background image

III.

HEAT EXCHANGER AND FLUE PIPE

Ordinarily, it is not necessary to clean heat exchanger or flue pipe
every year, but it is necessary to have your service technician
check unit before each heating season to determine whether
cleaning or replacement of parts is required.

If cleaning is necessary, the following steps should be performed:

1. Turn off all oil and electrical supplies upstream of furnace.

CAUTION:

If furnace has been in operation, some

surfaces may be hot. Allow time for unit to cool down.

2. Disconnect flue pipe.

3. Remove collar on flue connection.

4. Remove upper rear panel.

5. Remove flue collector box from secondary heat exchanger

tube flange. This exposes inside surfaces of secondary tubes
of heat exchanger.

6. Clean secondary tubes and flue pipe with a stiff brush and

vacuum cleaner.

7. If only secondary tubes need to be cleaned, no further

disassembly is required. Proceed to item 18 for reassembly.
If primary heat exchanger section is also to be cleaned
proceed to next item.

8. Disconnect limit control wires.

9. Disconnect oil line and remove oil burner from furnace.

10. Remove observation door.

11. Remove collar on observation tube.

12. Remove intermediate panel. Care must be taken not to bend

or damage limit control.

13. Loosen to hand tightness the 3 nuts labeled "A" in Fig. 4.

Remove screws labeled "B" in Fig. 4. Slide combustion
chamber forward out of heat exchanger. Be careful not to
bump combustion chamber as it becomes brittle after
having been fired.

14. Use a stiff brush and vacuum cleaner to clean inside of

primary drum.

CAUTION:

Never use incendiary type cleaners (smoke

sticks) for cleaning!

WARNING:

For all heat exchanger plates that have

been removed, the gaskets MUST be replaced. Failure to
replace gaskets could lead to heat exchanger leakage,
sooting, and a hazardous condition which could lead to
bodily harm.

15. Before reassembly, heat exchanger and combustion cham-

ber should be inspected to determine if replacement is
required. After cleaning, place combustion chamber back

into primary drum and secure with "B" screws. Use 35-45
lb-in. of torque. Ensure that cover plate gasket is in place
before tightening screws. Care must be taken not to damage
combustion chamber.

16. Tighten "A" nuts to 30 lb-in. of torque (firm, but not overly

tight).

17. Replace intermediate panel, observation tube collar, obser-

vation door, limit wiring, and oil burner.

18. Replace collector box on secondary tube flange, ensuring

proper placement of gasket. Tighten screws to 35-45 lb-in.
of torque.

19. Replace upper rear panel and flue collar.

20. Reconnect flue pipe and oil line(s) if removed.

21. Readjust burner for proper operation. Check limit operation

as outlined in Limit Control Check section.

IV.

BLOWER OILING AND REMOVAL

Periodic oiling of blower motor may be necessary. Check for
instructions on inside of blower access panel.

If it is ever necessary to remove blower from furnace, refer to Fig.
5 and perform the following:

1. Turn off all electrical power to furnace.

2. Remove louvered door and blower door.

3. Remove blower retaining screw (on blower partition panel

near corner where intermediate panel and blower partition
meet).

4. Remove cover from control box and disconnect thermostat

and power wires from board.

5. Remove 3 screws holding control box to blower partition.

6. Slide blower on rails toward front of unit until motor wire

connections at terminal block on motor can easily be
reached and disconnected.

7. Disconnect motor wires at terminal block on motor and then

disconnect 2 red wires connected to auxiliary limit control
mounted on opposite side of blower.

8. Swing control box out of way of blower and remove blower

from unit.

Fig. 4—Removing Combustion Chamber

A96398

A

B

Fig. 5—Removing Blower

A95486

REMOVE 3 SCREWS
TO REMOVE
JUNCTION BOX

BLOWER

RETAINER

SCREW

—9—


Содержание 363AAP

Страница 1: ...NITY OF THIS OR ANY OTHER APPLIANCE DO NOT ATTEMPT TO START THE BURNER WHEN EXCESS OIL HAS ACCUMULATED WHEN THE FURNACE IS FULL OF VAPOR OR WHEN THE COMBUSTION CHAMBER IS VERY HOT WARNING For use with...

Страница 2: ...r attic installation As this unit may be installed as an upflow or horizontal furnace it may be located in a basement on the same level as area to be heated suspended or in a crawlspace In any case un...

Страница 3: ...g openings Screens used shall not be smaller than 1 4 in mesh and shall be readily accessible for cleaning If free area through a design of louver or grille is known it shall be used in calculating si...

Страница 4: ...chimney is properly lined and sized per the applicable codes Refer to list of codes in Safety Consid erations section II MASONRY CHIMNEY This furnace can be vented into an existing masonry chimney Th...

Страница 5: ...humidifier connection See Fig 9 These terminals are energized with 115v 0 5 amp maximum during any call for heat FILTERS It is NECESSARY THAT ALL FURNACES BE EQUIPPED WITH A FILTER An external filter...

Страница 6: ...SCREW FILTER RACK FILTER ACCESS PANEL REAR OF FURNACE BASE PANEL FLUSH WITH REAR OF FURNACE SIDE FILTER RACK ALIGNMENT FILTER RACK BOTTOM FILTER RACK REAR PANEL REST FLANGE ON TOP OF BOTTOM PANEL FLA...

Страница 7: ...ed with damper The draft regulator should be adjusted after furnace has been firing for at least 10 minutes and stack draft should be measured and set between 0 025 and 0 035 in wc The draft should be...

Страница 8: ...User s Manual FAILURE TO FOLLOW THIS WARNING COULD RESULT IN POSSIBLE DAMAGE TO THIS EQUIPMENT SERIOUS PER SONAL INJURY OR DEATH WARNING Before performing any service functions unless operations spec...

Страница 9: ...dous condition which could lead to bodily harm 15 Before reassembly heat exchanger and combustion cham ber should be inspected to determine if replacement is required After cleaning place combustion c...

Страница 10: ...reduces efficiency of your system causes erratic performance of controls and could result in damage to motor or heating equipment 1 Inspect filters at regular intervals depending upon dirt conditions...

Страница 11: ...0 7 0 8 0 9 1 0 060210 High 2485 2395 2305 2250 2145 2075 1975 1885 1780 1675 Medium 2195 2125 2060 1990 1915 1860 1785 1700 1620 1525 Low 1640 1590 1540 1515 1460 1410 1350 1275 1190 1075 NOTES 1 Air...

Страница 12: ...DUCT CLEANOUT PORTS CLEANOUT PORTS A96336 DIMENSIONS IN UNIT SIZE UNIT DIMENSIONS DUCT SUPPLY OPENING FLUE DIAMETER SIDE RETURN OPENING END BOTTOM RETURN OPENING SIDE RETURN DUCT SIZE END BOTTOM RETUR...

Страница 13: ...Fig 8 Barometric Damper Locations A95117 FIG A FIG G FIG D FIG L FIG B FIG C FIG J FIG H FIG K POOR WRONG WRONG WRONG WRONG WRONG BAROMETRIC DAMPER LOCATIONS GOOD LOCATIONS BAD LOCATIONS 13...

Страница 14: ...ING MUST CONFORM TO CURRENT CSA 22 1 CANADIAN ELECTRICAL CODE PART 1 AND OR LOCAL CODES 3 IF ANY OF THE ORIGINAL WIRE AS SUPPLIED WITH THE FURNACE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATE...

Страница 15: ...fore attempting to put your furnace into operation for the heating season you should perform the following procedures WARNING If you do not follow these instructions exactly a fire or explosion may re...

Страница 16: ...eo based formats and materials All include video and or slides plus companion book Classroom Service Training plus hands on the products in our labs can mean increased confidence that really pays divi...

Отзывы: