2.0 Service, Maintenance and Warranty
To ensure continuing high performance and to minimise the possibility of premature equipment failure, periodic
maintenance should be performed on the air conditioning equipment. It is recommended the unit be maintained by a
qualified person as follows:
The minimum maintenance requirements for this equipment are as follows:
Monthly
•
Inspect and clean Return Air Filters.
•
Replace throwaway type filters when they become clogged with dust and lint or clean cleanable type filters
monthly
Yearly
•
Inspect indoor coil, internal drip tray and condensate drain. Clean when necessary
•
Inspect the heater’s fan motor and wheel for cleanliness and alignment. Clean and align the motor assembly
where applicable
•
Inspect outdoor coil. Clean when necessary.
•
Inspect the outdoor unit. Ensure air flow is not disturbed by any obstacle around it.
•
Inspect outdoor fans and motors. Ensure that fan blades are clean and adequately balanced
•
Inspect the unit cabinet and insulation for damage and corrosion. Repair where necessary. Check for vibration
and excessive noise. Correct where necessary
•
Inspect refrigerant tubing for oil accumulations. If oil is detected, leak test refrigerant tubing using an electronic
leak detector or liquid soap solution
•
Check refrigerant charge by measurement of superheat and sub cooling. Where necessary, adjust charge to
achieve optimum performance
•
Check the tightness of electrical connections
2.1 Brivis Customer Care Program
Brivis products are renowned for providing years of trouble free performance. To be at their most efficient performance, like
most things, they need a little care. So to ensure that every Brivis unit is always in perfect condition we have established
the Brivis Care Program for our valued customers.
When you are a member of our Care Program you will receive a courtesy contact regarding maintenance service to your
unit. This service includes cleaning the unit and ensuring that the system is operating at maximum efficiency. Not only does
this guarantee peak performance, it also allows any minor problems to be detected early. This ensures that the system will
always be ready when you need it.
Note:
When cleaning the internal drip tray the discharge duct must be removed for access.