Bryant EVOLUTION V 189BNV 13 Скачать руководство пользователя страница 13

13

Step 13 — Pumpdown & Evacuation

CAUTION

!

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Federal regulations require that you do not vent refrigerant to

the atmosphere. Recover during system repair or final unit

disposal.

If this system requires either a Pump Down or Evacuation for any

reason, the procedures below must be followed:

Pump Down -- Evolution Communicating

Because this system is inverter controlled, compressor, suction

pressure transducer, conventional procedure cannot be used to
“pump down” and isolate the refrigerant into the outdoor unit. The

UI (User Interface) has provisions to assist in performing this
function.

1. Connect gauges to 189BNV liquid and vapor service valve

ports to monitor operating pressures during and at comple-

tion of the procedure.

2. In the advanced menu of the UI, go to Checkout > Pump-

down

3. Select mode to pump down in (COOL). Set desired time

period. Default time period for the procedure is 120 min-

utes.

4. Select Start on UI to begin the pump--down process. Unit

will begin running in selected mode after a brief delay.

5. Close the liquid service valve.
6. The unit will run in selected mode with the low pressure

protection set to indicate pump--down is complete when the

suction pressure drops below 10 psig. Compressor protec-

tions are still active to prevent damage to the compressor or

inverter (high pressure, high current, high torque, etc.) .

7. Once system indicates pump--down complete or failure to

complete shutdown, close vapor service valve.

8. A small quantity of charge will remain in isolated section of

system dependent on ambient temperature and overall sys-

tem charge. This charge must be manually recovered. A

recovery system will be required to remove final quantity of

refrigerant from indoor coil and line set.

9. Remove power from indoor and outdoor unit prior to ser-

vicing unit.

Pump Down – Using 2--stage Thermostat

(Non--Communicating)

Because this system has an inverter controlled compressor, suction

pressure transducer, conventional procedure cannot be used to

“pump down” and isolate the refrigerant into the outdoor unit.

1. Connect gauges to 189BNV liquid and vapor service valve

ports to monitor operating pressures during and at

completion of the procedure.

2. Force system to operate in high stage by creating a large

differential between room temperature and set point on

thermostat. Use multi--meter to verify that 24 VAC is

present between C and Y1 and Y2 terminals at outdoor unit.

3. Close the liquid service valve.
4. The unit will continue to run until high or low pressure

switches open. Close vapor service valve once compressor

shuts down.

5. Remove power from indoor and outdoor unit prior to

servicing unit.

6. A quantity of charge will remain in isolated section of

system dependent on ambient temperature and overall

system charge. This charge must be manually recovered. A

recovery system will be required to remove final quantity of

refrigerant from indoor coil and line set.

Evacuation and recovery of refrigerant from 189BNV

1. Connect gauges to 189BNV liquid and vapor service valve

ports to monitor operating pressures during and at comple-

tion of the procedure. Attach recovery system or vacuum

pump to gauge set as needed for the service procedure. The

service valves must be open to evacuate the unit through the

line set service ports.

Evacuation and recovery of refrigerant from 189BNV

when using non--communicating thermostat

1. Connect gauges to 189BNV liquid and vapor service valve

ports to monitor operating pressures during and at

completion of the procedure. Attach recovery system or

vacuum pump to gauge set as needed for the service

procedure. The service valves must be open to evacuate the

unit through the line set service ports.

MAJOR COMPONENTS

Variable speed Control Board

A160120

Fig. 26 -- AOC (Application Operational Control) Board

The AOC board is located in the lower right hand side of inverter

tray. It’s functions include:

S

Compressor speed control

S

Outdoor fan motor control

S

Crankcase heater operation

S

Pressure switch monitoring

S

Time Delays

S

Pressure Transducer measurements

S

PEV control (pressure equalizer valve)

S

Temperature measurements

S

Inverter communication and control

Inverter

The inverter is located inside the control box. This is an air--cooled

device that communicates with the control board and drives the

compressor and fan motor to the demanded RPM. The inverter is
always powered with line voltage since no contactor is used. The

inverter changes the line voltage to DC volts and then recreates 3
phase sine waves that vary in frequency to drive the compressor

and fan motor at the desired RPM.

Содержание EVOLUTION V 189BNV 13

Страница 1: ...nstall on Solid Level Mounting Pad 3 Step 3 Clearance Requirements 3 Step 4 Operating Ambient 4 Step 5 Elevate Unit 4 Step 6 Making Piping Connections 4 Step 7 Make Electrical Connections 5 Step 8 Com...

Страница 2: ...erant equipment WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switc...

Страница 3: ...or specific applications and for R 22 retrofit Step 1 Check Equipment and Job Site Unpack Unit Move to final location Remove carton taking care not to damage unit Inspect Equipment File claim with shi...

Страница 4: ...eration Do not leave system open to atmosphere any longer than minimum required for installation POE oil in compressor is extremely susceptible to moisture absorption Always keep ends of tubing sealed...

Страница 5: ...re to follow this caution may result in equipment damage or improper operation Never use the system compressor as a vacuum pump Refrigerant tubes and indoor coil should be evacuated using the recommen...

Страница 6: ...g 189BNV models to non communicating 2 stage thermostats Use Fig 7 For required connections Unit is configured by factory for Evolution communicating control To wire unit for non communicating control...

Страница 7: ...r on Control Board Jumper Wire Required for Single Stage C BLU YEL R RED BLK A160118 O O RVS Cooling O B W2 W1 W1 Heat Stage 3 W W1 W2 Heat Cool Stage 1 Y1 W2 Y1 Y1 Heat Cool Stage 2 Y Y2 Y Y2 Y2 Fan...

Страница 8: ...non communicating furnaces set airflows to 350 400 cfm nominal ton in high stage and 70 80 percent of high stage airflow in low stage Step 9 Install Accessories No refrigeration circuit accessories ar...

Страница 9: ...Select Line Set Length Vapor Line Diameter CAUTION UNIT OPERATION HAZARD Failure to follow this caution may result in improper unit operation For new installations only Add additional refrigerant due...

Страница 10: ...nverter Motor Operational Control MOC then outputs the three phase PWM signal and frequency that gently ramps the compressor speed up to stage 2 and then will adjust to the demanded speed The gentle r...

Страница 11: ...s to stabilize before declaring a properly charged system If the indoor temperature is below 70 F 21 11 C or the outdoor temperature is not in the favorable range adjust charge for line set length abo...

Страница 12: ...g Mode 189BNV024B Fig 20 Charging in Cooling Mode 189BNV025 Fig 21 Charging in Cooling Mode 189BNV036 Fig 22 Charging in Cooling Mode 189BNV037 Fig 23 Charging in Cooling Mode 189BNV048 Fig 24 Chargin...

Страница 13: ...tion of the procedure 2 Force system to operate in high stage by creating a large differential between room temperature and set point on thermostat Use multi meter to verify that 24 VAC is present bet...

Страница 14: ...r NOTE A hissing sound may be heard during the equalization process This is normal TROUBLESHOOTING Systems Communication Failure If communication is lost with the User Interface UI the Green LED will...

Страница 15: ...r low pressure lockout check the refrigerant charge and indoor airflow cooling Brown Out Protection If the line voltage is less than 187V for at least 4 seconds the Compressor and OD fan goes to 0 rpm...

Страница 16: ...and distributor See Fig 31 for proper placement See Table 4 for proper resistances A14328 Fig 30 Outdoor Coil Thermistor OCT Attachment On Distributor Tube OAT Thermistor must be locked in place with...

Страница 17: ...e Unit Size Resistance Ohms 13 24B 21 2 25 36 37 48 49 60 11 1 Status Codes Unit may occasionally become unresponsive due to certain combinations of previous fault codes There may not be anything wron...

Страница 18: ...18 Utility Relay A13414 Fig 34 Variable Speed Control Board with optional Utility Relay...

Страница 19: ...19 Table 6 Fault Codes...

Страница 20: ...ig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oi...

Отзывы: