Operation
7
19
ekr 500 web guiding controller
EDV No.: MD.299.01.06
Chapter: 7
with removable control panel
Date:
29.07.08
Page:
62/86
7.2.3 Procedure for
web edge guiding
7.2.3.1 Automatic material setup
This chapter describes the standard procedure for storing the
bright/dark values of the sensors for web edge guiding.
1. Remove material from the connected sensors and clean the
sensor scanning areas.
2. Select the desired sensor by pressing the corresponding key
“
Sensor 1
“ or “
Sensor 2
“.
The LED of the key lights.
3. Activate automatic material setup in the setup selection menu
(see chapter 7.2.2).
The display shows the accompanying screen
(
here with sensor 1 selected
).
The animation shows the required operation steps for creating
the bright and dark value:
The hand moves the material into the sensor scanning area
(dark value) and back out again (bright value).
4. Remove material from the selected sensor
(no material within the sensor scanning area).
The detected bright value is shown in the display.
5. Cover scanning area of the selected sensor with the material to
be scanned for at least 2 seconds.
The detected dark value is shown in the display.
6. Press key “
ENTER
“.
The material setup for the selected sensor is completed.
The detected bright and dark value is stored.
The operating screen is displayed.
or