WATER REQUIREMENTS

Installation of the cooler water supply must conform to  

local plumbing rules, regulations and standards.

The following specifications for the cooler water 

 

supply are required:
Water Connection

 ½

 BSP

Min Water Pressure

 

100kPa / 15psi

Max Water Pressure

 

800kPa / 115psi

Min Water Flow

 

8 liters/min / 2.1 gallons/min

Max Water Temperature 

40°C / 104°F

Important! 

If the water pressure exceeds maximum 

specification then a pressure reducing valve is required and 

must be supplied and fitted by the installer.
A permanent water supply is required to be connected to the float 

valve. The water connection point is located on the underside of 

the cooler. 

You must install a manual 1/4 turn ball type shut off valve (do not 

use a stop cock) in the water supply line adjacent to the cooler, 

subject to local plumbing regulations. This allows the water 

supply to be isolated whenever work needs to be done on the 

cooler.

The water connection is a 1/2” BSP compression fitting or a 1/2” 

BSP to 1/4” compression fitting on the end of a flexible hose. 

This can fit directly onto the water pipe or be screwed directly 

onto the manual water shut-off valve as required.

Always ensure that the water pipe connection does not place 

sideways strain onto the float valve.

Important!

 In areas subject to freezing, the water supply line 

to the cooler requires a drain down facility at the lowest point in 

the water supply pipe. 

Important!

 Flush the water pipe to remove any swarf before 

final fitting. Swarf can lodge in the solenoid and float valve, 

preventing them from functioning correctly.

ELECTRICAL REQUIREMENTS

Installation of the cooler must conform to local electrical rules, 

regulations and standards.

Important!

 It is a requirement of Seeley International that all 

Breezair coolers be connected to a dedicated circuit to the 

distribution board, with a separate circuit breaker and incorporate 

a separate isolation switch in accordance with the local wiring 

rules and the National Electric Code.

The following specifications for the cooler electrical supply are 

required:

230V / 50Hz, 60Hz Single Phase (see nameplate for exact 

data for this cooler)

The electronics module is fitted with a 12A re-settable circuit 

breaker. To reset the circuit breaker turn off the isolation switch, 

remove the electronics module and push the manual reset 

toggle switch located underneath the electronics module.

WARNING!

 If the supply cord is damaged, it must be replaced 

by the manufacturer, its service agent or similarly qualified 

persons in order to avoid a hazard.

ILL1898-A

Содержание TBQ

Страница 1: ...INSTALLATION MANUAL TBQ TBS Evaporative Cooler Original English Instructions ...

Страница 2: ...THE FLOAT VALVE 12 MAINS WATER CONNECTION 12 INSTALLING THE VENTURI FAN ASSEMBLY 13 ELECTRICAL CONNECTION 13 CONNECTING THE WATER PUMP 14 CONNECTING THE MAGIQTOUCH CONTROLLER 15 MAGIQTOUCH CONTROLLER DISPLAY INFORMATION 15 SETTING THE WATER LEVEL 15 SETUP FOR BLEED FUNNEL 15 FAULT CODES INDICATED BY LED s ON THE ELECTRONICS MODULE 16 COMMISSIONING THE COOLER 16 COMMISSIONING COMPLETION CHECKLIST 1...

Страница 3: ...ss it just is a matter of looking at the job to be done and considering what action s are necessary so the person doing the job does not injure themselves SAFETY cont This should be considered in terms of What are the chances of an incident happening What could the possible consequence be What can you do to reduce or better still completely eliminate the risk Some points to consider What is the be...

Страница 4: ...Guide Step 21 FINAL CHECK Complete the commissioning checklist at the end of this document Step 2 COOLER LOCATION Check cooler location Consider regulations Discuss with customer Step 8 CHECK WEATHER DAMPER Check operation of the weatherdamper Ensure weatherdamper moves freely Step 13 INSTALL DRAIN VALVE Where provided Never drain waste water directly onto the roof Be sure to use supplied O Rings ...

Страница 5: ...duit and terminate in the junction box Step 16 INSTALL VENTURI FAN Ensure the venturi is fully located into the tank and the motor lead is not caught or pinched Step 6 MOUNT DROPPER Position level and secure the dropper Flash the dropper to prevent water ingress into the roof cavity Step 12 LOCAL REGULATIONS Read and adhere to local electrical and plumbing rules and regulations Step 17 ELECTRICAL ...

Страница 6: ... not between the antenna and the transmission tower that is providing the television signal to the home Allow adequate access to and around the cooler for maintenance Provision must be made for access to electricity water supplies and drains Note Do you need to discuss the installation of items like safety anchor points with the customer ILL1150 A ILL1155 C ILL1155 C Lift the venturi and fan assem...

Страница 7: ...eeds 43m s 141fps In exposed or very high wind areas use 16 screws minimum shank diameter 5 2mm 7 32 to secure the dropper In areas subject to windstorms hurricanes or where the cooler is located more than 8m 26 above the ground seek advice from a structural engineer The dropper may now be flashed to the roof Make sure there is no chance of water entering the roof space SECURING THE DROPPER TRANSI...

Страница 8: ...ecured objects are removed beforehand WEATHER DAMPER Break off both clips on the transition that retain the weatherdamper Ensure that the weatherdamper flaps open all the way and do not interfere with the dropper or any screws The flaps should move freely through 90º Important There must be no obstructions to the weatherdamper opening fully as it will adversely affect the performance of the cooler...

Страница 9: ...e and control cable Pass the taped end of the wall control cable through the conduit adaptor factory fitted in the transition and leave about 0 5m 20 in the water tank Take the power cable and drop the non plug end down the hole where the electronics module was and pass it through the conduit adaptor Important Pass the wall control cable through the conduit first Lock the power cable socket in pla...

Страница 10: ...re that the water pipe connection does not place sideways strain onto the float valve Important In areas subject to freezing the water supply line to the cooler requires a drain down facility at the lowest point in the water supply pipe Important Flush the water pipe to remove any swarf before final fitting Swarf can lodge in the solenoid and float valve preventing them from functioning correctly ...

Страница 11: ...NT You have the choice of installing a water management system including a drain valve water sensor and inlet solenoid or a bleed funnel Both systems provide overflow and water drain features however the water management system is also designed to actively reduce salt and mineral deposits in the air cooler INSTALLING THE BLEED FUNNEL ALTERNATIVE The bleed funnel is a simplified alternative to the ...

Страница 12: ...ed funnel option a 3 4 to 1 2 BSP adaptor is to be fitted with the washer to the extension tube as shown Connect the main water supply to the water inlet point under the air cooler using the 1 2 BSP Nut and olive fitting or 1 2 BSP 1 4 brass compression adaptor fitting as required Always install a shut off valve do not use a non return type valve close by the air cooler ILL972 C ILL985 E INSTALLIN...

Страница 13: ...ank Failure to do this may result in the cable being caught between the outside of the bracket and the venturi B NOTE Ensure the steel restraint cable and motor cable are secured against the side of the venturi by the sticker ELECTRICAL CONNECTION Connect the motor cable to the base of the electronics module It is a polarised plug and will only insert one way Ensure it is secured fully so that its...

Страница 14: ...NING Do not run the pump while the pad frames are off and the fan is on Once plugs are connected switch the electronics module on Important Ensure the flexible splash protection cover is in place ILL1061 C ILL1095 B LEGEND A Control Cable B Speed Adjustment C Inlet Solenoid D Water Sensor or Shorting Plug E Drain Valve F Pump G Operation Fault code LED s Ensure the cables cannot rest in the water ...

Страница 15: ... disconnect the pump making sure the plug is kept away from any water Turn the power back on ILL1663 A Once the water level is correct isolate the control box and connect the pump plug CONNECTING THE MAGIQTOUCH CONTROLLER Refer to the installation manual provided with the MagIQtouch Controller for instructions on installing the controller The wall control cable plugs into the electronics module A ...

Страница 16: ...ronic module upside down or misaligned Water too pure for the probes to sense water is present Pressure build up in pipes can lock up the solenoid valve when a non return isolation valve is used in the water supply line It is recommended to use a ball valve i e NOT a non return type of shut off valve Check drain valve is closing and not cycling due to debris being caught under drain valve washer F...

Страница 17: ...egulations and is wired back to the distribution board on its own separate circuit CHECK CABLES Cables have been correctly connected to the control boxes Power supply Motor cable Control cable Drain valve Solenoid cable Pump cable Probe cable where fitted OWNER INSTRUCTIONS The owner has been instructed how they can electrically isolate the unit at the meter box in case of an emergency DUCTWORK NO...

Страница 18: ...nity Measurement replaces water when Salinity level reaches set point Timed Drain drains Tank After 8 tank fill cycles or every 1 2 hours system dependant No Drain Control salinity control external to electronics eg continuous bleed No Water Thermostatic allows Thermostatic control in VENT mode No water present Cooling performance is limited WEATHER SEAL OPEN SPEED The cooler fan will turn on at t...

Страница 19: ...y Check fault condition via the tri colour LED on cooler electronics module Rectify fault as indicated and restart the cooler MagIQtouch Controller failure Replace MagIQtouch Controller Pump runs but no water circulation or Pump runs but pads lack water Insufficient water in tank Adjust float level Water hoses blocked Check and clean out blockage Pump strainer blocked Clean pump strainer Insuffici...

Страница 20: ...model selected AU 1502 864655 A MANUFACTURED BY SEELEY INTERNATIONAL PTY LTD 112 O SULLIVAN BEACH RD LONSDALE SA 5160 AUSTRALIA IMPORTED BY SEELEY INTERNATIONAL EUROPE LTD 5 PAPPLEWICK LANE HUCKNALL NOTTINGHAM NOTTINGHAMSHIRE NG15 7TN UNITED KINGDOM SEELEY INTERNATIONAL AMERICAS LTD 1202 NORTH 54TH AVENUE BUILDING 2 SUITE 117 PHOENIX ARIZONA 85043 USA Service All regions Please contact your local ...

Отзывы: