Page 19
If you require more resistors they are available to purchase from our web shop
https://www.btinstallershop.com
What happens when pins are configured and wired in this way
The dual resistor EOL mode is able to detect four states
Alarm event and restore,
Wire cut and wire shorted.
The seven segment displays will show C1 through C8 (following the AL symbol) to indicate the wire cut condition for any
of PINs 1-8, which are presently in the wire cut state.
The seven segment displays will show S1 through S8 (following the AL symbol) to indicate the wire shorted condition for
any of PINs 1-8, which are presently in the wire shorted state.
For Example
Relay 1 (RL1) will operate on a wire cut or wire short alarm
Alarms will also be sent through to the Alarm Receiving Centre for each of these conditions
3.3kΩ
1%
orange, orange, black, brown, brown
10kΩ
1%
brown, black, black, red, brown
Fig 7
There are 2 x 3k3 and 2 x 10K resistors included in the box allowing you to wire two pins in this way. EG Fire and Fire
Fault. See fig 7
open circuit pin 1
short circuit pin 8
3k3
089446
Red Dot in packet
10k
089447
Blue Dot in packet
Resistor
Item Code Label
Colour Code