TABLE 3—AIRFLOW DATA (CFM)
UNIT
SIZE
BLOWER
SPEED
EXTERNAL STATIC PRESSURE IN. WC
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.0
060210
High
2485
2395
2305
2250
2145
2075
1975
1885
1780
1675
Medium
2195
2125
2060
1990
1915
1860
1785
1700
1620
1525
Low
1640
1590
1540
1515
1460
1410
1350
1275
1190
1075
NOTES: 1. Airflow values in cubic ft per minute (CFM) rounded to nearest 5 CFM.
2. Data taken without filters in place.