63
m. Shall be designed to close damper(s) during
loss-of-power situations with spring return built
into motor.
n. Dry bulb outdoor air temperature sensor shall
be provided as standard. Enthalpy sensor is also
available on factory-installed only. Outdoor air
sensor setpoint shall be adjustable and shall
range from 40 to 100°F (4 to 38°C). Additional
sensor options shall be available as accessories.
o. The economizer controller shall also provide
control of an accessory power exhaust unit
function. Factory set at 100%, with a range of
0% to 100%.
p. The economizer shall maintain minimum air-
flow into the building during occupied period
and provide design ventilation rate for full
occupancy.
q. Dampers shall be completely closed when the
unit is in the unoccupied mode.
r. Economizer controller shall accept a 2 to 10
Vdc CO
2
sensor input for IAQ/DCV control. In
this mode, dampers shall modulate the outdoor
air damper to provide ventilation based on the
sensor input.
s. Compressor lockout temperature on W7220 is
adjustable from –45°F to 80°F, set at a factory
default of 32°F. Others shall open at 35°F (2°C)
and close at 50°F (10°C).
t. Actuator shall be direct coupled to economizer
gear. No linkage arms or control rods shall be
acceptable.
u. Economizer controller shall provide indications
when in free cooling mode, in the DCV mode,
or the exhaust fan contact is closed.
4. Inte
grated EconoMi$er2, and EconoMi$er X Ultra
Low Leak rate models. (Factory-installed on 3-
phase models only. Field-installed on all 3 and 1-
phase models):
a. Integrated, gear driven opposing modulating
blade design type capable of simultaneous
economizer and compressor operation.
b. Independent modules for vertical or horizontal
return configuration shall be available. Vertical
return modules shall be available as a factory-
installed option.
c. Damper blades shall be galvanized steel with
composite gears. Plastic or composite blades on
intake or return shall not be acceptable.
d. Shall include all hardware and controls to pro-
vide free cooling with outdoor air when tem-
perature and/or humidity are below setpoints.
e. Shall be equipped with gear driven dampers for
both the outdoor ventilation air and the return
air for positive air stream control.
f. Ultra Low Leak design meets California Title
24 section 140.4 and, ASHRAE 90.1-2016 and
IECC-2015 requirements for 4 cfm per sq. ft. on
the outside air dampers and 10 cfm per sq. ft. on
the return dampers.
g. Economizer controller on EconoMi$er X mod-
els shall be the Honeywell W7220 that pro-
vides:
1) 2-line LCD interface screen for setup, con-
figuration and troubleshooting
2) On-board Fault Detection and Diagnostics
(FDD) that senses and alerts when the
economizer is not operating properly, per
California Title 24.
3) Sensor failure loss of communication iden-
tification
4) Automatic sensor detection
5) Capabilities for use with multiple-speed
indoor fan systems
6) Utilize digital sensors: Dry bulb and
Enthalpy
h. Economizer controller on EconoMi$er 2 mod-
els with RTU Open controller shall be a 4 to 20
mA design controlled directly by the RTU Open
controller. RTU Open controller meets Califor-
nia Title 24 Fault Detection and Diagnostic
(FDD) requirements.
i. Shall be capable of introducing up to 100% out-
door air.
j. Shall be equipped with a barometric relief
damper capable of relieving up to 100% return
air and contain seals that meet ASHRAE 90.1-
2016 and IECC-2015 requirements.
k. Shall be designed to close damper(s) during
loss-of-power situations with spring return built
into motor.
l. Dry bulb outdoor air temperature sensor shall
be provided as standard. Enthalpy sensor is also
available on factory-installed only. Outdoor air
sensor setpoint shall be adjustable and shall
range from 40 to 100°F (4 to 38°C). Additional
sensor options shall be available as accessories.
m. The economizer controller shall also provide
control of an accessory power exhaust unit
function. Factory set at 100%, with a range of
0% to 100%.
n. The economizer shall maintain minimum air-
flow into the building during occupied period
and provide design ventilation rate for full
occupancy.
o. Dampers shall be completely closed when the
unit is in the unoccupied mode.
p. Economizer controller shall accept a 2 to 10 Vdc
CO
2
sensor input for IAQ/DCV control. In this
mode, dampers shall modulate the outdoor air
damper to provide ventilation based on the sen-
sor input.
q. Compressor lockout temperature on W7220 is
adjustable from –45°F to 80°F, set at a factory
default of 32°F. Others shall open at 35°F (2°C)
and closes at 50°F (10°C).
Содержание Preferred Series
Страница 16: ...16 581J 17 BASE UNIT DIMENSIONS DIMENSIONS ...
Страница 17: ...17 581J 17 BASE UNIT DIMENSIONS cont ...
Страница 18: ...18 581J 17 CORNER WEIGHTS DIMENSIONS cont ...
Страница 20: ...20 DIMENSIONS cont 581J 20 24 BASE UNIT DIMENSIONS ...
Страница 21: ...21 581J 20 24 BASE UNIT DIMENSIONS cont ...
Страница 22: ...22 581J 20 24 CORNER WEIGHTS DIMENSIONS cont ...
Страница 24: ...24 581J 28 BASE UNIT DIMENSIONS DIMENSIONS cont ...
Страница 25: ...25 581J 28 BASE UNIT DIMENSIONS cont ...
Страница 26: ...26 581J 28 CORNER WEIGHTS DIMENSIONS cont ...
Страница 28: ...28 581J 17 ROOF CURB DIMENSIONS ACCESSORY DIMENSIONS ...
Страница 29: ...29 581J 20 24 ROOF CURB DIMENSIONS ...
Страница 30: ...30 581J 28 ROOF CURB DIMENSIONS ACCESSORY DIMENSIONS cont ...
Страница 46: ...46 581J 17 24 ELECTRO MECHANICAL CONTROL WIRING DIAGRAMS TYPICALWIRING DIAGRAM ...
Страница 47: ...47 581J 17 24 ELECTRO MECHANICAL CONTROL WIRING DIAGRAM WITH OPTIONAL PERFECT HUMIDITY SYSTEM ...
Страница 48: ...48 581J 17 24 TYPICAL POWER WIRING DIAGRAM 208 230V SHOWN TYPICALWIRING DIAGRAM cont ...
Страница 49: ...49 581J 17 24 TYPICAL POWER WIRING DIAGRAM WITH OPTIONAL PERFECT HUMIDITY SYSTEM 208 230V SHOWN ...
Страница 67: ......