Bryant EVOLUTION V 189BNV 13 Скачать руководство пользователя страница 11

11

Charging Non--Communicating Systems

Charging Procedure

: Force system to operate in high stage

cooling by creating a large differential between room temperature

and set point on thermostat. Use multi--meter to verify that 24

VAC is present between C, Y1 /Y2 terminals at outdoor unit.
Factory charge amount is shown on unit rating plate for high stage.

Target subcooling chart is provided on back of control box door

see Fig. 18 -- 25 for example. To properly check or adjust charge,

condition must be favorable for subcooling charging. Favorable

conditions exists when outdoor temperature is between 65

_

F

(18

_

C) and 100

_

F (38

_

C), and the indoor temperature is between

70

_

F (21

_

C) and 80

_

F (27

_

C). Follow the procedure below:

Unit is factory charged for 15ft (4.57 m) of lineset. Adjust charge

by adding or removing 0.6 oz/ft (17.7 g/m) of 3/8 liquid line above

or below 15ft (4.57 m) respectively.

For standard refrigerant line lengths (80ft/24.4 m or less), allow

system to operate in cooling mode at least 25 minutes. If conditions

are favorable, check system charge by subcooling method. If any

adjustment is necessary, adjust charge slowly and allow system to

operate for 25 minutes to stabilize before declaring a properly

charged system.

If the indoor temperature is below 70°F (21.11°C), or the outdoor
temperature is not in the favorable range, adjust charge for line set
length above or below 15ft (4.57 m) and indoor fan coil /furnace
coil per Table 4.

Charge level should then be appropriate for the

system to achieve rated capacity. The charge level should then be

checked at another time when the both indoor and outdoor

temperatures are in a more favorable range.

NOTE

: If the line length is beyond 80ft (24.38 m) or greater than

20ft (6.10 m) vertical separation see Long line guideline for special

charging requirement.

Table 2 – Required Charge Adjustment for Indoor Coil Model

Furnace or Fan Coil Model Number

Outdoor Model Size

13

24B

25

36

37

48

49

60

CNPV*18**

---

/

/

/

/

/

/

/

CAP**18**

---

/

/

/

/

/

/

/

CNP**24

---

---

---

/

/

/

/

/

CNPV*19**

---

/

/

/

/

/

/

/

CAP**24

---

---

---

/

/

/

/

/

CSPH*24

---

---

---

/

/

/

/

/

CSPH*30**

/

---

---

/

/

/

/

/

F(E,V)4(A,B,C)NF002

+0.19

---

---

---

/

/

/

/

CAP**30

/

---

---

/

/

/

/

/

CNP**30

/

---

---

/

/

/

/

/

CNP**36

/

---

---

---

---

/

/

/

F(E,V)4(A,B,C)N(B,F)003

/

---

---

---

---

/

/

/

CAP**36

/

---

+.50

---

---

/

/

/

CNP**42

/

+.50

+.50

---

+.75

/

/

/

CAP**42

/

+.50

+.50

---

+.75

/

/

/

CSPH*36

/

+.50

+.50

---

+.75

/

/

/

CSPH*42**

/

+.50

+.50

+.75

+.75

/

/

/

CNP**31**

/

+.50

+1.25

+.75

+.75

/

/

/

CNP**48

/

+.50

+1.25

+.75

+.75

---

---

/

CSPH*48**

/

+.625

+1.25

+.75

+1.00

---

---

/

CNP**37

/

+.625

+1.25

+.75

+1.00

---

---

/

CNP**43

/

+.625

+1.25

+.75

+1.00

---

---

/

CAP**48

/

/

/

+.75

+1.00

---

---

/

CNP**60

/

/

/

/

+1.00

---

+0.125

---

CSPH*60

/

/

/

/

+1.00

---

+0.125

---

F(E,V)4(A,B,C)N(B,F)005

/

+.625

+1.25

+.75

+1.00

---

+0.125

/

F(E,V)4(A,B,C)NB006

/

/

/

+.75

+1.00

+1.5

+.625

+1.00

CAP**60

/

/

/

/

/

+1.5

+.625

+1.00

CNP**61

/

/

/

/

/

+1.5

+.625

+1.00

/ = Comb. not allowed

--- = No charge adjust for ID

Note: Charge adders are in decimal format

Содержание EVOLUTION V 189BNV 13

Страница 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Страница 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Страница 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Страница 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Страница 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Страница 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Страница 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Страница 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Страница 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Страница 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Страница 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Страница 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Страница 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Страница 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Страница 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Страница 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Страница 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Страница 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Страница 19: ...19 Table 6 Fault Codes...

Страница 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Отзывы: