Breezair TBQ Скачать руководство пользователя страница 15

TBQ/TBS EVAPORATIVE COOLER INSTALLATION MANUAL  

|  

15

 

ILL1714-A

ILL1615-A

SETTING THE WATER LEVEL 

cont

Turn on the mains water supply to the cooler. 
Turn the cooler on at the Controller, in “COOL” mode.
Adjust set temperature slider to be close to current room 

temperature so that fan speed remains low.

Allow the tank (reservoir) to fill with water. The float valve will 

eventually stop the water from entering the cooler. Wait for this 

to happen and check the water level.

ILL998-D

If the level is too high rotate the float clockwise. Drain some 

water from the tank and allow it to refill to the new set point. 

 

If too low rotate the float in an anti-clockwise direction. The 

correct water level is approximately 5mm / 3/16” below the 

surface of the tank the float valve is mounted on. It is advisable 

to check the water level again after the float valve washer has 

“bedded in”.

Cooler operating information is available from the ‘Service 

Operating Screen’ under the COOLER tab of the SETTINGS 

menu.

SETTING THE WATER LEVEL

Isolate power to the cooler electronics and disconnect the 

pump, making sure the plug is kept away from any water. Turn 

the power back on. 

ILL1663-A

Once the water level is correct, isolate the control box and 

connect the pump plug.

CONNECTING THE MAGIQTOUCH 

CONTROLLER

®

Refer to the installation manual provided with the MagIQtouch 

Controller for instructions on installing the controller.

The wall control cable plugs into the electronics module - (A). 

(Refer diagram on previous page)

Coolers are supplied with a 20m / 66’ control cable. Longer 

cable lengths are available from Seeley.

Note!

 Where maximum recommended cable lengths are 

exceeded, or cables are not routed in accordance with Seeley 

recommendations, Seeley technical support may not be 

available and the product warranty may be voided.

MAGIQTOUCH CONTROLLER

®

 DISPLAY 

INFORMATION

Diagnosis and cooler operating information can also be viewed 

from the MagIQtouch Controller. Faults are displayed on the 

screen as they occur.

ILL997-C

ILL1664-A

SETUP FOR BLEED FUNNEL

If you installed the bleed funnel instead of the drain valve then 

the cooler will automatically be set to “NO DRAIN CONTROL” 

provided that the shorting plug is installed correctly.
The “NO DRAIN CONTROL” setting can also be set manually 

under the “COOLER” tab in the “WATER MANAGER” menu.

Содержание TBQ

Страница 1: ...INSTALLATION MANUAL TBQ TBS Evaporative Cooler Original English Instructions ...

Страница 2: ...THE FLOAT VALVE 12 MAINS WATER CONNECTION 12 INSTALLING THE VENTURI FAN ASSEMBLY 13 ELECTRICAL CONNECTION 13 CONNECTING THE WATER PUMP 14 CONNECTING THE MAGIQTOUCH CONTROLLER 15 MAGIQTOUCH CONTROLLER DISPLAY INFORMATION 15 SETTING THE WATER LEVEL 15 SETUP FOR BLEED FUNNEL 15 FAULT CODES INDICATED BY LED s ON THE ELECTRONICS MODULE 16 COMMISSIONING THE COOLER 16 COMMISSIONING COMPLETION CHECKLIST 1...

Страница 3: ...ss it just is a matter of looking at the job to be done and considering what action s are necessary so the person doing the job does not injure themselves SAFETY cont This should be considered in terms of What are the chances of an incident happening What could the possible consequence be What can you do to reduce or better still completely eliminate the risk Some points to consider What is the be...

Страница 4: ...Guide Step 21 FINAL CHECK Complete the commissioning checklist at the end of this document Step 2 COOLER LOCATION Check cooler location Consider regulations Discuss with customer Step 8 CHECK WEATHER DAMPER Check operation of the weatherdamper Ensure weatherdamper moves freely Step 13 INSTALL DRAIN VALVE Where provided Never drain waste water directly onto the roof Be sure to use supplied O Rings ...

Страница 5: ...duit and terminate in the junction box Step 16 INSTALL VENTURI FAN Ensure the venturi is fully located into the tank and the motor lead is not caught or pinched Step 6 MOUNT DROPPER Position level and secure the dropper Flash the dropper to prevent water ingress into the roof cavity Step 12 LOCAL REGULATIONS Read and adhere to local electrical and plumbing rules and regulations Step 17 ELECTRICAL ...

Страница 6: ... not between the antenna and the transmission tower that is providing the television signal to the home Allow adequate access to and around the cooler for maintenance Provision must be made for access to electricity water supplies and drains Note Do you need to discuss the installation of items like safety anchor points with the customer ILL1150 A ILL1155 C ILL1155 C Lift the venturi and fan assem...

Страница 7: ...eeds 43m s 141fps In exposed or very high wind areas use 16 screws minimum shank diameter 5 2mm 7 32 to secure the dropper In areas subject to windstorms hurricanes or where the cooler is located more than 8m 26 above the ground seek advice from a structural engineer The dropper may now be flashed to the roof Make sure there is no chance of water entering the roof space SECURING THE DROPPER TRANSI...

Страница 8: ...ecured objects are removed beforehand WEATHER DAMPER Break off both clips on the transition that retain the weatherdamper Ensure that the weatherdamper flaps open all the way and do not interfere with the dropper or any screws The flaps should move freely through 90º Important There must be no obstructions to the weatherdamper opening fully as it will adversely affect the performance of the cooler...

Страница 9: ...e and control cable Pass the taped end of the wall control cable through the conduit adaptor factory fitted in the transition and leave about 0 5m 20 in the water tank Take the power cable and drop the non plug end down the hole where the electronics module was and pass it through the conduit adaptor Important Pass the wall control cable through the conduit first Lock the power cable socket in pla...

Страница 10: ...re that the water pipe connection does not place sideways strain onto the float valve Important In areas subject to freezing the water supply line to the cooler requires a drain down facility at the lowest point in the water supply pipe Important Flush the water pipe to remove any swarf before final fitting Swarf can lodge in the solenoid and float valve preventing them from functioning correctly ...

Страница 11: ...NT You have the choice of installing a water management system including a drain valve water sensor and inlet solenoid or a bleed funnel Both systems provide overflow and water drain features however the water management system is also designed to actively reduce salt and mineral deposits in the air cooler INSTALLING THE BLEED FUNNEL ALTERNATIVE The bleed funnel is a simplified alternative to the ...

Страница 12: ...ed funnel option a 3 4 to 1 2 BSP adaptor is to be fitted with the washer to the extension tube as shown Connect the main water supply to the water inlet point under the air cooler using the 1 2 BSP Nut and olive fitting or 1 2 BSP 1 4 brass compression adaptor fitting as required Always install a shut off valve do not use a non return type valve close by the air cooler ILL972 C ILL985 E INSTALLIN...

Страница 13: ...ank Failure to do this may result in the cable being caught between the outside of the bracket and the venturi B NOTE Ensure the steel restraint cable and motor cable are secured against the side of the venturi by the sticker ELECTRICAL CONNECTION Connect the motor cable to the base of the electronics module It is a polarised plug and will only insert one way Ensure it is secured fully so that its...

Страница 14: ...NING Do not run the pump while the pad frames are off and the fan is on Once plugs are connected switch the electronics module on Important Ensure the flexible splash protection cover is in place ILL1061 C ILL1095 B LEGEND A Control Cable B Speed Adjustment C Inlet Solenoid D Water Sensor or Shorting Plug E Drain Valve F Pump G Operation Fault code LED s Ensure the cables cannot rest in the water ...

Страница 15: ... disconnect the pump making sure the plug is kept away from any water Turn the power back on ILL1663 A Once the water level is correct isolate the control box and connect the pump plug CONNECTING THE MAGIQTOUCH CONTROLLER Refer to the installation manual provided with the MagIQtouch Controller for instructions on installing the controller The wall control cable plugs into the electronics module A ...

Страница 16: ...ronic module upside down or misaligned Water too pure for the probes to sense water is present Pressure build up in pipes can lock up the solenoid valve when a non return isolation valve is used in the water supply line It is recommended to use a ball valve i e NOT a non return type of shut off valve Check drain valve is closing and not cycling due to debris being caught under drain valve washer F...

Страница 17: ...egulations and is wired back to the distribution board on its own separate circuit CHECK CABLES Cables have been correctly connected to the control boxes Power supply Motor cable Control cable Drain valve Solenoid cable Pump cable Probe cable where fitted OWNER INSTRUCTIONS The owner has been instructed how they can electrically isolate the unit at the meter box in case of an emergency DUCTWORK NO...

Страница 18: ...nity Measurement replaces water when Salinity level reaches set point Timed Drain drains Tank After 8 tank fill cycles or every 1 2 hours system dependant No Drain Control salinity control external to electronics eg continuous bleed No Water Thermostatic allows Thermostatic control in VENT mode No water present Cooling performance is limited WEATHER SEAL OPEN SPEED The cooler fan will turn on at t...

Страница 19: ...y Check fault condition via the tri colour LED on cooler electronics module Rectify fault as indicated and restart the cooler MagIQtouch Controller failure Replace MagIQtouch Controller Pump runs but no water circulation or Pump runs but pads lack water Insufficient water in tank Adjust float level Water hoses blocked Check and clean out blockage Pump strainer blocked Clean pump strainer Insuffici...

Страница 20: ...model selected AU 1502 864655 A MANUFACTURED BY SEELEY INTERNATIONAL PTY LTD 112 O SULLIVAN BEACH RD LONSDALE SA 5160 AUSTRALIA IMPORTED BY SEELEY INTERNATIONAL EUROPE LTD 5 PAPPLEWICK LANE HUCKNALL NOTTINGHAM NOTTINGHAMSHIRE NG15 7TN UNITED KINGDOM SEELEY INTERNATIONAL AMERICAS LTD 1202 NORTH 54TH AVENUE BUILDING 2 SUITE 117 PHOENIX ARIZONA 85043 USA Service All regions Please contact your local ...

Отзывы: