49
To wire the return air enthalpy sensor, perform the
following:
1. Use a 2--conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the en-
thalpy controller.
2. Connect the field--supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(+) terminal on the enthalpy controller. Connect the
BLK wire to (--) spade connector on the return air en-
thalpy sensor and the (--) terminal on the enthalpy
controller.
Smoke Detectors
Smoke detectors are available as factory--installed options on
551J models. Smoke detectors may be specified for Supply
Air only or for Return Air without or with economizer or in
combination of Supply Air and Return Air. All components
necessary for operation are factory--provided and mounted.
The unit is factory--configured for immediate smoke detector
shutdown operation; additional wiring or modifications to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
Units equipped with factory--optional Return Air smoke
detectors require a relocation of the sensor module at unit
installation. See Fig. 61 for the as shipped location.
Completing Installation of Return Air Smoke Sensor:
1. Unscrew the two screws holding the Return Air
Smoke Detector assembly. See Fig. 62, Step 1. Save
the screws.
2. Turn the assembly 90 degrees and then rotate end to
end. Make sure that the elbow fitting is pointing
down. See Fig. 62, Step 2.
3. Screw the sensor and detector plate into its operating
position using screws from Step 1. See Fig. 62, Step 3.
4. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Return Air
Smoke Detector
(as shipped)
C12282
Fig. 61 -- Return Air Smoke Detector, Shipping Position
Additional Application Data —
Refer to the Application Data sheet titled
Factory
Installed Smoke Detectors for Small and Medium Rooftop
Units 2 to 25 Tons
for discussions on additional control
features of these smoke detectors including multiple unit
coordination.
Step 1
Step 2
Step 3
C12283
Fig. 62 -- Completing Installation of Return Air Smoke Sensor
Содержание 551J Series
Страница 4: ...4 C160142 Fig 2 Dimensional Drawing Sizes 07 09 ...
Страница 5: ...5 C160143 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Страница 6: ...6 C13302A Fig 3 Dimensional Drawing Sizes 11 and 12 ...
Страница 7: ...7 C13303A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Страница 39: ...39 a551J 006 Fig 41 RTU Open Controller Wiring Diagram ...
Страница 40: ...40 a551J 007 Fig 42 Typical RTU Open Controller Wiring Diagram Wiring Diagram with Perfect Humidityt System ...
Страница 53: ...53 ...