Troubleshooting
RTG 199 HE – 6 720 811 617 (2016/01)
42
7.7.1
Working hours
To see how many hours the appliance has worked, please enter the
“Diagnostic menu” (chapter 7.7);
▶ Select the sub-mode “H0”.
Write the number that shows in the display.
▶ Select the sub-mode “H1”.
Write the number that shows in the display.
▶ Select the sub-mode “H2”.
Write the number that shows in the display.
After checking the sub-modes H0, H1 and H2, introduce the values in
the table below;
Example:
Calculation of number of working hours,
7.7.2
Number of cycles
To see how many cycles the appliance has done, please enter the
“Diagnostic menu” (chapter 7.7);
▶ Select the sub-mode “C0”.
Write the number that shows in the display.
▶ Select the sub-mode “C1”.
Write the number that shows in the display.
▶ Select the sub-mode “C2”.
Write the number that shows in the display.
After checking the sub-modes C0, C1 and C2, introduce the values in a
table as the example;
Example:
Calculation of number of cycles (1 cycle = 1 ignition),
8
Troubleshooting
8.1
Introduction
Many of the questions customers ask regarding operation of this unit can
be answered by following the troubleshooting steps as outlined below.
For best results, perform each step before proceeding to the next. The
suggested solutions may require that the cover be taken off. (See fig. 3,
page 8).
8.2
Burner does not ignite when hot water is turned ON
It is recommended to use “Control board diagnostics” page 41, chapter
7.7 as a tool for problem solving. If the display is showing a blinking two
digit code, refer to this section.
1. If the display is blank, verify power to outlet. (120VAC/60Hz
properly grounded circuit required). Verify that the heater power
button is pressed ON.
2. Verify the fuses in the control board are good. To access fuses, the
control board must be removed. See chapter 5.2, page 34.
3. Make sure cold water inlet connection is plumbed to the right side of
heater when facing unit. See Fig.35, page 29.
4. A minimum of 0.5 gallons per minute (1.9 l/m) of hot water demand
is required to activate the heater. Confirm at least 0.5 gpm flow by
timing how long it takes to fill a container. A quart container should fill
in 23 seconds or less, from hot water tap only, to activate heater. In
unusual circumstances with high inlet water temperatures and low
set temperatures, the heater may increase the activation rate above
0.5 gpm to avoid overheating at low flows. Gradually increase water
flow (hot water demand) through the heater to determine if the
heater activates with higher flow.
5. Clean inlet filter screen per chapter 7.1, page 37.
6. Inspect the water path for obstructions. Make sure all shower heads,
faucet aerators and whole house filters are clear of debris.
10F
10th most recent error
1P*
Appliance type - Cd (Condensing)
Appliance type - nC (Non condensing)
2P*
Appliance power - 175 / 199 (kBTU/hr)
3P*
Temperature range - H (100-140°F)
Temperature range - C (100-184°F)
H0
Numbers of hours - mode 0
H1
Numbers of hours - mode 1
H2
Numbers of hours - mode 2
C0
Number of cycles - mode 0
C1
Number of cycles - mode 1
C2
Number of cycles - mode 2
Working hours
Number in H0
______
_
Number in H1
______ (X 100) =
_
Number in H2
______ (X 10 000) =
_______
(H0 + H1 + H2) = Total of hours
__________
Table 46
Diagnostic menu
Table 45 * Settings define from factory
Working hours
Number in H0
60
60 +
Number in H1
5 (X 100) =
500 +
Number in H2
0 (X 10 000) =
0
(H0 + H1 + H2) = Total of hours
560
Table 47
Number of cycles
Number in C0
40
40 +
Number in C1
6 (X 100) =
600 +
Number in C2
1 (X 10 000) =
10 000
(C0 + C1 + C2) = Total of cycles
10 640
Table 48
CAUTION:
▶ If you are unable to perform the tasks listed below, or
need additional assistance please contact your
original installer or a licensed gas technician.