Installation
EFX 120/S19-2350
Bradley
• 215-1818 Rev. B; ECN 17-09-009
12/7/2017
5
When the check valves are in the open (opera ting)
position, the cover screw for the stop/check stem will
be flush with the valve cap.
Check for leaks by
pressurizing unit SLOWLY.
Install Thermometer using
pipe sealant or teflon tape.
Check the temperature when approximately 10 GPM
water flow is reached (equivalent to two face washes)
Stop/Check
Cover Screw
Check
Stop Nut
Water Recirculation
Plug
Thermometer
Tempered Water
(to Fixture)
HOT
COLD
Shut the hot water supply off by closing hot water inlet valve or supply check valve. While the hot water supply is turned off, check
to make sure the cold water continues to flow. If the cold water is flowing properly, reopen the hot water supply.
Shut the cold water supply off by closing the cold water inlet valve or supply check valve. While the cold water supply is off, check
to make sure that the hot water flow has shut down. If hot water is shut down, reopen cold water supply. Test unit weekly for
proper function and desired set temperature.
This device must be checked for final temperature and
adjusted as necessary. The standard preset factory
temperature setting is 85°F (29°C). [the range of the valve
is 65°F – 90°F (18°C – 32°C)]. Insert Allen Wrench through
the hole in the cap and into the set screw to adjust. Consult
proper medical and/or safety authorities for the optimum
temperature recommended for your particular application.
No single emergency fixture supplied by this device has
a minimum flow rate less than 1.5 GPM (5.7 L/m).
C
H
5/32" Allen Wrench
Connect Supply Lines and Install Thermometer
2
Adjust Temperature with Water Running
3
Test Unit
DO NOT SKIP THIS STEP!!!
4