37
Condensing PV Series
37
Installation of Inner Door With Gasket
Step 7.
Clean any residual gasket residue or other debris from the
combustion chamber surface before installing the inner
door/gasket assembly.
Step 8.
Place the left side inner door into position first. Firmly
position the radiused channel of the inner door around the
feedline. Using the ¼” hex drive screws from step 3c,
secure the left side inner door in place.
DO NOT OVER
TIGHTEN SCREWS.
Step 9.
Position pilot tube and igniter/sensor wire against left side inner door flange gasket.
DO
NOT ROUTE PILOT TUBE AND IGNITER/SENSOR WIRE THROUGH RADIUSED
CHANNEL WITH THE FEEDLINE.
WARNING
Stripped fastener connections
may allow for seal breach of
inner door. A seal breach may
result in a fire or explosion
causing property damage,
personal injury or death. Do
not over tighten screws in
steps 8, 10 and 11.