66
b. Requires field-supplied electrical box, North
American 1-gang box, 2-in. (51 mm) x 4-in.
(102 mm).
c. Shall have a clear colored lens.
25. Winter start kit
a. Shall contain a bypass device around the low
pressure switch.
b. Shall be required when mechanical cooling is
required down to 25°F (–4°C).
c. Shall not be required to operate on an econo-
mizer when below an outdoor ambient of 40°F
(4°C).
26. Time Guard
a. Shall prevent compressor short cycling by pro-
viding a 5-minute delay (±2 minutes) before
restarting a compressor after shutdown for any
reason.
b. One device shall be required per compressor.
27. Barometric Hood (Horizontal Economizer Appli-
cations)
Shall be required when a horizontal economizer
and barometric relief are required. Barometric
relief damper must be installed in the return air
(horizontal) duct work. This hood provides weather
protection.
28. Hinged Access Panels
a. Shall provide easy access through integrated
quarter turn latches.
b. Shall be on major panels of – filter, control box,
fan motor and compressor.
29. Display Kit for Variable Frequency Drive
a. Kit allows the ability to access the VFD control-
ler programs to provide special setup capabili-
ties and diagnostics.
b. Kit contains display module and communica-
tion cable.
c. Display Kit can be permanently installed in the
unit or used on any 2-Speed Indoor Fan Motor
System VFD controller as needed.
30. Condensate Overflow Switch:
a. This sensor and related controller monitors the
condensate level in the drain pan and shuts
down compression operation when overflow
conditions occur. It includes:
1) Indicator light - solid red (more than 10
seconds on water contact - compressors
disabled), blinking red (sensor discon-
nected).
2) 10 second delay to break - eliminates nui-
sance trips from splashing or waves in pan
(sensor needs 10 seconds of constant water
contact before tripping).
3) Disables the compressor(s) operation when
condensate plug is detected, but still allows
fans to run for Economizer.
31. Foil Faced Insulation
Throughout unit cabinet air stream, non-fibrous
and cleanable foil faced insulation is used.
GUIDE SPECIFICATIONS (cont)
Содержание Preferred Series
Страница 16: ...16 581J 17 BASE UNIT DIMENSIONS DIMENSIONS ...
Страница 17: ...17 581J 17 BASE UNIT DIMENSIONS cont ...
Страница 18: ...18 581J 17 CORNER WEIGHTS DIMENSIONS cont ...
Страница 20: ...20 DIMENSIONS cont 581J 20 24 BASE UNIT DIMENSIONS ...
Страница 21: ...21 581J 20 24 BASE UNIT DIMENSIONS cont ...
Страница 22: ...22 581J 20 24 CORNER WEIGHTS DIMENSIONS cont ...
Страница 24: ...24 581J 28 BASE UNIT DIMENSIONS DIMENSIONS cont ...
Страница 25: ...25 581J 28 BASE UNIT DIMENSIONS cont ...
Страница 26: ...26 581J 28 CORNER WEIGHTS DIMENSIONS cont ...
Страница 28: ...28 581J 17 ROOF CURB DIMENSIONS ACCESSORY DIMENSIONS ...
Страница 29: ...29 581J 20 24 ROOF CURB DIMENSIONS ...
Страница 30: ...30 581J 28 ROOF CURB DIMENSIONS ACCESSORY DIMENSIONS cont ...
Страница 46: ...46 581J 17 24 ELECTRO MECHANICAL CONTROL WIRING DIAGRAMS TYPICALWIRING DIAGRAM ...
Страница 47: ...47 581J 17 24 ELECTRO MECHANICAL CONTROL WIRING DIAGRAM WITH OPTIONAL PERFECT HUMIDITY SYSTEM ...
Страница 48: ...48 581J 17 24 TYPICAL POWER WIRING DIAGRAM 208 230V SHOWN TYPICALWIRING DIAGRAM cont ...
Страница 49: ...49 581J 17 24 TYPICAL POWER WIRING DIAGRAM WITH OPTIONAL PERFECT HUMIDITY SYSTEM 208 230V SHOWN ...
Страница 67: ......