Condensing PV Series
9
Control Timings
Ignition State
Timing
Pre-purge
2 Seconds
Trial for Ignition
90 Seconds
Flame Stabilization Period
3 Seconds
Inter-purge
15 Seconds
Flame Failure Response Time
1.5 Seconds (2 second maximum; 1 second minimum.)
Post-purge
15 Seconds
PS Fault Delay (failed open/close)
Retry after 2 minutes
Soft Lockout
Retry after 5 minutes
ECO Limit Lockout
Indefinite (see PV SERVICE PROCEDURE VI; page 26)
Verify Resistive Delay
Retry after 2 minutes (repeats 5 times)
Simulated Resistive Load Lockout
Indefinite (cycle power to restart)
Hardware Error Lockout
Indefinite (self clears if fault clears for at least 15 seconds)