background image

12

PRE--START--UP

ENVIRONMENTAL,

FIRE,

EXPLOSION,

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death and/or property damage.

1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Relieve and recover all refrigerant from system before

touching or disturbing compressor plug if refrigerant
leak is suspected around compressor terminals.

3. Never attempt to repair soldered connection while

refrigerant system is under pressure.

4. Do not use torch to remove any component. System

contains oil and refrigerant under pressure.

5. To remove a component, wear protective goggles and

proceed as follows:

a. Shut off electrical power to unit and install

lockout tag.

b. Relieve and reclaim all refrigerant from system

using both high-- and low--pressure ports.

c. Cut component connecting tubing with tubing

cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to torch

flame.

!

WARNING

Proceed as follows to inspect and prepare the unit for initial

start--up:

1. Remove all access panels (see Fig. 17).
2. Read and follow instructions on all DANGER, WARNING,

CAUTION, and INFORMATION labels attached to, or

shipped with unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages, such as

broken lines, loose parts, disconnected wires, etc.

b. Inspect all field-- and factory--wiring connections. Be

sure that connections are completed and tight.

c. Ensure wires do not touch refrigerant tubing or sharp

sheet metal edges.

d. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that condensate drain pan and trap are filled

with water to ensure proper drainage.

b. Make sure that all tools and miscellaneous loose parts

have been removed.

START--UP

Step 1 — Check for Refrigerant Leaks

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Never use air or gases containing

oxygen for leak testing or operating

refrigerant compressors. Pressurized

mixtures of air or gases containing

oxygen can lead to an explosion.

!

WARNING

Proceed as follows to locate and repair a refrigerant leak and to

charge the unit:

1. Locate leak and make sure that refrigerant system pressure

has been relieved and reclaimed from both high-- and low--
pressure ports.

2. Repair leak following accepted practices.

NOTE

: Install a filter drier whenever the system has been opened

for repair.

3. Add a small charge of Puron (R--410A) refrigerant vapor to

system and leak--test unit.

4. Recover refrigerant from system and evacuate to 500

microns if no additional leaks are found.

5. Charge unit with Puron (R--410A) refrigerant, using an

accurate scale. Refer to unit rating plate for required charge.

Step 2 — Start--Up Cooling Section And Make

Adjustments

Complete the required procedures given in the Pre--Start--Up

section before starting the unit. Do not jumper any safety devices

when operating the unit. Do not operate the unit when the outdoor
temperature is below 40

F (4

C) (unless accessory low--ambient

kit is installed). Do not rapid cycle the compressor. Allow 5
minutes between “on” cycles to prevent compressor damage.

CHECKING COOLING CONTROL OPERATION

Start and check the unit for proper cooling control operation as

follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is

placed in AUTO position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room

temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that compressor

and outdoor fan shut down when control setting is satisfied
and that indoor blower shuts down after 90 second fan time
delay expires.

IMPORTANT

: Three--phase, scroll compressors are direction

oriented. Unit must be checked to ensure proper compressor
3--phase power lead orientation. If not corrected within 5 minutes,
the internal protector will shut off the compressor. The 3--phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures may be minimal.

CHECKING AND ADJUSTING REFRIGERANT

CHARGE

The refrigerant system is fully charged with Puron (R--410A)
refrigerant and is tested and factory sealed.

707C

--

--

(C

,D

)

Содержание 707C C Series

Страница 1: ...cal Controls and Wiring 30 Refrigerant Circuit 31 Evaporator Airflow 31 Puron Items 31 TROUBLESHOOTING 32 START UP CHECKLIST 32 A170030 Fig 1 Unit 707C C 707C D SAFETY CONSIDERATIONS Improper installa...

Страница 2: ...downflow panels before rigging and lifting into place The panel removal process may require the unit to be on the ground Step 2 Provide Unit Support IMPORTANT The unit must be secured to the curb by i...

Страница 3: ...3 A180287 Fig 2 24 36 Unit Dimensions 707C C D...

Страница 4: ...4 Fig 3 42 60 Unit Dimensions 707C C D...

Страница 5: ...6 778 46 1 1170 Large CPRFCURB013B00 14 356 14 356 43 9 1116 42 2 1072 Part Number CPRCURB011B00 can be used on both small and large basepan units The cross supports must be located based on whether...

Страница 6: ...PLACING UNIT ON ROOF CURB DUCTS DETAIL A VOIR D TAIL A MINIMUM HEIGHT 36 914 4 mm HAUTEUR MINIMUM UNIT HEIGHT HAUTEUR D UNIT SEE DETAIL A VOIR D TAIL A BANDE SCELLANT DOIT TRE EN PLACE AVANT DE PLACER...

Страница 7: ...nd any other safety precautions that might apply Training for operators of the lifting equipment should include but not be limited to the following 1 Application of the lifter to the load and adjustme...

Страница 8: ...insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Con...

Страница 9: ...ied electrical disconnect switch and unit DO NOT USE ALUMINUM WIRE 3 Be sure that high voltage power to unit is within operating voltage range indicated on unit rating plate On 3 phase units ensure ph...

Страница 10: ...00 ft 30 5 m from the unit as measured along the control voltage wires use no 16 AWG color coded insulated 35 C minimum wires STANDARD CONNECTION Locate the seven eight for 3 phase low voltage thermos...

Страница 11: ...Motor HP RPM 800 10x10 254x254 1 2 1050 1000 10x10 254x254 1 2 1050 1150 11x10 279 4x254 3 4 1000 1350 11x10 279 4x254 1 2 1075 1550 11x10 279 4x254 1 0 1075 1750 11x10 279 4x254 1 0 1040 HIGH PRESSU...

Страница 12: ...essurized mixtures of air or gases containing oxygen can lead to an explosion WARNING Proceed as follows to locate and repair a refrigerant leak and to charge the unit 1 Locate leak and make sure that...

Страница 13: ...e is more than 2 F 1 1 C lower than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section INDOOR AIRFL...

Страница 14: ...l cap off of the desired speed tap wire Re fer to Table 3 for color coding 5 Connect the desired speed tap wire to the HIGH terminal on the interface fan board IFB UNIT OPERATION HAZARD Failure to fol...

Страница 15: ...ck CFM 1187 1124 1061 996 930 896 840 776 698 610 BHP 0 36 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 39 0 40 36 Low Blue CFM 1056 982 911 882 812 740 667 564 486 361 BHP 0 24 0 24 0 24 0 26 0 26 0 27 0 28...

Страница 16: ...0 82 0 78 0 74 0 69 60 Low Blue CFM 1330 1277 1232 1191 1147 1103 1060 1004 963 919 BHP 0 26 0 27 0 29 0 30 0 31 0 32 0 33 0 34 0 36 0 37 Med Low Pink CFM 1475 1436 1399 1351 1317 1270 1236 1188 1152...

Страница 17: ...02 1351 1311 1263 1224 1172 1136 1080 1041 Med Low Pink CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104 Medium 1 Red CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381 Med High Orange CFM 2149 2111 206...

Страница 18: ...66 0 64 0 63 0 61 0 59 High Black CFM 1560 1491 1416 1337 1255 1233 1160 1082 998 911 WATTS 708 699 683 674 660 634 624 606 581 566 BHP 0 76 0 75 0 73 0 72 0 71 0 68 0 67 0 65 0 62 0 61 42 Low Blue CF...

Страница 19: ...2 0 88 0 84 60 Low Blue CFM 1479 1436 1387 1346 1298 1253 1206 1160 1114 1061 WATTS 224 239 247 262 270 284 300 307 319 330 BHP 0 24 0 26 0 26 0 28 0 29 0 30 0 32 0 33 0 34 0 35 Med Low Pink CFM 1841...

Страница 20: ...600 1400CFM 12x20x1 12x20x1 305x508x25 305x508x25 2 0 2 5 3 0 0 09 0 14 0 16 0 18 0 25 0 28 0 3 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 5 4 0 0 10 0 11 0 12 0 13 0 14 0 16 0 16 1500 2200...

Страница 21: ...2 0 14 0 16 0 18 20 kW 0 00 0 00 0 02 0 04 0 06 0 08 0 09 0 11 0 13 0 15 0 17 0 19 Large Cabinet 42 60 STATIC STANDARD CFM SCFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 25...

Страница 22: ...22 A150503 Fig 12 Connection Wiring Diagram 208 230 1 60 707C C D...

Страница 23: ...23 A150513 Fig 12 Cont Ladder Wiring Diagram 208 230 1 60 707C C D...

Страница 24: ...24 A150504 Fig 13 Connection Wiring Diagram 208 230 3 60 707C C D...

Страница 25: ...25 A150514 Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 707C C D...

Страница 26: ...26 A150505 Fig 14 Connection Wiring Diagram 460 3 60 707C C D...

Страница 27: ...27 A150515 Fig 14 Cont Ladder Wiring Diagram 460 3 60 707C C D...

Страница 28: ...unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or adjust charge conditions must be favorable for subcooling charging Favorable conditio...

Страница 29: ...the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean c...

Страница 30: ...and condensate drain line when inspecting the coils Clean the drain pan and condensate drain by removing all foreign matter from the pan Flush the pan and drain trough with clear water Do not splash w...

Страница 31: ...of charge low airflow across indoor coil dirty filters etc It opens at 50 psig 957 Pa If system pressure is above this switch should be closed To check switch 1 Turn off all power to unit 2 Disconnect...

Страница 32: ...cause long term damage to some synthetic roofing materials Exposure even if immediately cleaned up may cause embrittlement leading to cracking to occur in one year or more When performing any service...

Страница 33: ...ompressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Deter...

Страница 34: ...sig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE synthetic oils S Vacuum pumps will not remove moisture...

Страница 35: ...INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL S...

Страница 36: ...ue or change at any time specifications or designs without notice and without incurring obligations E2019 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 11 19 R...

Отзывы: