30
Table 7 -- Menu Structure
*
(cont)
Menu
Parameter
Parameter
Default
Value
Parameter
Range and Increment
[
EXPANDED PARAMETER NAME
Notes
ADVANCED
SETUP
(cont)
MAT T CAL
0.0
_
F
(or C)
+/---2.5
_
F
(+/---1.4
_
C)
SUPPLY AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration supply air
temperature (SAT) sensor
OAS T CAL
1.0
_
F
(or C)
+/---2.5
_
F
(+/---1.4
_
C)
OUTSIDE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration outside air
temperature (OAT) sensor
OAS H CAL
0% RH
+/---10% RH
OUTSIDE AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of outside air enthalpy sensor
RA T CAL
0.0
_
F
(or C)
+/---2.5
_
F
(+/---1.4
_
C)
RETURN AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration return air
temperature (RA) sensor
RA H CAL
0% RH
+/---10% RH
RETURN AIR HUMIDITY CALIBRATION
Allows for the operator to adjust for an out of calibration return air enthalpy
sensor
DA T CAL
0.0
_
F
(or C)
+/---2.5
_
F
(+/---1.4
_
C)
DISCHARGE AIR TEMPERATURE CALIBRATION
Allows for the operator to adjust for an out of calibration discharge air
temperature (DAT) sensor
2SP FAN DELAY
5 Minutes
0 to 20 minutes in
1 minute increments
TIME DELAY ON 2
nd
STAGE ECONOMIZING
When in economizing mode this is the delay for the high speed fan to try to
satisfy the call for second stage cooling before the first stage mechanical
cooling is enabled.
CHECKOUT
[[[
DAMPER OPEN
n/a
n/a
Positions damper to the full open position.
Exhaust fan contacts enable during the DAMPER OPEN test. Make sure
you pause in this mode to allow for exhaust contacts to energize due to the
delay in the system.
DAMPER CLOSE
n/a
n/a
Positions damper to the fully closed position
CONNECT Y1---O
n/a
n/a
Closes the Y1---O relay (Y1---O).
See
CAUTION
on page 37.
CONNECT Y2---O
n/a
n/a
Closes the Y2---O relay (Y2---O)
See
CAUTION
on page 37.
CONNECT AUX1---O
n/a
n/a
Energizes the AUX1---O output. If AUX1---O setting is:
S
NONE --- not action taken
S
ERV --- 24 Vac out. Turns on or signals an ERV that the conditions
are not good for economizing but are good for ERV operation.
[[
S
SYS --- 24 Vac out. Issues a system alarm.
CONNECT EXH1
n/a
n/a
Closes the power exhaust fan 1 relay (EXH1)
Содержание 551J Series
Страница 4: ...4 C160142 Fig 2 Dimensional Drawing Sizes 07 09 ...
Страница 5: ...5 C160143 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Страница 6: ...6 C13302A Fig 3 Dimensional Drawing Sizes 11 and 12 ...
Страница 7: ...7 C13303A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Страница 39: ...39 a551J 006 Fig 41 RTU Open Controller Wiring Diagram ...
Страница 40: ...40 a551J 007 Fig 42 Typical RTU Open Controller Wiring Diagram Wiring Diagram with Perfect Humidityt System ...
Страница 53: ...53 ...