15
Units With Electric Heat Option with Single Point Box
and Without Disconnect Option
L1
L2
L3
Single Point Box
Factory
Wiring
Equip GR
Lug
Ground (GR)
Terminal Block
— OR —
L1
L2
L3
BLK
YEL
BLU
BLK
YEL
BLU
Single Point Box
Factory
Wiring
Equip GR
Lug
Ground (GR)
Fuse/Terminal Block
Fuse
Fuse
Fuse
Disconnect
per
NEC
13
11
13
L1
L2
L3
C
IFC
208/230-3-60
460-3-60
575-3-60
Units Without Disconnect Option
Units With Disconnect Option
L3
L2
L1
L3
L2
L1
T3
T1
Optional
Disconnect
Switch
Disconnect factory test leads; discard.
Factory
Wiring
T2
BLU
BLK
YEL
Ground
(GR)
Equip
GR Lug
Equip GR Lug
Ground
(GR)
C12763
Fig. 16 -- Power Wiring Connections
Refer to Fig. 23 for power transformer connections and the
discussion on connecting the convenience outlet on page 17.
Field power wires are connected to the unit at line--side
pressure lugs on compressor contactor C and indoor fan
contactor IFC (see wiring diagram label for control box
component arrangement), at factory--installed option
non--fused disconnect switch. Max wire size is #4 AWG
(copper only) per pole on contactors and #2ga AWG (copper
only) per pole on optional non--fused disconnect. See Fig. 16
and the unit label diagram for field power wiring
connections.
NOTE
: TEST LEADS -- Unit may be equipped with short
leads (pigtails) on the field line connection points on
contactor C or optional disconnect switch. These leads are
for factory run--test purposes only; remove and discard
before connecting field power wires to unit connection
points. Make field power connections directly to line
connection pressure lugs only.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in
personal injury, death, or property damage.
Do not connect aluminum wire between disconnect
switch and 551J unit. Use only copper wire. (See Fig. 17.)
COPPER
WIRE ONLY
ELECTRIC
DISCONNECT
SWITCH
ALUMINUM
WIRE
A93033
Fig. 17 -- Disconnect Switch and Unit
Units With Factory--Installed Non--Fused Disconnect —
The factory--installed option non--fused disconnect (NFD)
switch is located in a weatherproof enclosure located
under the main control box (see Fig. 18). The manual
switch handle and shaft are shipped in the disconnect
enclosure. Assemble the shaft and handle to the switch at
this point. Discard the factory test leads (see Fig. 16).
Connect field power supply conductors to LINE side
terminals when the switch enclosure cover is removed to
attach the handle.
Содержание 551J Series
Страница 4: ...4 C160142 Fig 2 Dimensional Drawing Sizes 07 09 ...
Страница 5: ...5 C160143 Fig 2 Unit Dimensional Drawing Sizes 07 09 cont ...
Страница 6: ...6 C13302A Fig 3 Dimensional Drawing Sizes 11 and 12 ...
Страница 7: ...7 C13303A Fig 3 Unit Dimensional Drawing Sizes 11 and 12 cont ...
Страница 39: ...39 a551J 006 Fig 41 RTU Open Controller Wiring Diagram ...
Страница 40: ...40 a551J 007 Fig 42 Typical RTU Open Controller Wiring Diagram Wiring Diagram with Perfect Humidityt System ...
Страница 53: ...53 ...