![Bryant 551J Series Скачать руководство пользователя страница 19](http://html.mh-extra.com/html/bryant/551j-series/551j-series_installation-instructions-manual_2822065019.webp)
19
different colors with minimum of seven leads. If the
thermostat does not require a 24--v source (no “C”
connection required), use a thermostat cable or equivalent
with minimum of six leads. Check the thermostat
installation instructions for additional features which
might require additional conductors in the cable.
Typical
Thermostat
Connections
Central
Terminal
Board
W1
Y2
Y1
R
W2
G
C
X
W1
Y2
Y1
R
W2
G
C
X
T–STAT
C
W2
G
W1
O/B/Y2
R
Y1
(Note 1)
Note 1: Typical multi-function marking. Follow manufacturer’s configuration
instructions to select Y2.
Note 2: W2 connection not required on units with single-stage heating.
Field Wiring
(Note 2)
C09351
Fig. 25 -- Typical Low--Voltage Connections
For wire runs up to 50 ft. (15 m), use no. 18 AWG
(American Wire Gage) insulated wire (35
_
C minimum).
For 50 to 75 ft. (15 to 23 m), use no. 16 AWG insulated
wire (35
_
C minimum). For over 75 ft. (23 m), use no. 14
AWG insulated wire (35
_
C minimum). All wire sizes
larger than no. 18 AWG cannot be directly connected to
the thermostat and will require a junction box and splice
at the thermostat.
Central Terminal Board —
The Central Terminal Board (CTB) is a pass through
connection point. The CTB provides the capability to add
factory--installed options and field--installed accessories to
the units by cutting jumper wires without having to change
or reroute wires through the structure of the unit. The CTB
does not provide any microprocessor control; it is simply a
basic multifunction wiring terminal configuration.
Unit Without Thru--Base Connection Kit —
Pass the thermostat control wires through the hole
provided in the corner post; then feed the wires through
the raceway built into the corner post to the control box.
Pull the wires over to the terminal strip on the upper--left
corner of the Central Terminal Board (CTB). See Fig. 25
and Fig. 26.
RACEWAY
HOLE IN END PANEL (HIDDEN)
C08027
Fig. 26 -- Field Control Wiring Raceway
NOTE
:
If thru--the--bottom connections accessory is
used, refer to the accessory installation instructions for
information on routing power and control wiring.
Heat Anticipator Settings —
Set heat anticipator settings at 0.14 amp for the first stage
and 0.14 amp for second--stage heating, when available.
Electric Heaters
551J units may be equipped with field--installed accessory
electric heaters. The heaters are modular in design, with
heater frames holding open coil resistance wires strung
through ceramic insulators, line--break limit switches and a
control contactor. One or two heater modules may be used in
a unit.
Heater modules are installed in the compartment below
the indoor (supply) fan outlet. Access is through the
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Fig. 27, Fig. 28 and Fig. 29.
DISCONNECT MOUNTING
LOCATION
UNIT BLOCK-OFF
PANEL
OUTDOOR
ACCESS PANEL
INDOOR
ACCESS
PANEL
C08133
Fig. 27 -- Typical Access Panel Location
Содержание 551J Series
Страница 4: ...4 C160142 Fig 2 Dimensional Drawing Sizes 07 09 ...
Страница 5: ...5 C160143 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Страница 6: ...6 C13302A Fig 3 Dimensional Drawing Sizes 11 and 12 ...
Страница 7: ...7 C13303A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Страница 39: ...39 a551J 006 Fig 41 RTU Open Controller Wiring Diagram ...
Страница 40: ...40 a551J 007 Fig 42 Typical RTU Open Controller Wiring Diagram Wiring Diagram with Perfect Humidityt System ...
Страница 53: ...53 ...