AIR CONDITIONER WITH PURON (R--410A) QUICK REFERENCE GUIDE
Puron refrigerant operates at 50--70 percent higher pressures than R--22. Be sure that servicing equipment and replacement components are
designed to operate with Puron. Puron refrigerant cylinders are rose colored.
S
Puron refrigerant cylinders manufactured prior to March 1, 1999, have a dip tube that allows liquid to flow out of cylinder in upright
position.
Cylinders manufactured March 1, 1999 and later DO NOT have a dip tube and MUST be positioned upside down to allow liquid to flow.
S
Recovery cylinder service pressure rating must be 400 psig. DOT 4BA400 or DOT BW400.
S
Puron systems should be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose.
S
Manifold sets should be minimum 700 psig high--side and 180 psig low--side with 550 psig low--side retard.
S
Use hoses with minimum 700 psig service pressure rating.
S
Leak detectors should be designed to detect HFC refrigerant.
S
Puron, as with other HFCs, is only compatible with POE synthetic oils.
S
Vacuum pumps will not remove moisture from oil.
S
Only use factory specified liquid--line filter driers with rated working pressures no less than 600 psig.
S
Do not install a suction--line filter drier in liquid line.
S
POE synthetic oils absorb moisture rapidly. Do not expose oil to atmosphere.
S
POE synthetic oils may cause damage to certain plastics and roofing materials.
S
Wrap all filter driers and service valves with wet cloth when brazing.
S
A Puron liquid--line filter drier is provided with every unit.
S
Do not use an R--22 TXV.
S
Never open system to atmosphere while it is under a vacuum.
S
When system must be opened for service, break vacuum with dry nitrogen and replace filter driers.
S
Always replace filter drier after opening system for service.
S
Do not vent Puron into the atmosphere.
S
Observe all warnings, cautions, and bold text.
S
Do not leave Puron suction line driers in place for more than 72 hrs.
707C
--
--
(C
,D
)
Содержание 707C C Series
Страница 3: ...3 A180287 Fig 2 24 36 Unit Dimensions 707C C D...
Страница 4: ...4 Fig 3 42 60 Unit Dimensions 707C C D...
Страница 22: ...22 A150503 Fig 12 Connection Wiring Diagram 208 230 1 60 707C C D...
Страница 23: ...23 A150513 Fig 12 Cont Ladder Wiring Diagram 208 230 1 60 707C C D...
Страница 24: ...24 A150504 Fig 13 Connection Wiring Diagram 208 230 3 60 707C C D...
Страница 25: ...25 A150514 Fig 13 Cont Ladder Wiring Diagram 208 230 3 60 707C C D...
Страница 26: ...26 A150505 Fig 14 Connection Wiring Diagram 460 3 60 707C C D...
Страница 27: ...27 A150515 Fig 14 Cont Ladder Wiring Diagram 460 3 60 707C C D...