Combined Overcurrent /
Combined Overcurrent /
Combined Overcurrent /
Combined Overcurrent / Earth Fault Relay
Earth Fault Relay
Earth Fault Relay
Earth Fault Relay and Voltage Monitoring
and Voltage Monitoring
and Voltage Monitoring
and Voltage Monitoring
True R.M.S. measurements
Low Set and High Set tripping thresholds for both Overcurrent and Earth Fault detection
6 selectable IDMT (Inverse Definite Minimum Time) characteristic curves or adjustable DT (Definitive Time)
Three phase over current and earth fault detection with live display of individual phase and earth fault currents
Last trip memory (last 10 trips stored and can be recalled)
Pre-defined selectable CT ratio’s (5:5….6000:5)
Display of measured phase to neutral or phase to phase voltages
Display of measured frequency, power, power factor and hours run
Microprocessor based (self checking) with non-volatile memory
“Ecosmart” Energy efficient power supply design
Rear mounted pluggable connectors for supply, relay contacts and current inputs
•
OPERATION & OVERVIEW
The
P9690
P9690
P9690
P9690
(from the P9600 series family of IDMT/DT relays) is a microprocessor based relay
designed to monitor and detect Overcurrent on individual phases and non-directional Earth faults (by
measurement of the neutral current) in 3-phase applications. Typically the
P9690
P9690
P9690
P9690
is wired in
conjunction with external current transformers of the feeder to be protected.
In addition, the
P9690
P9690
P9690
P9690
is also able to measure and display, phase to neutral or phase to phase
voltages along with the system frequency. It can also calculate the power factor and power for each
phase. Finally, it will indicate total hours for as long as it remains powered. Note that tripping of this
product only occurs on Overcurrent or Earth faults. It will not trip due to voltage or power issues.
A clear backlit LCD provides all key information the user requires for both operation and setting up.
Setting is achieved in a few simple steps and requires no previous knowledge of product operation.
Normal operation provides the user with actual live individual phase currents and earth fault current
all on one screen. The actual phase current represents that of the current passing through the
primary side of the externally connected CT’s. This is achieved by the setting of the ratio for the CT.
Programming mode allows the user to assign the operation mode for both internal relays. They can
be individually assigned to Overcurrent, Earth fault or a combination of both. They can also be
configured for Auto or Manual resetting. Relay 2 has the added option of being allowed to energise
at the start or end of a time out period. If assigned to energise at the start, the Relay can be used to
operate a buzzer or lamp giving early warning before a system actually shuts down.
Low-set and High-set thresholds can be programmed for both Overcurrent and Earth fault
detection. The time current characteristic of the low-set units are selectable between Normal
Inverse curve 3/10, Normal Inverse curve 1.3/10, Long Time Inverse curve, Very Inverse curve,
Extremely Inverse curve, Extremely Inverse 0.65 curve and Definite Time. High-set units are the
Definitive Time type. Instantaneous tripping is possible by setting the time to minimum.
Two simple Summary screens are displayed once the programming is complete. The same screens
can also be displayed by presses of the
“RESET”
button. This allows the user to access key
information with the tamperproof transparent cover closed and sealed.
A Test mode is provided (also accessible with tamperproof cover closed) to confirm the correct
operation of the internal relays. The relays will energise when the
“TEST”
button is pressed and de-
energise when the button is released (AUTO Reset) or when the
“RESET”
button is pressed (MAN
Reset).
Following a trip condition, the information about the trip is then stored. This can then be recalled
later if required using the
“RESET”
button to access the information. The
P9690
P9690
P9690
P9690
has the ability to
store up to 10 trips and using the “Up” and “Down” buttons, allows each trip to be displayed
individually. Each trip is also marked with a time stamp showing the time from power up as well as
the time from the previous trip. This feature is very useful for establishing a pattern on particular
inputs, knowing when they occurred and how frequent!
•
FUNCTION OVERVIEW
Programming mode.
Programmable parameters
User settings summary mode
1
Summary screens are split into two with one screen showing Overcurrent settings and the
other showing Earth fault settings.
2
Displaying of the Summary screens during normal operation is achieved via subsequent
presses of the “RESET” button. See Section 8. QUICK VIEW OF USER SETTINGS
for further information.
•
PRESENTATION
1. LCD (Liquid Crystal Display) for user information 5.
“MODE”
button*
2.
“RESET”
button 6. Parameter increment button*
3.
“TEST”
button 7. Parameter decrement button*
4.
“Power supply”
green LED indication 8.
“Trip status”
red LED indication
* accessible only when the front cover is open
START
TOROID RATIO
Set ratio of externally
connected toroids
NETWORK
FREQUENCY
Set for 50 or 60Hz
connected toroids
RELAY 1 SETTING
Assign monitoring function
and set reset mode method
RELAY 2 SETTING
Assign monitoring function,
relay activation and reset
mode methods
OVERCURRENT
SETTING
Set Low-set and High-set
tripping parameters
EARTH FAULT
CURRENT SETTING
Set Low-set and High-set
tripping parameters
SUMMARY
1
List all parameter and
function settings
START
Display live individual
phase currents and
earth fault current
SUMMARY
1 2
List all parameter and
function settings
I
L1
0.00
A
I
L2
0.00
A
I
L3
0.00
A
I
O
0.00
A
Dims:
W x H. 96 x 96mm (front)
W x H. 89.5 x 89.5mm (main body)
L. 100mm