Industrial Wall Control Application Notes

66

 FAN SPEEDS & AIR FLOW

When the wall control is NOT set for 

EXTERNAL [EXTERNAL] mode

, the fan is controlled through 10 speeds 

according to the automatic or manual settings. 

When the wall control is set for 

EXTERNAL [EXTERNAL] mode

, the fan can only operate at the following 3 

speeds:

MINIMUM

Speed 3

MEDIUM

Speed 6

MAXIMUM

Speed 10

For the purpose of applying the Breezair coolers to various downstream systems, the air flow performance curves 
are provided below. 

Breezair TBA 550 Airflow - Industrial wall control speed settings

for "External" fan speed inputs.

0

20

40

60

80

100

120

140

160

180

200

1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400 2500 2600 2700 2800 2900 3000 3100

Airflow  L/s

S

ta

ti

c

P

re

s

s

u

re

(

P

a

)

Speed 10 - max

Speed 6

Speed 3

As the policy of this company is one of continuous improvement, all specifications are subject to change without notice.

Seeley International Pty Ltd

1-11 Rothesay Ave St Marys, Adelaide, South Australia 5042

Содержание IWC05

Страница 1: ...Application Notes Application Notes Industrial Wall Control IWC05...

Страница 2: ...control of the cooler functions in the MANUAL Man mode The IWC05 may also be set up to control the Air Cooler from EXTERNAL devices such as PLCs and Building Management System computers In this case t...

Страница 3: ...ive voltage is applied when there is no voltage on Input 2 With Input Fan1 and Fan2 positive the cooler will run at maximum speed Input 4 Pump Pump ON OFF This input enables the pump to run when a pos...

Страница 4: ...onsider a Temperature of 20 3 C the bit stream will be 0000000 011001011 Therefore read as 20 3 C 203 Output 8 Drain Drain Control Output This output is activated whenever the Drain Valve is open It w...

Страница 5: ...lue in binary is 10 x the Temperature reading for example 20 6 C is sent as a value of 206 The below example shown at 1sec div is 44 RH which is 00101100 in binary The bit format is S L H D L H D L H...

Страница 6: ...plied with 20m data cable in accessories kit Hubs are supplied with 20m data cable in kit Industrial Wall Controls IWC are supplied with 20m Sensor cable in kit 60m Sensor cable on reel available 20m...

Страница 7: ...eezair coolers to various downstream systems the air flow performance curves are provided below Breezair TBA 550 Airflow Industrial wall control speed settings for External fan speed inputs 0 20 40 60...

Страница 8: ...828534 D 0705 ILL1331 A...

Отзывы: