25
Troubleshooting Chart – Honeywell V1 continued-
LED Status
Control Status
Probable Cause
Five flashes and
three second
pause
Temperature sensor
fault.
1. Damage to the temperature
wire.
2. Temperature sensor
resistance out of range.
3. Replace temperature sensor.
4. If temperature sensor
replacement does not correct
the problem; verify control is
not wet or physically
damaged.
5. Turn set point knob to "OFF"
position. Turn set point knob
to "PILOT" position and light
pilot.
6. Replace gas valve if five flash
error persists.
Six flashes and
three second
pause
Water leak detected
by accessory
module (some
models).
Excessive amount of water in
drain pan/water dam.
Seven flashes
and three second
pause
Gas valve electronic
fault detected.
1. Verify control is not wet or
physically damaged.
2. Turn set point knob to "OFF"
position. Turn set point knob
to "PILOT" position and light
pilot.
3. Replace gas valve if seven
flash error persists.
Eight flashes and
three second
pause
False pilot flame
present.
1. Pilot valve stuck in open
position.
2. Turn set point knob to "OFF"
position. Turn set point knob
to "PILOT" position and light
pilot.
3. Replace gas valve if eight
flash error persists.
Содержание FVIR Defender Safety System RG240T6N394264475
Страница 16: ...16 Lighting Shutdown Instructions White Rodgers Mechanical Gas Control ...
Страница 17: ...17 Lighting Shutdown White Rodgers Electronic Gas Control ...
Страница 18: ...18 Lighting Shutdown Honeywell Gas Control ...
Страница 29: ...29 INSTALLATION FOR POTABLE WATER Figure 11 ...
Страница 32: ...32 NOTES ...