Industrial Wall Control Application Notes

INPUT CONFIGURATION (continued)

In EXTERNAL [EXTERNAL] mode the power source must be 
provided adjacent to the Wall Control via a power outlet and 
adaptor. The adaptor may be a common small appliance adaptor 
such as used for telephones, answering machines, weigh scales 
etc, having the specified electrical output (see page 1). 

INPUTS 

If any one of inputs 2,3 or 4 is high, the IWC05 MANUAL [Man] 
and AUTO [Auto] controls will be over-ridden and the IWC05 will 
not respond to temperature and humidity changes sensed by the 
Remote Sensor. In EXTERNAL [EXTERNAL] and AUTO [Auto] 
modes the Temperature and Humidity and clock displays will cycle 
every 5 seconds.

Input 1 [Power]  - Remote  OFF

This input enables the Cooler to be switched OFF. A positive voltage to the input 1 of the IWC05 holds the system 
in the OFF state, and is indicated on the IWC05 screen by a    

R

   . 

WARNING!

 

It is not recommended that this switched input be used to control the Cooler in an emergency 

situation, because it is not fail-safe, ie: if for any reason the cable continuity is cut, it is not possible to 
apply a positive voltage to input 1 to switch the cooler OFF.

Input 2 [F1]  - Fan1

This input enables the fan to run at minimum speed when a positive voltage is 
applied. It functions in conjunction with Input 3 in a binary code to provide 
the external control with three different speed settings for the cooler fan. With 
Input Fan1 and Fan2 positive the cooler will run at maximum speed.

Input 3 [F2]  - Fan2

This input enables the fan to run at medium speed when a positive voltage is applied when there is no voltage on 
Input 2. With Input Fan1 and Fan2 positive the cooler will run at maximum speed.

Input 4 [Pump]  - Pump ON / OFF

This input enables the pump to run when a positive voltage is applied. However, the pump operation is subject to 
the CPMD module and the status of the cooler. If there is insufficient water in the tank the pump will not run until 
water is at the correct level as sensed by the water probes.

Input 5 [H.E.]  - Humidity Enable

This input only functions when the IWC05 is in EXTERNAL [EXTERNAL] Mode. It is possible for External controls 
to drive the cooler to the point where the room humidity exceeds the default set point as sensed at all times by the 
Breezair Remote Sensor. This input enables the IWC05 to over-ride the external pump command and disallow the 
pump to run when the room humidity goes high. If this Input is not enabled, the pump will run as required by the 
external command regardless of room humidity.

Input 6 [DT]  - Pad Dry Time

In AUTO TIMER mode only, when the clock stops the cooler, the fan will continue to run for 60 minutes on speed 2 
in order to dry the cooling pads. 

Input 7 [HD]  - Humidity Disable

This input disables Humidity control in AUTO [Auto] mode when no External [EXTERNAL] control is present. The 
case may arise in AUTO [Auto] in which the temperature is satisfied and the fan is therefore stopped. BUT the 
indoor humidity may fall below the set point and the IWC05 will demand that the cooler operate to raise the 
humidity to the set point. The effect will be to lower the room temperature still further. If this is undesirable, the 
humidity control may be disabled by this input.

Input 8 [Sp1]  - Spare

Currently there is no requirement for this input.

22

FAN

X

X

X

X

X

X

X

X

INPUT 2

INPUT 3

OFF

HIGH

NIL

NIL

HIGH

LOW

MED

HIGH

Содержание IWC05

Страница 1: ...Application Notes Application Notes Industrial Wall Control IWC05...

Страница 2: ...control of the cooler functions in the MANUAL Man mode The IWC05 may also be set up to control the Air Cooler from EXTERNAL devices such as PLCs and Building Management System computers In this case t...

Страница 3: ...ive voltage is applied when there is no voltage on Input 2 With Input Fan1 and Fan2 positive the cooler will run at maximum speed Input 4 Pump Pump ON OFF This input enables the pump to run when a pos...

Страница 4: ...onsider a Temperature of 20 3 C the bit stream will be 0000000 011001011 Therefore read as 20 3 C 203 Output 8 Drain Drain Control Output This output is activated whenever the Drain Valve is open It w...

Страница 5: ...lue in binary is 10 x the Temperature reading for example 20 6 C is sent as a value of 206 The below example shown at 1sec div is 44 RH which is 00101100 in binary The bit format is S L H D L H D L H...

Страница 6: ...plied with 20m data cable in accessories kit Hubs are supplied with 20m data cable in kit Industrial Wall Controls IWC are supplied with 20m Sensor cable in kit 60m Sensor cable on reel available 20m...

Страница 7: ...eezair coolers to various downstream systems the air flow performance curves are provided below Breezair TBA 550 Airflow Industrial wall control speed settings for External fan speed inputs 0 20 40 60...

Страница 8: ...828534 D 0705 ILL1331 A...

Отзывы: