background image

8

Outdoor Fan Motor Operation

The outdoor unit control (Fig. 9) energizes outdoor fan anytime

compressor is operating as needed during low--ambient cooling
operation. The outdoor fan remains energized if a pressure switch

opens or compressor scroll over temperature should occur. This
OD fan is an ECM motor which operates at varying speeds

depending on the ambient and the demand.

Time Delays

The unit time delays include:

S

Five minute time delay to start cooling operation when there is a
call from the wall control. To bypass this feature, momentarily
short and release Forced Defrost pins.

S

Five minute compressor re--cycle delay on return from a
brown--out condition.

S

See Tab le 7 for other delay information.

General Information

Evolution Controlled low ambient cooling:

This unit is capable of low ambient cooling down to 0

_

F

(--17.8

_

C) with Low Ambient enabled on the Evolution wall

control. A low ambient kit is not required.
The Evolution Control provides an automatic evaporator coil
freeze protection algorithm that eliminates the need for an

evaporator freeze thermostat. The only accessory that may be
required is wind baffles in locations which are likely to experience

cross winds in excess of 5 miles an hour. This generally occurs

only on roof and open area applications.
Low ambient cooling must be enabled in the wall control setup.

The outdoor unit fan will cycle on and off based on outdoor coil
temperature, outdoor air temperature, and suction pressure

measurements to keep the compressor running at the proper
conditions.

Utility Interface With Evolution Wall Control

The utility curtailment relay should be wired between the two

UTIL connections on the control board for this Evolution
Communicating System (see Fig. 16). This input allows a power

utility device to interrupt compressor operation during peak load

periods. When the utility sends a signal to shut the system down,
the User Interface will display, ”Curtailment Active”. See wall

control installation instructions for setup details.

Communication and Status Function Lights

Evolution Control, Green Communications (COMM)Light

A green LED

(COMM light)

on the outdoor board (see Fig. 9)

indicates successful communication with the other system

products. The green LED will remain OFF until communication is
established. Once a valid command is received, the green LED will

turn ON continuously. If no communication is received within 2

minutes, the LED will be turned OFF until the next valid
communication.

Amber Status Light

Amber colored

STATUS light

indicates operation and error status.

See Table 7 for definitions.

S

Two minute time delay to return to standby operation from last
valid communication.

S

One minute time delay of outdoor fan at termination of cooling
mode when outdoor ambient is greater than or equal to 100

_

F

(37.8

_

C).

STATUS
LED

COMM
LED

A11139

Fig. 9 -- Variable Speed Control Board

Step 12 — Check Charge
Charge in CHARGING mode

Factory charge amount and desired subcooling are shown in the
user interface (UI). To properly check or adjust charge, conditions

must be favorable for subcooling charging in cooling mode.

Favorable conditions exist when the outdoor temperature is
between 65

_

F and 100

_

F (18

_

C and 38

_

C), and the indoor

temperature is between 70

_

F and 80

_

F (21

_

C and 27

_

C). If the

temperatures are outside of these ranges, weigh--in charge only. If

confirmation is needed return and check subcooling when the
temperatures are within the desired range.

Charging Procedure

: Unit is factory charged for 15ft (4.57 m) of

lineset and for smallest rated indoor coil combinations. If any
refrigerant charge adjustment is required based on the indoor coil

combination and the line set length input, the wall control will
calculate and display the target subcooling and the amount of

additional charge to be added. Therefore wall control is the source

of information for charging the system correctly. Refrigerant
charge adjustment amount for adding or removing 0.6 oz/ft (17.74

g/m) of 3/8 liquid line above or below 15ft (4.57 m) respectively,
and an additional amount of refrigerant charge adjustment (2 lbs)

for a large ID coil if required, is calculated and displayed by the

wall control.
Perform a final charge check when OD is between 65

F (18

C)

and 100

F (38

C).

If the range is acceptable, go to the CHARGING screen on the wall

control. Set the wall control to check the charge in cooling mode.
Allow system to operate in cooling mode for the stabilization

period as indicated on the wall control. Once conditions are

indicated as favorable and stable by the wall control, check the
system charge by subcooling method. Compare the subcooling

taken at the liquid service valve to the subcooling target (target
service valve subcool) listed on the charging screen.

Add

refrigerant if the subcooling is low and remove charge if

subcooling is high. Tolerance should be

2

F.

If any adjustment is necessary, add or remove the charge slowly

(no greater than 0.5 lb per minute) and allow system to operate for
15 minutes to stabilize before declaring a properly charged system.
The use of a commercial charge metering device (restrictor) such as

Imperial

liquid low side charger model 535--C or

Watsco

ChargeFaster model CH200 is recommended when adding

refrigerant to an operating system. This prevents potential damage
of liquid slugging of the compressor and allows the subcooling to

stabilize quicker.

Содержание 180CNV024

Страница 1: ...distributor or branch for information or assistance The qualified installer or agency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions...

Страница 2: ...susceptible to lineset transmitted noise inside the dwelling and in extreme cases tubing breakage CAUTION INSTALLATION RECOMMENDATIONS In some cases noise in the living area has been traced to gas pu...

Страница 3: ...shipment is damaged or incomplete Locate unit rating plate on unit corner panel It contains information needed to properly install unit Check rating plate to be sure unit matches job specifications St...

Страница 4: ...ft 24 38 m substantial capacity and performance losses can occur Follow the pipe sizing recommendations in the 180CNV Product data to manage these losses Refer to Table 1 for field tubing diameters Re...

Страница 5: ...heck should include all field and factory joints Evacuate Refrigerant Tubing and Indoor Coil CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operat...

Страница 6: ...r has an internal crankcase heater Furnish power to the unit a minimum of 24 hr before starting the unit for the first time To furnish power to heater only set thermostat to OFF and close electrical d...

Страница 7: ...e energized to run at lowest cooling demand If this does not satisfy cooling demand the system will ramp up in stages until it satisfies the demand After coping with the higher demand the unit returns...

Страница 8: ...ons S Two minute time delay to return to standby operation from last valid communication S One minute time delay of outdoor fan at termination of cooling mode when outdoor ambient is greater than or e...

Страница 9: ...th the control board and drives the compressor to the demanded RPM When the contactor closes it powers the inverter with line voltage The inverter changes the line voltage to 410 volts DC 3 phase and...

Страница 10: ...n 187v for at least 4 seconds the contactor and fan relay are de energized Compressor and fan operation are not allowed until voltage is a minimum of 190v The control will flash the appropriate fault...

Страница 11: ...e CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation In order to minimize the ambient influence make sure the thermistor curved surface hugs...

Страница 12: ...long flashes indicating the second digit of the error code The short flash is 0 25 seconds ON and the long flash is 1 0 second ON Time between flashes is 0 25 seconds Time between short flash and firs...

Страница 13: ...1 BRN RED SEC1 SEC2 PWM2 PWM1 INVERTER PL1 PL2 RVS CC PL11 PL4 PL6 OCT OAT SPT OST A B C NO USE UTIL LS Y C O COMM STATUS YEL BLU EXV PL5 PL3 HPS Utility Interface A11544 Fig 16 Variable Speed Control...

Страница 14: ...14 Table 7 Troubleshooting...

Страница 15: ...ld hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pre...

Страница 16: ...iscontinue or change at any time specifications or designs without notice and without incurring obligations E2017 Bryant Heating Cooling Systems 7310 W Morris St Indianapolis IN 46231 Edition Date 12...

Отзывы: