Bryant EVOLUTION V 189BNV 13 Скачать руководство пользователя страница 4

4

Step 4 — Operating Ambient

The minimum outdoor operating ambient is 40

_

F (4.4

_

C) with

Evolution

Connex

Control,

55

_

F

(12.8

_

C)

with

non--communicating systems. The maximum outdoor operating

ambient is 115

_

F (46.1

_

C). Compressor protections will prevent

operation below minimum ambient temperature range. The system

may operate in cooling up to 125

_

F (52

_

C) (52C) with significant

reduced capacity cutback above 115

_

F (46.1

_

C). Refer to Product

Data “Detailed Cooling Capacity” table.

Low ambient cooling

operation is not currently available.

Step 5 — Elevate Unit

Elevate unit per local climate and code requirements to provide

clearance above estimated snowfall level and ensure adequate
drainage of unit.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not allow water and/or ice to build up in base pan.

CAUTION

!

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Locate the unit in such a way that it is stable in all

circumstances including adverse weather conditions.

Step 6 — Make Piping Connections

!

WARNING

PERSONAL INJURY AND UNIT DAMAGE

HAZARD

Failure to follow this warning could result in personal injury or

death.
Relieve pressure and recover all refrigerant before system

repair or final unit disposal. Use all service ports and open all

flow--control devices, including solenoid valves.

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Do not leave system open to atmosphere any longer than

minimum required for installation. POE oil in compressor is

extremely susceptible to moisture absorption. Always keep

ends of tubing sealed during installation.

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment damage

or improper operation.

If ANY refrigerant tubing is buried, provide a 6 in. (152.4 mm)

vertical rise at service valve. Refrigerant tubing lengths up to 36

in. (914.4 mm) may be buried without further special

consideration. Do not bury lines longer than 36 in. (914.4 mm).

CAUTION

!

Outdoor units may be connected to indoor section using accessory
tubing package or field--supplied refrigerant grade tubing of correct

size and condition. For tubing requirements between 80 -- 100 ft.

(24.38 -- 30.48 m), capacity and performance losses can occur.
Follow the pipe sizing recommendations in the 189BNV Product

data to manage these losses. This unit shall not be installed with
greater than 100 ft (30.48 m) of equivalent line length.
Refer to Table 1 for field tubing diameters. No additional

accessories are required for line lengths between 80 -- 100 ft. (24.4
-- 30.5 m) on this product.

Table 1 – Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (in.)

189BNV

LIQUID

VAPOR

*

Connection

Diameter

Tube

Diameter

Connection

Diameter

Max (Rated)

Diameter

Minimum Tube

Diameter

13, 24B

3/8

3/8

3/4

3/4

5/8

25

3/8

3/8

3/4

7/8

5/8

36

3/8

3/8

3/4

7/8

5/8

37

3/8

3/8

7/8

1---1/8

5/8

48, 49

3/8

3/8

7/8

1---1/8

3/4

60

3/8

3/8

7/8

1---1/8

3/4

*

Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for performance data when using different size and length line sets.

Notes

:

1. Do not apply capillary tube indoor coils to these units.

Содержание EVOLUTION V 189BNV 13

Страница 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Страница 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Страница 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Страница 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Страница 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Страница 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Страница 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Страница 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Страница 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Страница 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Страница 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Страница 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Страница 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Страница 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Страница 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Страница 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Страница 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Страница 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Страница 19: ...19 Table 6 Fault Codes...

Страница 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Отзывы: