1.
Loosen tube-ends. Insert tube puller between the tube-end and header. Apply pressure to the
puller and strike the side of the tube two or three times with a hammer to help loosen the tube-
end in the upper and lower header.
2.
Pull lower tube end. Wedge the tube puller under the flange of the tube. Drive the tube puller
with several blows with a hammer on the end of the handle. Alternate with downward blows to
lift tube-end.
3.
Clear tube-end from the header. Continue driving wedge under and leveraging flange up until it
pops the end of the tube free from the hole in the header.
4.
Pull upper tube-end. Repeat the procedure to the pull the tube-end of the same tube from the
upper header.
Figure 9: Tube Puller Insertion
5.
Prepare the headers and replacement tubes. Before placing a new tube into the header, clean
the holes by wiping gently with emery cloth to be sure that there are no burrs. Clean the
replacement tube-ends of any rust or debris. With a small brush, apply a thin coating of gray
pipe dope around the inside of the hole. Pipe dope may also be applied to the tube-end. Cutting
oil may be mixed with the pipe dope for easier application.