background image

29

MAINTENANCE

To ensure continuing high performance, and to minimize the
possibility of premature equipment failure, periodic maintenance

must be performed on this equipment. This cooling unit should be
inspected at least once each year by a qualified service person. To

troubleshoot unit, refer to Table 8, Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer
about the availability of a maintenance contract.

PERSONAL

INJURY

AND

UNIT

DAMAGE

HAZARD

Failure to follow this warning could result in personal

injury or death and possible unit component damage.
The ability to properly perform maintenance on this

equipment requires certain expertise, mechanical skills,

tools and equipment. If you do not possess these, do not

attempt to perform any maintenance on this equipment,

other than those procedures recommended in the Owner’s

Manual.

!

WARNING

ELECTRICAL SHOCK AND FIRE HAZARD

Failure to follow these warnings could result in personal

injury or death:

1. Turn off electrical power to the unit and install lockout

tag before performing any maintenance or service on this
unit.

2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact

with the unit.

!

WARNING

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Errors made when reconnecting wires may cause improper

and dangerous operation. Label all wires prior to

disconnecting when servicing.

CAUTION

!

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect indoor coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel for cleanliness each

cooling season. Clean when necessary.

4. Check electrical connections for tightness and controls for

proper operation each cooling season. Service when
necessary.

5. Ensure electric wires are not in contact with refrigerant

tubing or sharp metal edges.

Air Filter

IMPORTANT

: Never operate the unit without a suitable air filter

in the return--air duct system. Always replace the filter with the
same dimensional size and type as originally installed. See Table 1
for recommended filter sizes.
Inspect air filter(s) at least once each month and replace

(throwaway--type) or clean (cleanable--type) at least twice during
each cooling season and twice during the heating season, or

whenever the filter becomes clogged with dust and lint.

Indoor Blower and Motor

NOTE

: All motors are pre--lubricated. Do not attempt to lubricate

these motors.
For longer life, operating economy, and continuing efficiency,

clean accumulated dirt and grease from the blower wheel and

motor annually.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Disconnect and tag electrical power to the unit before

cleaning the blower motor and wheel.

!

WARNING

To clean the blower motor and wheel:

1. Remove and disassemble blower assembly as follows:

a. Remove blower access panel (see Fig. 17).

b. Disconnect 5 pin plug and 4 pin plug from indoor

blower motor. Remove capacitor if required.

c. On all units remove blower assembly from unit.

Remove screws securing blower to blower partition and
slide assembly out. Be careful not to tear insulation in
blower compartment.

d. Ensure proper reassembly by marking blower wheel and

motor in relation to blower housing before disassembly.

e. Loosen setscrew(s) that secures wheel to motor shaft,

remove screws that secure motor mount brackets to
housing, and slide motor and motor mount out of

housing.

2. Remove and clean blower wheel as follows:

a. Ensure proper reassembly by marking wheel orientation.

b. Lift wheel from housing. When handling and/or

cleaning blower wheel, be sure not to disturb balance
weights (clips) on blower wheel vanes.

c. Remove caked--on dirt from wheel and housing with a

brush. Remove lint and/or dirt accumulations from
wheel and housing with vacuum cleaner, using soft

brush attachment. Remove grease and oil with mild
solvent.

d. Reassemble wheel into housing.

e. Reassemble motor into housing. Be sure setscrews are

tightened on motor shaft flats and not on round part of

shaft. Reinstall blower into unit.

f. Connect 5 pin plug and 4 pin plug to indoor blower

motor. Reinstall capacitor if required.

g. Reinstall blower access panel (see Fig. 17).

3. Restore electrical power to unit. Start unit and check for

proper blower rotation and motor speeds during cooling
cycles.

707C

--

--

(C

,D

)

Содержание 707C C Series

Страница 1: ...cal Controls and Wiring 30 Refrigerant Circuit 31 Evaporator Airflow 31 Puron Items 31 TROUBLESHOOTING 32 START UP CHECKLIST 32 A170030 Fig 1 Unit 707C C 707C D SAFETY CONSIDERATIONS Improper installa...

Страница 2: ...downflow panels before rigging and lifting into place The panel removal process may require the unit to be on the ground Step 2 Provide Unit Support IMPORTANT The unit must be secured to the curb by i...

Страница 3: ...3 A180287 Fig 2 24 36 Unit Dimensions 707C C D...

Страница 4: ...4 Fig 3 42 60 Unit Dimensions 707C C D...

Страница 5: ...6 778 46 1 1170 Large CPRFCURB013B00 14 356 14 356 43 9 1116 42 2 1072 Part Number CPRCURB011B00 can be used on both small and large basepan units The cross supports must be located based on whether...

Страница 6: ...PLACING UNIT ON ROOF CURB DUCTS DETAIL A VOIR D TAIL A MINIMUM HEIGHT 36 914 4 mm HAUTEUR MINIMUM UNIT HEIGHT HAUTEUR D UNIT SEE DETAIL A VOIR D TAIL A BANDE SCELLANT DOIT TRE EN PLACE AVANT DE PLACER...

Страница 7: ...nd any other safety precautions that might apply Training for operators of the lifting equipment should include but not be limited to the following 1 Application of the lifter to the load and adjustme...

Страница 8: ...insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Conditioning Contractors National Association SMACNA and Air Conditioning Con...

Страница 9: ...ied electrical disconnect switch and unit DO NOT USE ALUMINUM WIRE 3 Be sure that high voltage power to unit is within operating voltage range indicated on unit rating plate On 3 phase units ensure ph...

Страница 10: ...00 ft 30 5 m from the unit as measured along the control voltage wires use no 16 AWG color coded insulated 35 C minimum wires STANDARD CONNECTION Locate the seven eight for 3 phase low voltage thermos...

Страница 11: ...Motor HP RPM 800 10x10 254x254 1 2 1050 1000 10x10 254x254 1 2 1050 1150 11x10 279 4x254 3 4 1000 1350 11x10 279 4x254 1 2 1075 1550 11x10 279 4x254 1 0 1075 1750 11x10 279 4x254 1 0 1040 HIGH PRESSU...

Страница 12: ...essurized mixtures of air or gases containing oxygen can lead to an explosion WARNING Proceed as follows to locate and repair a refrigerant leak and to charge the unit 1 Locate leak and make sure that...

Страница 13: ...e is more than 2 F 1 1 C lower than required liquid line temperature NOTE If the problem causing the inaccurate readings is a refrigerant leak refer to Check for Refrigerant Leaks section INDOOR AIRFL...

Страница 14: ...l cap off of the desired speed tap wire Re fer to Table 3 for color coding 5 Connect the desired speed tap wire to the HIGH terminal on the interface fan board IFB UNIT OPERATION HAZARD Failure to fol...

Страница 15: ...ck CFM 1187 1124 1061 996 930 896 840 776 698 610 BHP 0 36 0 36 0 37 0 37 0 38 0 38 0 39 0 39 0 39 0 40 36 Low Blue CFM 1056 982 911 882 812 740 667 564 486 361 BHP 0 24 0 24 0 24 0 26 0 26 0 27 0 28...

Страница 16: ...0 82 0 78 0 74 0 69 60 Low Blue CFM 1330 1277 1232 1191 1147 1103 1060 1004 963 919 BHP 0 26 0 27 0 29 0 30 0 31 0 32 0 33 0 34 0 36 0 37 Med Low Pink CFM 1475 1436 1399 1351 1317 1270 1236 1188 1152...

Страница 17: ...02 1351 1311 1263 1224 1172 1136 1080 1041 Med Low Pink CFM 1457 1404 1367 1318 1284 1233 1197 1144 1104 Medium 1 Red CFM 1736 1695 1642 1601 1553 1512 1465 1427 1381 Med High Orange CFM 2149 2111 206...

Страница 18: ...66 0 64 0 63 0 61 0 59 High Black CFM 1560 1491 1416 1337 1255 1233 1160 1082 998 911 WATTS 708 699 683 674 660 634 624 606 581 566 BHP 0 76 0 75 0 73 0 72 0 71 0 68 0 67 0 65 0 62 0 61 42 Low Blue CF...

Страница 19: ...2 0 88 0 84 60 Low Blue CFM 1479 1436 1387 1346 1298 1253 1206 1160 1114 1061 WATTS 224 239 247 262 270 284 300 307 319 330 BHP 0 24 0 26 0 26 0 28 0 29 0 30 0 32 0 33 0 34 0 35 Med Low Pink CFM 1841...

Страница 20: ...600 1400CFM 12x20x1 12x20x1 305x508x25 305x508x25 2 0 2 5 3 0 0 09 0 14 0 16 0 18 0 25 0 28 0 3 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 5 4 0 0 10 0 11 0 12 0 13 0 14 0 16 0 16 1500 2200...

Страница 21: ...2 0 14 0 16 0 18 20 kW 0 00 0 00 0 02 0 04 0 06 0 08 0 09 0 11 0 13 0 15 0 17 0 19 Large Cabinet 42 60 STATIC STANDARD CFM SCFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 25...

Страница 22: ...22 A150503 Fig 12 Connection Wiring Diagram 208 230 1 60 707C C D...

Страница 23: ...23 A150513 Fig 12 Cont Ladder Wiring Diagram 208 230 1 60 707C C D...

Страница 24: ...24 A150504 Fig 13 Connection Wiring Diagram 208 230 3 60 707C C D...

Страница 25: ...25 A150514 Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 707C C D...

Страница 26: ...26 A150505 Fig 14 Connection Wiring Diagram 460 3 60 707C C D...

Страница 27: ...27 A150515 Fig 14 Cont Ladder Wiring Diagram 460 3 60 707C C D...

Страница 28: ...unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or adjust charge conditions must be favorable for subcooling charging Favorable conditio...

Страница 29: ...the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clean c...

Страница 30: ...and condensate drain line when inspecting the coils Clean the drain pan and condensate drain by removing all foreign matter from the pan Flush the pan and drain trough with clear water Do not splash w...

Страница 31: ...of charge low airflow across indoor coil dirty filters etc It opens at 50 psig 957 Pa If system pressure is above this switch should be closed To check switch 1 Turn off all power to unit 2 Disconnect...

Страница 32: ...cause long term damage to some synthetic roofing materials Exposure even if immediately cleaned up may cause embrittlement leading to cracking to occur in one year or more When performing any service...

Страница 33: ...ompressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor overload or start relay Deter...

Страница 34: ...sig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron as with other HFCs is only compatible with POE synthetic oils S Vacuum pumps will not remove moisture...

Страница 35: ...INDOOR EVAPORATOR AIR FILTER IS CLEAN AND IN PLACE VERIFY THAT UNIT INSTALLATION IS LEVEL CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL S...

Страница 36: ...ue or change at any time specifications or designs without notice and without incurring obligations E2019 Bryant Heating Cooling Systems D 7310 W Morris St D Indianapolis IN 46231 Edition Date 11 19 R...

Отзывы: