15
2.4 Where in the room?
The locations must comply with applicable building regulations
In a room
WITH
a fuel burning appliance
- The CO alarm should be a horizontal
distance of between 1m and 3m from the
potential CO source
- If there is a partition in the room, the CO
Alarm should be located on the same side of
the partition as the potential source.
Ceiling Mounted
If it is mounted on the ceiling it should be at
least 300mm from any wall or light fitting.
In rooms with sloped ceilings, the CO Alarm
should be located at the high side of the room.
Wall Mounting (EIB3018 only)
If ceiling mounting is impractical, ONLY the
EIB3018 CO Alarm can be mounted on a wall.
It should be located at a height greater than
the height of any door or window but still be
at least 150mm from the ceiling.
300mm
150mm
1 to 3 m
1 to 3 m
DEAD AIR
DON'T LOCATE
HERE
CO Alarm
Fig.1
300m
m
CO Alarm
Fig.2