Breezair TBQ Скачать руководство пользователя страница 16

16 

 |   

ILL1014-I

ILL976-D

REFITTING THE PAD FRAMES

Refit the pad frames by locating the bottom edge in the tank 

groove, then push the top into the lid.

TESTING THE PUMP

Test the pump by turning the cooler on at the MagIQtouch 

Controller, in “COOL” mode. Check that water is evenly 

distributed to all pads. 

Note!

 If the cooler has not been on before it will run a “Pre-Wet” 

routine where the pump will operate to saturate the pads.  

This cycle takes 2 minutes, then the fan will start automatically.

TESTING THE DRAIN VALVE (WHERE FITTED)

Select the “SETTINGS” mode on the MagIQtouch Controller 

and select the “COOLER” sub-heading.

Select the “MANUAL DRAIN” option to operate and test the 

drain valve.

COMMISSIONING THE COOLER

TEST OPERATION

Check that the green light on the electronics module is on and 

double flashing every 2 seconds. This indicates that power is 

connected to the electronics module. 

Important!

 Ensure the flexible splash protection cover is put 

back in place.

FAULT CODES INDICATED BY LED’s ON 

THE ELECTRONICS MODULE

Fault Code 01 (1 Red Flash) = Communication Failure.

• 

Ensure the wall control cable is fitted correctly.

•  Check that wall control cable is in good condition.

Fault Code 02 (2 Red Flashes) = Failure to detect water at 

probes within 8 minutes.

• 

Ensure water pressure is sufficient to fill and maintain the tank 

to specified level within 8 minutes. 

•  In areas of hard or polluted water, blockage of the strainer/

filter in the water inlet solenoid valve may restrict water flow. 

•  Water level set too low. For Breezair coolers the water level 

should be set to 5mm / 3/16” below the float valve base. 

•  Ensure probe plug is properly connected.
•  Plug connections at electronic module upside down or 

misaligned. 

•  Water too pure for the probes to sense water is present.
•  Pressure build up in pipes can lock up the solenoid valve 

when a non-return isolation valve is used in the water supply 

line. It is recommended to use a ball valve, i.e. NOT a non-

return type of shut off valve.

•  Check drain valve is closing and not cycling due to debris 

being caught under drain valve washer.

Fault Code 04 (4 Red Flashes) = Failure to clear probes 

during drain within 4 minutes (where drain valve fitted).

•  Check the drain valve opens and water drains from the tank, 

with nothing obstructing the outflow of water. (e.g. drain hose 

kinked)

•  Excessive drain hose lengths or bends cause air locking and 

won’t allow water to drain.

•  Build up of foreign material in drain hose not allowing water to 

drain away correctly.

• 

Screws used to fix drain hoses to drain adaptors restricting 

water from draining from tank.

•  Drain valve has failed to open when drain was initiated.
•  Inlet water solenoid not shutting off water when the drain is 

open.

• 

Water will only flow one way through the inlet water solenoid 

valve. Therefore, it must be installed correctly. Directional 

arrow must be pointing towards the float valve assembly. If 

not, water will not shut off. (Directional arrow can be found on 

the bottom of the solenoid valve body). 

•  Debris interfering with water sensor probes. 
•  Probes not clipped onto mounting brackets correctly.
•  Check cooler is level and water drains quickly.

Fault Code 07 (7 Red Flashes) = Incorrect supply frequency 

(Hz).

This fault will only be seen when the mains power supply 

frequency deviates from normal frequency by more than 8%. 

Mains power supply frequency should be 50 or 60Hz. See 

nameplate for exact data for this air cooler. Petrol/gasoline 

generators are the most likely cause of this type of fault. This 

typically will not occur on mains power supplies.

Содержание TBQ

Страница 1: ...INSTALLATION MANUAL TBQ TBS Evaporative Cooler Original English Instructions ...

Страница 2: ...THE FLOAT VALVE 12 MAINS WATER CONNECTION 12 INSTALLING THE VENTURI FAN ASSEMBLY 13 ELECTRICAL CONNECTION 13 CONNECTING THE WATER PUMP 14 CONNECTING THE MAGIQTOUCH CONTROLLER 15 MAGIQTOUCH CONTROLLER DISPLAY INFORMATION 15 SETTING THE WATER LEVEL 15 SETUP FOR BLEED FUNNEL 15 FAULT CODES INDICATED BY LED s ON THE ELECTRONICS MODULE 16 COMMISSIONING THE COOLER 16 COMMISSIONING COMPLETION CHECKLIST 1...

Страница 3: ...ss it just is a matter of looking at the job to be done and considering what action s are necessary so the person doing the job does not injure themselves SAFETY cont This should be considered in terms of What are the chances of an incident happening What could the possible consequence be What can you do to reduce or better still completely eliminate the risk Some points to consider What is the be...

Страница 4: ...Guide Step 21 FINAL CHECK Complete the commissioning checklist at the end of this document Step 2 COOLER LOCATION Check cooler location Consider regulations Discuss with customer Step 8 CHECK WEATHER DAMPER Check operation of the weatherdamper Ensure weatherdamper moves freely Step 13 INSTALL DRAIN VALVE Where provided Never drain waste water directly onto the roof Be sure to use supplied O Rings ...

Страница 5: ...duit and terminate in the junction box Step 16 INSTALL VENTURI FAN Ensure the venturi is fully located into the tank and the motor lead is not caught or pinched Step 6 MOUNT DROPPER Position level and secure the dropper Flash the dropper to prevent water ingress into the roof cavity Step 12 LOCAL REGULATIONS Read and adhere to local electrical and plumbing rules and regulations Step 17 ELECTRICAL ...

Страница 6: ... not between the antenna and the transmission tower that is providing the television signal to the home Allow adequate access to and around the cooler for maintenance Provision must be made for access to electricity water supplies and drains Note Do you need to discuss the installation of items like safety anchor points with the customer ILL1150 A ILL1155 C ILL1155 C Lift the venturi and fan assem...

Страница 7: ...eeds 43m s 141fps In exposed or very high wind areas use 16 screws minimum shank diameter 5 2mm 7 32 to secure the dropper In areas subject to windstorms hurricanes or where the cooler is located more than 8m 26 above the ground seek advice from a structural engineer The dropper may now be flashed to the roof Make sure there is no chance of water entering the roof space SECURING THE DROPPER TRANSI...

Страница 8: ...ecured objects are removed beforehand WEATHER DAMPER Break off both clips on the transition that retain the weatherdamper Ensure that the weatherdamper flaps open all the way and do not interfere with the dropper or any screws The flaps should move freely through 90º Important There must be no obstructions to the weatherdamper opening fully as it will adversely affect the performance of the cooler...

Страница 9: ...e and control cable Pass the taped end of the wall control cable through the conduit adaptor factory fitted in the transition and leave about 0 5m 20 in the water tank Take the power cable and drop the non plug end down the hole where the electronics module was and pass it through the conduit adaptor Important Pass the wall control cable through the conduit first Lock the power cable socket in pla...

Страница 10: ...re that the water pipe connection does not place sideways strain onto the float valve Important In areas subject to freezing the water supply line to the cooler requires a drain down facility at the lowest point in the water supply pipe Important Flush the water pipe to remove any swarf before final fitting Swarf can lodge in the solenoid and float valve preventing them from functioning correctly ...

Страница 11: ...NT You have the choice of installing a water management system including a drain valve water sensor and inlet solenoid or a bleed funnel Both systems provide overflow and water drain features however the water management system is also designed to actively reduce salt and mineral deposits in the air cooler INSTALLING THE BLEED FUNNEL ALTERNATIVE The bleed funnel is a simplified alternative to the ...

Страница 12: ...ed funnel option a 3 4 to 1 2 BSP adaptor is to be fitted with the washer to the extension tube as shown Connect the main water supply to the water inlet point under the air cooler using the 1 2 BSP Nut and olive fitting or 1 2 BSP 1 4 brass compression adaptor fitting as required Always install a shut off valve do not use a non return type valve close by the air cooler ILL972 C ILL985 E INSTALLIN...

Страница 13: ...ank Failure to do this may result in the cable being caught between the outside of the bracket and the venturi B NOTE Ensure the steel restraint cable and motor cable are secured against the side of the venturi by the sticker ELECTRICAL CONNECTION Connect the motor cable to the base of the electronics module It is a polarised plug and will only insert one way Ensure it is secured fully so that its...

Страница 14: ...NING Do not run the pump while the pad frames are off and the fan is on Once plugs are connected switch the electronics module on Important Ensure the flexible splash protection cover is in place ILL1061 C ILL1095 B LEGEND A Control Cable B Speed Adjustment C Inlet Solenoid D Water Sensor or Shorting Plug E Drain Valve F Pump G Operation Fault code LED s Ensure the cables cannot rest in the water ...

Страница 15: ... disconnect the pump making sure the plug is kept away from any water Turn the power back on ILL1663 A Once the water level is correct isolate the control box and connect the pump plug CONNECTING THE MAGIQTOUCH CONTROLLER Refer to the installation manual provided with the MagIQtouch Controller for instructions on installing the controller The wall control cable plugs into the electronics module A ...

Страница 16: ...ronic module upside down or misaligned Water too pure for the probes to sense water is present Pressure build up in pipes can lock up the solenoid valve when a non return isolation valve is used in the water supply line It is recommended to use a ball valve i e NOT a non return type of shut off valve Check drain valve is closing and not cycling due to debris being caught under drain valve washer F...

Страница 17: ...egulations and is wired back to the distribution board on its own separate circuit CHECK CABLES Cables have been correctly connected to the control boxes Power supply Motor cable Control cable Drain valve Solenoid cable Pump cable Probe cable where fitted OWNER INSTRUCTIONS The owner has been instructed how they can electrically isolate the unit at the meter box in case of an emergency DUCTWORK NO...

Страница 18: ...nity Measurement replaces water when Salinity level reaches set point Timed Drain drains Tank After 8 tank fill cycles or every 1 2 hours system dependant No Drain Control salinity control external to electronics eg continuous bleed No Water Thermostatic allows Thermostatic control in VENT mode No water present Cooling performance is limited WEATHER SEAL OPEN SPEED The cooler fan will turn on at t...

Страница 19: ...y Check fault condition via the tri colour LED on cooler electronics module Rectify fault as indicated and restart the cooler MagIQtouch Controller failure Replace MagIQtouch Controller Pump runs but no water circulation or Pump runs but pads lack water Insufficient water in tank Adjust float level Water hoses blocked Check and clean out blockage Pump strainer blocked Clean pump strainer Insuffici...

Страница 20: ...model selected AU 1502 864655 A MANUFACTURED BY SEELEY INTERNATIONAL PTY LTD 112 O SULLIVAN BEACH RD LONSDALE SA 5160 AUSTRALIA IMPORTED BY SEELEY INTERNATIONAL EUROPE LTD 5 PAPPLEWICK LANE HUCKNALL NOTTINGHAM NOTTINGHAMSHIRE NG15 7TN UNITED KINGDOM SEELEY INTERNATIONAL AMERICAS LTD 1202 NORTH 54TH AVENUE BUILDING 2 SUITE 117 PHOENIX ARIZONA 85043 USA Service All regions Please contact your local ...

Отзывы: