To adjust the activation type for a relay, go to
Settings > Relay Settings > Relay #
and select
“Activation Type”. To adjust the activation type for a zone alarm, go to
Settings > Zone
Settings > Zone #
and select “Alarm Settings”. Not all activation types will always be available.
Adjusting the Zone Display Type
The zone display controls what gas concentration values are shown on the
Home Screen
.
Navigate to
Settings > Zone Settings > Zone Display Type
to select either a time-weighted-
average value or the 8-hour peak average value.
Assigning Sensors
In order for a relay to determine if its setpoint has been exceeded, at least one sensor must be
assigned. To assign a sensor, go to
Settings > Relay Settings > Relay #
and select “Add
Sensor to Relay”. This will bring up the
Sensor Map
to display all currently configured sensors.
If a sensor icon is green, that sensor can be added to a relay. If a gray sensor icon needs to
be added, go back to
Settings > Sensor Map
and follow the instructions for “Adding/Removing
Sensors”. A single sensor can be added to multiple relays. To remove a sensor assignment,
press and hold the sensor icon for 5 seconds. Then select “Remove”. Removing the sensor
IOM03
Rev 1.1 – May 18, 2021
33