for
the 600 Series condensing gas boilers and have been
comprehensively tested. The Buderus wall and roof-mounted
flue terminal kits ensure trouble-free operation.
The following items for the flue (see fig. 2) are included in the
delivery of the boiler:
– pos. 1: 1 Concentric bend 60/100;
– pos. 2: 1 Horizontal flue terminal 60/100;
– pos. 3: 1 Flue finishing kit.
1.3.3
Maximum Flue length
The maximum pipe length of the air supply and flue gas
exhaust pipes for the 600 Series condensing gas boilers (see
table 2) is determined by the total pressure loss of all
components in the flue gas exhaust / air supply system.
Take the flue conduit clearances into account when planning
the layout of the place of installation (see subsection 1.3.1:
"Siting the flue terminal" on page 9).
Maximum wall thickness without extensions is 550 mm.
Maintain a minimum side wall clearance of 50 mm (see fig. 3).
1.3.4
Additional flue parts
Additional flue parts (see table 3) can be ordered from your
supplier.
Fig. 2
Horizontal flue pack
1
2
3
Fig. 3
Side flue and rear flue installation
550 mm
50 mm
L
Flow pressure available for use [Pa]
600 Series
11 S
19 S
24 S
24 C
35
60
100
10
Boiler
Maximum
pipe length
For every 90° bend the
maximum pipe length has
to be reduced by
600 Series
L = 7.5 m
1.2 m
Table 2 Pipe length
Flue parts
Order No.
Concentric pipe, 500 mm long, adjustable
NE 83703
Concentric pipe, 1000 mm long, not adjustable
NE 83704
Concentric bend 90°
NE 83705
Concentric bend 45°
NE 83706
Table 3 Additional flue parts