II.

DUCTWORK ACOUSTICAL TREATMENT

Metal duct systems that do not have a 90 degree elbow and 10 ft
of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.

III.

SUPPLY AIR CONNECTIONS

Connect supply-air duct to 3/4-in. flange on furnace supply-air
outlet. The supply-air duct attachment must ONLY be connected
to furnace supply-/outlet-air duct flanges or air conditioning coil

casing (when used). DO NOT cut main furnace casing to attach
supply side air duct, humidifier, or other accessories. All accesso-
ries MUST be connected external to furnace main casing.

IV.

RETURN AIR CONNECTIONS

WARNING:

Never connect return-air ducts to the back

of the furnace. A failure to follow this warning can cause
a fire, personal injury, or death.

The return-air duct must be connected to bottom , sides (left or
right), or a combination of bottom and side(s) of main furnace
casing as shown in Fig. 1. Bypass humidifier may be attached into

Fig. 3—Confined Space: Air For Combustion and Ventila-

tion from an Indoor Unconfined Space

A89012

SUPPLY

AIR

6

 MIN

(FRONT) 

RETURN AIR

VENT THROUGH ROOF 

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

 MAX 

1 SQ IN.
PER 1000
BTUH* IN DOOR

OR WALL

12

 MAX 

INTERIOR

HEATED

SPACE 

* Minimum opening size is 100 sq in. with
  minimum dimensions of 3 in. 

† 

Minimum of 3 in. when type-B1 vent is used.

UNCONFINED
SPACE 

CONFINED

SPACE 

Fig. 4—Confined Space: Air For Combustion and Ventila-

tion from Outdoors

A89013

1 SQ IN.

PER

4000

BTUH*

DUCTS

TO

OUTDOORS

1 SQ IN.
PER 4000
BTUH*

SUPPLY

AIR

VENT
THROUGH
ROOF

D

B

A

C

E  

1 SQ IN.
PER 4000
BTUH*

DUCT

TO

OUTDOORS

RETURN AIR

1 SQ IN.
PER 2000
BTUH*

1 SQ IN.
PER 2000
BTUH*

DUCTS

TO

OUTDOORS

12

 MAX

12

 MAX

12

 MAX

Use any of the following
combinations of openings:
A & B     C & D    D & E     F & G

NOTE:

*

Minimum dimensions of 3 in.

CONFINED

SPACE

12

MAX

12

MAX

OUTDOORS

1 SQ IN.

PER

4000

BTUH*

F

G

TABLE 2—MINIMUM FREE AREA OF COMBUSTION AIR OPENING

383KAV

FURNACE

INPUT

(BTUH)

AIR FROM INDOOR

UNCONFINED SPACE

OUTDOOR AIR THROUGH

VERTICAL DUCTS

OUTDOOR AIR THROUGH

HORIZONTAL DUCTS

OUTDOOR AIR THROUGH

SINGLE DUCT

Free Area

of Opening

(Sq In.)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

Free Area of

Opening and Duct

(Sq In.)

Round

Pipe

(In. Dia)

44,000

100

11.0

4

22.0

6

14.67

5

66,000

100

16.5

5

33.0

7

22.00

6

88,000

100

22.0

6

44.0

8

29.33

7

110,000

110

27.5

6

55.0

9

36.67

7

132,000

132

33.0

7

66.0

10

44.00

8

154,000

154

38.5

8

77.0

10

51.33

9

* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased, if other gas appliances
in the space require combustion air.

—6—

Содержание GAS-FIRED INDUCED-COMBUSTION FURNACES 383KAV

Страница 1: ...unit and other safety precautions that may apply In the United States follow all safety codes including the National Fuel Gas Code NFGC NFPA 54 1999 ANSI Z223 1 1999 and the Installation Standards Wa...

Страница 2: ...4 3 16 12 9 16 12 11 16 4 127 042091 17 1 2 15 7 8 16 4 124 048091 21 19 3 8 19 1 2 4 155 036110 17 1 2 15 7 8 16 4 153 048111 21 19 3 8 19 1 2 4 173 060111 24 1 2 22 7 8 23 4 176 048135 21 19 3 8 19...

Страница 3: ...g codes installation must conform with NFGC in the United States and the NSCNGPIC and all authorities having jurisdiction in Canada These instructions cover minimum requirements for a safe instal lati...

Страница 4: ...s warning can cause a fire personal injury or death This furnace must be installed so the electrical components are protected from water This furnace shall not be installed directly on carpeting tile...

Страница 5: ...cating with the outdoors shall be provided See item 2 below c If furnace is installed on a raised platform to provide a return air plenum and return air is taken directly from hallway or space adjacen...

Страница 6: ...VENT THROUGH ROOF 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX 1 SQ IN PER 1000 BTUH IN DOOR OR WALL 12 MAX INTERIOR HEATED SPACE Minimum opening size is 100 sq in with minimum dimensions of 3 in Mini...

Страница 7: ...t in hole Install flat washer if desired 3 Install another nut on other side of furnace base Install flat washer if desired 4 Adjust outside nut to provide desired height and tighten inside nut to sec...

Страница 8: ...15 v Wiring Refer to the furnace rating plate or Table 5 for equipment electrical requirements The control system requires an earth ground for proper operation CAUTION Do not connect aluminum wire bet...

Страница 9: ...if humidifier operation is desired during blower operation TABLE 5 ELECTRICAL DATA UNIT SIZE VOLTS HERTZ PHASE OPERATING VOLTAGE RANGE MAXIMUM UNIT AMPS MINIMUM WIRE GAGE MAXIMUM WIRE LENGTH FT MAXIMU...

Страница 10: ...ontrol area The switch or fuse link opens and shuts off power to the gas valve if a flame rollout or overheating condition occurs in the gas control area DO NOT bypass the switch Correct inadequate co...

Страница 11: ...NDUCTOR ON PCB FIELDWIRINGTERMINAL FIELD GROUND EQUIPMENT GROUND FIELD SPLICE PLUG RECEPTACLE L1 L2 L1 BLWR HI LO TO 115VAC FIELD DISCONNECT NOTE 4 EQUIPMENT GROUND SPARE 2 HEAT SPARE 1 COOL NOTE 7 CO...

Страница 12: ...e blower if it was off and begins a heating cycle The blower remains on until the end of the prepurge period then shuts off until the end of the hot surface igniter warm up and trial for ignition peri...

Страница 13: ...TED STATES At installation altitudes above 2000 ft this furnace has been approved for a 4 percent derate for each 1000 ft above sea level See Table 7 for derate multiplier factor EXAMPLE 88 000 Btuh i...

Страница 14: ...3 3 0 43 3 1 43 3 2 43 3 3 Altitudes 950 43 2 7 43 2 8 43 2 9 43 3 0 43 3 1 2000 975 43 2 6 43 2 7 43 2 8 43 2 9 43 2 9 to 1000 43 2 5 43 2 5 43 2 6 43 2 7 43 2 8 4500 1025 43 2 3 43 2 4 43 2 5 43 2 6...

Страница 15: ...50 43 2 5 43 2 6 43 2 7 43 2 8 43 2 9 to 775 43 2 4 43 2 5 43 2 5 43 2 6 43 2 7 800 43 2 2 43 2 3 43 2 4 43 2 5 43 2 5 7000 825 43 2 1 43 2 2 43 2 2 43 2 3 43 2 4 850 48 3 7 43 2 0 43 2 1 43 2 2 43 2...

Страница 16: ...48 3 4 775 49 3 3 49 3 4 49 3 5 49 3 6 49 3 7 Orifice sizes shown in BOLD are factory installed CAUTION DO NOT redrill orifices Improper drilling burrs out of round holes etc can cause excessive burn...

Страница 17: ...ower to furnace d Set thermostat to call for heat and wait 1 minute When pressure switch is functioning properly hot surface igniter should NOT glow and control diagnostic light flashes a status code...

Страница 18: ..._________ 1 4 in Upward Slope ____________ Joints Secure ____________ See Attached Vent Table Instructions CHECKLIST START UP ____________ Gas Input Rate Set Within 2 percent of Rating Plate _________...

Страница 19: ...19...

Страница 20: ...ideo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays di...

Отзывы: