Separable RC and RH connections are provided for systems with
separate transformers for heating and cooling. To accommodate
separate transformers, cut jumper R12 on the Equipment Control-
ler board. It is located just below and to the right of the RC and RH
connections. As shipped, the R12 jumper ties RC and RH
terminals together so either can be used in single transformer
application.
When installing a 24-vac humidifer, connect it directly to the
HUM terminal on Equipment Controller, and C terminal of indoor
equipment. Do not use an external humidstat. All necessary control
is provided by Zone Perfect Plus.
When using an FK series fan coil, connect DHUM (dehumidify)
output directly to DH terminal of fan coil. This output may also
drive a relay (connected with other side to C) which can be
connected to reduce fan speed in other types of blowers. The relay
will be energized when humidity is normal and will deenergize
when humidity is high, calling for reduced fan speed.
An LAT sensor must be connected in all systems. Both LAT and
HPT sensors must be connected in heat pump/fan coil systems.
WIRING CONSIDERATIONS
Zone Perfect Plus treats all furnaces as if they were 2-stage. For
single stage equipment, connect to W1. The same holds true for
auxiliary heat in fan coils. (Refer to Fig. 15-38.)
With any 2-stage furnace, configure the furnace so that low fire is
controlled by W1 and high fire is controlled by W1 and W2
together. This means the internal algorithm is to be disabled. See
furnace instructions.
Some variable speed furnaces have a "zoning" setting. If such a
setting exists, it should be turned on. It forces the furnace to adjust
its airflow more frequently to accommodate the effects of damper
movement. See furnace instructions.
All 2-speed air conditioners and heat pumps need to be configured
so that Y1 controls low speed and Y1 and Y2 together control high
speed in both heating and cooling. This is usually done by
selecting the "zoning" position of the stage 2 latch pot. See 2-speed
equipment instructions.
In 2-speed dual fuel applications (2-speed heat pump and furnace),
do not set the furnace interface jumper on the heat pump to ON,
→
Fig. 10—4-Zone System Wiring Diagram
A98086
O REVERSING VALVE COOL
B REVERSING VALVE HEAT
RH HEATING TRANSFORMER
RC COOLING TRANSFORMER
DEF DEFROST
DHUM DEHUMIDIFY
SEE
FIGURES FOR
EQUIPMENT
WIRING
24 VAC ZONING
TRANSFORMER
C
RZ
4 ZONE EQUIPMENT CONTROLLER
HUM HUMIDIFY
G FAN
W2 HEAT STAGE 2
W1 HEAT STAGE 1
Y2 COMPRESSOR STAGE 2
Y1 COMPRESSOR STAGE 1
HPTC
LAT
LATC
HPT
OAT
OATC
V+
RS+
RS-
VG
DAMPERS
8
1
CLS_
COM_
OPN_
=
=
=
CLOSE
COMMON = 24VAC FROM RZ
OPEN
OUTDOOR AIR
TEMP SENSOR
LEAVING AIR
TEMP SENSOR
HEAT PUMP
TEMP SENSOR
CLS3
COM3
OPN3
CLS4
COM4
OPN4
ZONE 3
DAMPER
ZONE 4
DAMPER
CLS1
COM1
OPN1
CLS2
COM2
OPN2
ZONE 1
DAMPER
ZONE 2
DAMPER
JUMPER NEEDED
FOR HEAT PUMP
APPLICATIONS
DAMPER
FUSE
3A
OPTION
SWITCHES
NOTE SWITCH
#8 IS AT TOP
D20
(LED)
NOTES:
*
= OPTIONAL COMPONENTS
= INSTALLING ZONE 1 REMOTE SENSOR AT OS1 AND OS1C WILL OVERRIDE
TEMPERATURE SENSOR ON USER INTERFACE
= COMMUNICATION BUS ARE IN PARALLEL WITH EACH OTHER
(EITHER CONNECTOR CAN BE USED)
DEFROST
†
†
REMOTE
SENSORS
COMMUNICATION
BUS
ZONE 3
SENSOR
ZONE 4
SENSOR
OPTIONAL
ZONE 1
SENSOR
ZONE 2
SENSOR
V+
COMMUNICATION
BUS
RS+
RS-
VG
OS1
OS1C
ZS2
ZS2C
ZS3
ZS3C
ZS4
ZS4C
V+
USER INTERFACE
RS+
RS-
VG
VG
V+
SMART SENSORS*
RS+
RS-
WHITE
RED
BLUE/YELLOW
GREEN
WHITE
RED
BLUE/YELLOW
GREEN
†
†
†