INTRODUCTION

The Carbon Monoxide Transmitter uses an 

electrochemical sensor to monitor the CO 

level and outputs a proportional 0-10 Vdc 

signal. The device may also be configured with 

an alarm relay.

BEFORE INSTALLATION

Read these instructions carefully before installing and commissioning the CO transmitter. Failure to follow 

these instructions may result in product damage. Do not use in an explosive or hazardous environment, 

with combustible or flammable gases, as a safety or emergency stop device or in any other application 

where failure of the product could result in personal injury. 

Take electrostatic discharge precautions 

during installation and do not exceed the device ratings.

MOUNTING

The transmitter should be mounted on a flat surface three to five feet from the floor of the area to be 

controlled. Do not mount the sensor near doors, opening windows, supply air diffusers, or other known air 

disturbances. Avoid areas with vibrations or rapid temperature changes.

The transmitter has two integrated mounting tabs on either side of the enclosure that facilitate a #10 size 

screw (not supplied). See Figure 1. 

Remove the cover from the enclosure by loosening 

4 Phillips screws in each corner of the enclosure as 

seen in Figure 2. 

Complete wiring instructions on page 2. Re-install 

the cover and tighten the screws with a Phillips 

screwdriver. See Figure 3.

Figure 1

Figure 3

Figure 2

IN-GE-CMD5B1XXX010-002

Copyright © Greystone Energy Systems, Inc.   All Rights Reserved    Phone:  +1 506 853 3057  Web: www.greystoneenergy.com

Carbon Monoxide Transmitter

with 0-10 Vdc Output

CMD5B1XXX010 Series - Installation Instructions