581J*17-28 MCA MOCP ELECTRICAL DATA
LEGEND
NOTES:
1. Refer to Packaged Rooftop Builder (Selection Software) for additional electri-
cal data.
2. In compliance with NEC requirements for multimotor and combination load
equipment (refer to NEC Articles 430 and 440), the overcurrent protective
device for the unit shall be fuse or HACR breaker. Canadian units may be fuse
or circuit breaker.
3. For 208/230 v units, where one value is shown it is the same for either 208 or
230 volts.
4. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater
than 2%. Use the following formula to determine the percentage of voltage
imbalance.
Example: Supply voltage is 230-3-60
AB = 224 v
BC = 231 v
AC = 226 v
Determine maximum deviation from average voltage.
(AB) 227-224 = 3 v
(BC) 231-227 = 4 v
(AC) 227-226 = 1 v
Maximum deviation is 4 v.
Determine percent of voltage imbalance.
This amount of phase imbalance is satisfactory as it is below the maximum allowable
2%.
581J
UNIT
TYPE
NOM.
V-Ph-Hz
IFM TYPE
NO CONVENIENCE OUTLET OR UNPOWERED CONVENIENCE
OUTLET
WITH POWERED CONVENIENCE OUTLET
NO POWERED EXHAUST
WITH POWERED EXHAUST
(POWERED FROM UNIT)
NO POWERED EXHAUST
WITH POWERED EXHAUST
(POWERED FROM UNIT)
MCA
HACR
BRKR
DISC. SIZE
MCA
HACR
BRKR
DISC. SIZE
MCA
HACR
BRKR
DISC. SIZE
MCA
HACR
BRKR
DISC. SIZE
FLA
LRA
FLA
LRA
FLA
LRA
FLA
LRA
17
208/230-3-60
STD
68.3
90
71
393
80.1
100
85
413
73.1
90
77
398
84.9
100
90
68.3
MED
71.4
90
75
423
83.2
100
88
443
76.2
100
80
428
88.0
100
94
71.4
HIGH
74.4
90
78/77
425
86.2
100
92/91
445
79.2
100
84/83
430
91.0
100
97/96
74.4
460-3-60
STD
34.9
45
36
234
41.1
50
44
246
37.1
45
39
236
43.3
50
46
34.9
MED
36.8
45
39
249
43.0
50
46
261
39.0
50
41
251
45.2
50
48
36.8
HIGH
37.9
50
40
250
44.1
50
47
262
40.1
50
42
252
46.3
50
50
37.9
575-3-60
STD
26.2
30
27
184
31.0
40
33
192
27.9
35
29
186
32.7
40
35
26.2
MED
26.2
30
27
184
31.0
40
33
192
27.9
35
29
186
32.7
40
35
26.2
HIGH
29.0
35
31
198
33.8
40
36
206
30.7
40
33
200
35.5
45
38
29.0
20
208/230-3-60
STD
75.7
100
79
440
87.5
100
93
460
80.5
100
85
445
92.3
100
98
75.7
MED
79.1
100
83/82
455
90.9
100
97/96
475
83.9
100
89/88
460
95.7
110
102/101 79.1
HIGH-HE
82.6
100
87
451
94.4
110
101
471
87.4
100
93
456
99.2
125
106
82.6
460-3-60
STD
36.6
45
38
245
42.8
50
46
257
38.8
50
41
247
45.0
50
48
36.6
MED
38.2
50
40
252
44.4
50
47
264
40.4
50
43
254
46.6
50
50
38.2
HIGH-HE
40.4
50
43
250
46.6
50
50
262
42.6
50
45
252
48.8
60
52
40.4
575-3-60
STD
26.2
30
27
186
31.0
40
33
194
27.9
35
29
188
32.7
40
35
26.2
MED
29.0
35
31
200
33.8
40
36
208
30.7
40
33
202
35.5
45
38
29.0
HIGH-HE
31.0
40
33
198
35.8
45
38
206
32.7
40
35
200
37.5
45
40
31.0
24
208/230-3-60
STD
86.6
100
91
574
98.4
125
105
594
91.4
100
97
579
103.2
125
111
86.6
MED-HE
86.6
100
91
574
98.4
125
105
594
91.4
100
97
579
103.2
125
111
86.6
HIGH-HE
98.0
125
105
653
109.8
125
118
673
102.8
125
110
658
114.6
125
124
98.0
460-3-60
STD
45.3
50
48
310
51.5
60
55
322
47.5
60
50
312
53.7
60
58
45.3
MED-HE
45.3
50
48
310
51.5
60
55
322
47.5
60
50
312
53.7
60
58
45.3
HIGH-HE
51.0
60
54
350
57.2
70
62
362
53.2
60
57
352
59.4
70
64
51.0
575-3-60
STD
33.4
40
35
232
38.2
45
41
240
35.1
45
37
234
39.9
50
43
33.4
MED-HE
35.4
45
37
230
40.2
50
43
238
37.1
45
39
232
41.9
50
45
35.4
HIGH-HE
37.3
45
40
257
42.1
50
45
265
39.0
50
42
259
43.8
50
47
37.3
28
208/230-3-60
STD
116.6
150
120/119
591
128.4 175/175 134/133
611
121.4 150/150 126/125
596
133.2 175/175 139/138 116.6
MED-HE
120.1
150
124
587
131.9
175
138
607
124.9
150
130
592
136.7
175
143
120.1
HIGH-HE
131.5
175
137
666
143.3
175
151
686
136.3
175
143
671
148.1
175
157
131.5
460-3-60
STD
51.1
60
53
321
57.3
70
60
333
53.3
60
56
323
59.5
70
63
51.1
MED-HE
53.3
60
56
319
59.5
70
63
331
55.5
70
58
321
61.7
80
66
53.3
HIGH-HE
59.0
70
62
359
65.2
80
70
371
61.2
70
65
361
67.4
80
72
59.0
575-3-60
STD
40.5
50
42
256
45.3
50
48
264
42.2
50
44
258
47.0
60
50
40.5
MED-HE
42.5
50
45
254
47.3
60
50
262
44.2
50
47
256
49.0
60
52
42.5
HIGH-HE
44.4
50
47
281
49.2
60
52
289
46.1
60
49
283
50.9
60
54
44.4
BRKR
—
Circuit Breaker
DISC
—
Disconnect
FLA
—
Full Load Amps
HACR
—
Heating Air-conditioning And Refrigeration
IFM
—
Indoor Fan Motor
LRA
—
Locked Rotor Amps
MCA
—
Minimum Circuit Amps
RLA
—
Rated Load Amps
% Voltage Imbalance
= 100 x
max voltage deviation from average voltage
average voltage
Average Voltage
=
(224 + 231 + 226)
=
681
=
227
3
3
% Voltage Imbalance = 100x
4
=
1.78%
227
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your
local electric utility company immediately.
A
B
C
MOTOR
ELECTRICAL DATA (cont)
Содержание Preferred Series
Страница 16: ...16 581J 17 BASE UNIT DIMENSIONS DIMENSIONS ...
Страница 17: ...17 581J 17 BASE UNIT DIMENSIONS cont ...
Страница 18: ...18 581J 17 CORNER WEIGHTS DIMENSIONS cont ...
Страница 20: ...20 DIMENSIONS cont 581J 20 24 BASE UNIT DIMENSIONS ...
Страница 21: ...21 581J 20 24 BASE UNIT DIMENSIONS cont ...
Страница 22: ...22 581J 20 24 CORNER WEIGHTS DIMENSIONS cont ...
Страница 24: ...24 581J 28 BASE UNIT DIMENSIONS DIMENSIONS cont ...
Страница 25: ...25 581J 28 BASE UNIT DIMENSIONS cont ...
Страница 26: ...26 581J 28 CORNER WEIGHTS DIMENSIONS cont ...
Страница 28: ...28 581J 17 ROOF CURB DIMENSIONS ACCESSORY DIMENSIONS ...
Страница 29: ...29 581J 20 24 ROOF CURB DIMENSIONS ...
Страница 30: ...30 581J 28 ROOF CURB DIMENSIONS ACCESSORY DIMENSIONS cont ...
Страница 46: ...46 581J 17 24 ELECTRO MECHANICAL CONTROL WIRING DIAGRAMS TYPICALWIRING DIAGRAM ...
Страница 47: ...47 581J 17 24 ELECTRO MECHANICAL CONTROL WIRING DIAGRAM WITH OPTIONAL PERFECT HUMIDITY SYSTEM ...
Страница 48: ...48 581J 17 24 TYPICAL POWER WIRING DIAGRAM 208 230V SHOWN TYPICALWIRING DIAGRAM cont ...
Страница 49: ...49 581J 17 24 TYPICAL POWER WIRING DIAGRAM WITH OPTIONAL PERFECT HUMIDITY SYSTEM 208 230V SHOWN ...
Страница 67: ......