The Breezair Industrial Wall Control (IWC05) is designed to provide both local and external Evaporative Air cooler 
control for all Breezair air coolers fitted with the CPMD digital module. The external control may be either a PLC or 
Building Management System. The IWC05 is designed to accept external input voltages ranging from 4VDC to 
32VDC and will switch outputs ranging from 1.4VDC to 32VDC at a load of 40mA. The IWC05 has binary outputs 
for Temperature and Humidity for use with other equipment.

CABLE LENGTHS
The maximum total cable length between the cooler CPMD module and the Remote sensor (via the IWC05) 
is 100m. 

Within this limit, the maximum sensor cable length must not exceed 60m. EG: a combination of 40m of 

comms (communications) cable and 60m of sensor cable is permitted and 80m of comms cable and 20m of sensor 
cable is permitted.

Each IWC05 kit is provided with one 20m sensor cable and one 40m comms cable. 80m comms cables and 60m 
sensor cables are available as an option, to be purchased separately.
The above restrictions apply in order to avoid excessive voltage drop and electrical noise. 
YOU MAY USE LONGER CABLES WHEN REQUIRED, BUT WHEN YOU DO THE FOLLOWING CONDITIONS 
MUST APPLY:
 

Cable conductors must be larger to reduce voltage drop.

 

Cables must be screened (or shielded) to reduce noise.

 

Screens must be earthed (grounded).

 

Ensure that conductors are correctly orientated. Use junction boxes or high quality plugs for
terminations.

 

Seeley International takes no responsibility for mal-function of the IWC05 when longer
cables are used.

 

See diagram 2.

1

1

Industrial Wall Control Application Notes

11

AUTO [Auto] mode, and manual control of the cooler functions in the MANUAL [Man] mode.

The IWC05 may also be set up to control the Air Cooler from EXTERNAL devices, such as PLCs and Building 
Management System computers. In this case the IWC05 will cease to function in its AUTO [Auto] or MANUAL 
[Man]  mode and will respond only to the external commands.

The IWC05 provides at all times outputs that may be employed to command other external devices such as 
dampers, fans, signal equipment, etc. These outputs contain the status of the various Air Cooler components (fan, 
pump, drain valve), as well as the Remote Sensor temperature and humidity values.

To ensure signal integrity over distances greater than 100 meters between the IWC05 and the PLC or Building 
management system it is advisable to use shielded cables.

INPUT CONFIGURATION

Connect the Positive input to the input terminals. This voltage must range between 4VDC to a maximum of 32VDC. 
Current in the input is limited by the series resistors.
Connect the Negative input to the common terminal. 
All inputs to the IWC05 are optically isolated from the main circuits.
The IWC05 does not have its own internal power supply to operate the external inputs.

These cables are transmitting digital signals 
and must not be installed next to power cables.

INPUTS AND OUTPUTS

The IWC05 may be set up to control the Air Cooler 
as a local machine, independent of any other 
devices. In that case there will not be any 
connections made to the Input and Output 
terminals. The Remote Sensor supplied in this Kit 
together with the IWC05 will provide automatic 
temperature and/or humidity control along with its 
water management and auto drain features in the 

WHITE

WHITE

WHITE

WHITE

BLACK

BLACK

BLACK

BLACK

RED

RED

RED

RED

GREEN

GREEN

GREEN

GREEN

YELLOW

YELLOW

YELLOW

YELLOW

BLUE

ILL1415-A

BLUE

BLUE

BLUE

2

CONNECTION ORDER FOR SENSOR CABLE ONLY

Содержание IWC05

Страница 1: ...Application Notes Application Notes Industrial Wall Control IWC05...

Страница 2: ...control of the cooler functions in the MANUAL Man mode The IWC05 may also be set up to control the Air Cooler from EXTERNAL devices such as PLCs and Building Management System computers In this case t...

Страница 3: ...ive voltage is applied when there is no voltage on Input 2 With Input Fan1 and Fan2 positive the cooler will run at maximum speed Input 4 Pump Pump ON OFF This input enables the pump to run when a pos...

Страница 4: ...onsider a Temperature of 20 3 C the bit stream will be 0000000 011001011 Therefore read as 20 3 C 203 Output 8 Drain Drain Control Output This output is activated whenever the Drain Valve is open It w...

Страница 5: ...lue in binary is 10 x the Temperature reading for example 20 6 C is sent as a value of 206 The below example shown at 1sec div is 44 RH which is 00101100 in binary The bit format is S L H D L H D L H...

Страница 6: ...plied with 20m data cable in accessories kit Hubs are supplied with 20m data cable in kit Industrial Wall Controls IWC are supplied with 20m Sensor cable in kit 60m Sensor cable on reel available 20m...

Страница 7: ...eezair coolers to various downstream systems the air flow performance curves are provided below Breezair TBA 550 Airflow Industrial wall control speed settings for External fan speed inputs 0 20 40 60...

Страница 8: ...828534 D 0705 ILL1331 A...