ARCHITECTURAL AND ENGINEERING SPEC

TECHNICAL SPECS

SHIPPING SPECS

INSTALLATION OF ALARM

The combination smoke and CO alarm shall be a BRK Model SC9120B and shall provide at 

a minimum the following features and functions:

1.   An ionization smoke sensing chamber and an electrochemical CO sensor both with a 

10 year service life.

2.   Powered by 120V AC, 60Hz and have a monitored 9V battery backup and a solid state 

piezo horn rated at 85dB at 10 ft. and be capable of self restoring.

3.  The unit shall perform self diagnostic tests and issue a malfunction warning (three 

chirps) if the unit malfunctions.

4.  The unit shall have an “End of Life” signal (5 chirps). This signal should be capable of 

temporarily being silenced for up to 2 days. After about 2 days, the signal will resume. 

After about 2-3 weeks the signal cannot be silenced.

5.   A visual power-on indicator to confirm unit is receiving AC power or has switched to 

battery backup mode. Separate LED ‘s to indicate a smoke or CO alarm.

6.  The CO sensor is adjusted not to detect CO levels below 30 PPM and will not alarm 

when exposed to constant levels of 30 PPM for 30 days. It will alarm at the following 

levels: 400 PPM CO between 4 and 15 minutes, 150 PPM CO between 10 and 50 

minutes and 70 PPM CO between 60 and 240 minutes.

7.  Two Latching features: Alarm Latch to easily identify initiating alarm after alarm 

condition has subsided. Low battery latch: to visually identify which unit is in low 

battery condition. Two Silence Features: Alarm Silence to temporarily silence nuisance 

alarms. Low Battery Silence to silence low battery chirp for up to 8 hours.

8.  Two Locking features - tamper resistant locking pins that lock battery drawer  

and/or alarm to mounting bracket.

9.  The unit shall be capable of operating between 40°F (4°C) and 100°F (38°C) and 

relative humidity between 10% and 95%.

10.  The unit shall have a plug in connector and be capable of interconnection of up to 18 

alarms, 12 of which can be smoke alarms.

11.  The unit shall at a minimum meet the requirements of UL217 and UL2034, CSFM, 

NFPA 72 and 720 and the ICC.

Alarm Dimensions:   5.6”dia. x 2.0”H
Weight:  

8.5 oz

Operating Voltage:  

120V AC 60Hz w/ 9V alkaine battery backup 

Operating Current: 

0.09 amps (standby/alarm)

Temperature Range:   40°F (4°C) to 100°F (38°C)
Humidity Range: 

10% to 95% relative humidity (RH)

Audio Alarm: 

85dB at 10 feet

Test/Silence: 

Electronically simulates smoke or CO condition, causing the  

 

unit to alarm. Press and hold test/silence button.

Alarm Reset: 

Automatic when smoke or CO clears

Interconnections: 

Up to 18 units of First Alert or BRK Smoke, CO and Heat  

 

Alarms. Maximum of 12 smoke alarms. See user’s manual  

 

for details.

Smoke Sensor: 

Dual Ionization 

CO Sensor: 

Electrochemical

Indicator Lights/Sounds: 
   AC Power:  

Constant Green LED 

   DC Power:  

Intermittent Green LED  

   Local Alarm:  

Red LED flashes rapidly 

   Remote Alarm:  

Red LED out.  

   Latching Alarm:  

Red LED flashes 2 sec. on/2 sec. off after local alarm 

   Low Battery Latch:  Green LED flashes on for 2 seconds, off for 2 seconds.
Listing: 

Listed to UL217 and UL2034 Standards

Individual Carton Dimensions  

5.69”L x 2.25”W x 5.59”H 

   Weight  

0.63 lbs. 

   Cube  

0.04 ft3 

   UPC  

0 29054 51306 9 

Master Carton Dimensions  

14.43”L x 6.19”W x 12.63”H 

Master Pack 

12   

   Weight  

8.1 lbs. 

   Cube:  

0.65 ft3 

   I2of5:  

100 29054 51306 6 

Pallet Information  

 

   Cases per Layer 

19 

   Number of Layers:  

3  

   Cases per Pallet:  

57 

   Units per Pallet:  

684 

   Cube:  

42.2 ft3 

   Weight:  

527 lbs.

©2015 BRK Brands, Inc. a Jarden Corporation 

Company (NYSE: JAH)

3901 Liberty Street Road

Aurora, IL  60504-8122

All rights reserved 
First Alert is a registered trademark of the First Alert Trust

BRK is a registered trademark of BRK Brands, Inc.

CM3233

brkelectronics.com

Installation of this smoke alarm must conform to all local electrical 

codes and Article 760 of the National Electrical Code (NFPA 70) and 

NFPA 72. Interconnected units must meet the following requirements: 

Total length of wire interconnecting units should be less than 1000 feet, 

be #18 gauge or larger and be rated at least 300V. It is recommended 

that all units be on the same fuse or circuit breaker. If local codes 

do not permit, be sure the neutral wire is common to both phases.

THE PARTS OF THIS SMOKE ALARM

1.  Mounting bracket
2.  Mounting Slots
3.  Locking Pins 
4.  Hot (Black) AC Wire
5.  Nuetral (White) AC Wire
6.  Interconnect (Orange) Wire
7.  Battery Drawer Latch
8.  Battery Drawer - Install 9V 

battery here

9.  Quick-Connect Plug

MOUNTING

BRACKET

TOP VIEW

SIDE VIEW

5.6”

2.0”

1

2

3

5

6

4

2

3

9

7

8

678

43

1

5

2

A

B

}

}

43

1

5

1.  Smoke /CO Alarm 
2.  Ceiling or Wall 
3.  Power Connector 
4.  Wire Nut

5.  Junction Box
6.  Neutral Wire (White)
7.  Interconnect Wire (Orange)
8.  Hot Wire (Black)

A. 

Unswitched 120VAC 60 Hz source

B. 

To additional units; Maximum = 18 total 
(Maximum 12 Smoke Alarms)