Installation and Operation Manual
X-DPT-DeviceNet-SLA5800-SLAMf-Series-RevB-PC-eng
Part Number: 541B200AAG
March, 2015
23
Section 4 - Configuration
Brooks DeviceNet PCs
4.1.9.2. Valve Override
1
The following table outlines the valid valve override types.
Table 4-8 Valve Override Values
Value Sate
Description
0
Normal
Valve is under normal operational control
1
Closed
Valve is driven fully closed
2
Open
Valve is driven fully open
3
Hold
Valve is held to last updated value prior to assertion of override
4
Safe State
Valve is driven to the condition specified by Safe State
4.1.10. Pressure Control Group
2
Table 4-9 Supported Pressure Control Parameters
EDS Parameter
Values
Description
EPATH
Pressure Control Data Type
3,
4
Appendix B - Data Type
Definitions
The data type associated with the value of
Setpoint.
[0x33-1-3]
Pressure Control Data
Units
3
See “Pressure Units
Table” in Appendix C -
Data Units
The engineering units associated with
Setpoint.
[0x33-1-4]
Pressure Control Constant
Time Ramp Rate
0 to 86400000 msec
Sets the time the controller will take to move
from the current position to the new setpoint
position
[0x33-1-19]
Pressure Control Derivative
Gain
-3.4e38 to 3.4e38
The value of the Derivative gain of the PID
controller
[0x33-1-101]
Pressure Control Integral
Gain
-3.4e38 to 3.4e38
The value of the Integral gain of the PID
controller
[0x33-1-102]
Pressure Control
Proportional Gain
-3.4e38 to 3.4e38
The value of the Proportional gain of the PID
controller
[0x33-1-103]
1
This Override action only occurs when the device is in the Executing State.
2
Available for Pressure Controllers Only.
3
This parameter is only configurable when the device is in the Idle State (i.e. when the device is not being actively scanned/polled).
4
This parameter will automatically be set based upon the inferred data type of the selected Assembly used for I/O (i.e. if an Assembly is
selected that contains Setpoint as one of its data members, and the inferred data type of the assembly is INT, then this attribute will be
automatically set to INT once I/O data exchange begins).