Steady amber – fan assembly has a failure (full or partial).
–
Slow-flashing amber (on 2 seconds, then off 2 seconds) – fan assembly is not seated correctly or is faulty.
–
Fast-flashing amber (on ½ second, then off ½ second) – environmental range exceeded.
•
Enter
fanShow
. If the status of the fan assembly displays absent or faulty, check if the assembly is seated in the
chassis. If it is seated, the power supply could be faulty or is not receiving power for some reason.
•
Enter
sensorShow
to determine if a fan is running above average temperatures of other installed fan(s).
•
Enter
errDump
to display the system error log.
For more information on LED operation, see
Interpreting Fan Assembly LEDs
.
For output examples and additional information on Fabric OS commands, see
and the
Brocade Fabric OS Command Reference Manual
.
For more information about error messages, refer to the
Brocade Fabric OS Message Reference Manual
.
Fan Assembly Task Guide
This section addresses the steps for installing or replacing fan assemblies when the chassis is running (hot-swap) or must
be powered off (cold-swap). References are provided for more details on removal and installation steps.
NOTE
Each fan assembly contains three fans for a total of six fans for three installed fan assemblies. The chassis
requires five fans out of six functioning fans for operation. If hot-swapping a fan assembly, be sure to have the
replacement fan assembly ready to install before removing a faulty fan assembly, and replace it as soon as
possible.
NOTE
If a fan assembly has failed, do not remove it from the chassis unless an FRU is available for replacement. If the
slot is left empty for an extended time period, chassis air leakage and overheating can occur.
NOTE
Make sure that captive screws that secure fan assemblies to the chassis are tightened. If the screws are not
tightened, high pressure from fan operation may unseat the fan from chassis connectors.
Replacing a Fan Assembly (Hot-Swap)
NOTE
The fans must be in the same direction as before.
If your chassis is up and running, but a fan assembly has failed, complete the following steps:
1. Remove the fan assembly.
2. Insert the new fan assembly into the empty slot as soon as possible, and securely tighten the captive screw.
3. Verify that the fan assembly status LED is green.
Replacing a Fan Assembly (Cold-Swap)
If your chassis is up and running, but you want to power down the chassis to replace a failed fan assembly, complete the
following steps:
1. Shut down the system using the
sysShutdown
command.
2. Unplug the power cords from the receptacles on all power supply assemblies.
3. Loosen the captive screw and remove the faulty fan assembly.
4. Insert the new fan assembly and securely tighten the captive screw.
5. Plug the power cords into all power supply assemblies from the power sources to the power on the chassis.
6. Verify that the fan assembly status LEDs are green.