5
Your ventilation system is equipped with a heat recovery core that is designed specifically to control
excess humidity and reduce ventilation costs by recovering the heat energy from the exhausted air,
and using that same heat energy to warm the fresh air being supplied. This heat recovery process
is accomplished in such a way that the stale air is never mixed with the fresh air.
1.3 R
ECOVERY
E
XAMPLE
(
IN
WINTER
)
VF0026
OUTDOOR
S
INDOOR
When the outdoor temperature is below -5°C (23°F), heat recovery creates frost in the module.
To maintain proper operation, the unit is programmed to defrost the recovery module. The defrost
frequency varies according to the outdoor temperature. Defrost lasts 7 minutes (or 10 minutes if set
on “Extented Defrost”). During the defrost cycle, the unit shifts to maximum speed and the dampers
close.
After defrosting, the unit returns to the operating mode selected by the user.
1.4 D
EFROST
M
ODE
M
ODEL
HRV150FL
HRV190FL
W
IDTH
30¼"
30¼"
H
EIGHT
16½"
16½"
D
EPTH
171∕
8
"
171∕
8
"
W
EIGHT
65
LB
. (29.5
KG
)
65
LB
. (29.5
KG
)
E
LECTRICAL
SUPPLY
120 V, 60 H
Z
120 V, 60 H
Z
P
OWER
CONSUMPTION
160
WATTS
195
WATTS
1.5 S
PECIFICATIONS
Stale air to outdoors
6°C/42°F
Fresh air from outdoors
0°C/32°F
Fresh air to building
16°C/61°F
Stale air from building
22°C/72°F