3
Installation
S19-310SBFW
Bradley Corporation •
215-163SBFW Rev. K; ECM 08-539
6/9/09
Ø
9" (229mm) Flange
with (3)
Ø
3
⁄
8
" (10mm)
Holes on
Ø
8" (203mm)
Bolt Circle
Top View From Bowl
9"
(229mm)
25
3
⁄
8
"
(645mm)
86"
(2184mm)
to Bottom
of Base
68
11
⁄
16
"
(1745mm)
to Bottom
of Base
Ø
10¾"
(273mm)
36½"
(927mm)
to Bottom
of Base
6
5
⁄
8
"
(168mm)
10½"
(267mm)
9½"
(241mm)
66"
(1676mm)
to Bottom
of Base
6"
(152mm)
4½"
(114mm)
Ø
3.1"
(78.7mm)
Installation
Supplies Required:
• (3)
3
⁄
8
" floor anchors and bolts
• Teflon tape and pipe sealant
• Piping to 1¼" NPT water supply inlet and to 1¼" NPT
drain outlet on unit
• Adequate supply pipe supports
• Min. 4" drain to accommodate 30 gallons per minute
discharge for shower waste
• OPTIONAL: sign-mounting hardware
NOTE: Local codes may require the installation
of a backfl ow prevention valve to complete proper
installation. Compliance with local codes is the
responsibility of the installer. Valve must be tested
annually to verify that it is functioning properly. Backfl ow
prevention valves are not included with the fi xture and
may be supplied by the contractor or purchased from
Bradley Corporation.
Step 1: Secure base to floor
1. Install three suitable anchors (supplied by installer)
for
3
⁄
8
" bolts in the floor.
2. Bolt the base to the floor anchors using
3
⁄
8
" bolts
(supplied by installer).
Step 2: Assemble components
1. Assemble the remaining unit components as
shown on page 4.
• Apply teflon tape or pipe sealant (supplied by
installer) as required to all male-threaded pipe
joints.
• Use the rubber grip pad provided or a strap
wrench around pipes when tightening to prevent
marring the Bradtect® protective, safety yellow
coating. Place the grip pad on the pipe, then put
the wrench over the grip pad and turn the pipe
with the wrench.
• The bottom edge of the showerhead should be
86" (2184mm) from the floor.
Step 3: Connect water supply
IMPORTANT: Do not rely on Bradley’s
Combination Unit to support supply piping.
1. Connect water supply piping to 1¼" NPT inlet
on unit (piping by installer). Provide adequate
supports (by installer) for supply pipe using pipe
hangers or other means.
2. Connect drain piping to 1¼" NPT drain outlet on
unit (piping by installer).
3. Hang the safety sign from the unit with the curtain
hooks provided (or mount it to the wall using sign-
mounting hardware by installer).
NOTE: All dimensions assume standard thread
engagement. Variations in manufacturing allow for
+/-
1
⁄
8
" (3mm) per threaded joint. To fi nd the tolerance
of a dimension, add the number of thread joints in
between a dimension and multiply it by
1
⁄
8
" (3mm).