background image

 

12

 

2.  In order to service the water heater in the event the heat exchanger needs to be flushed from lime 

deposits, tee fittings with shut off valves and service connections to hoses should be installed.  
Also install a shut off valve to the hot water supply to isolate the service tee fittings.  A plumbing 
installation kit, which includes these fittings and a pressure relief valve, is available from your 
supplier.  Refer to piping diagrams (fig. 2-5) at the end of Section V. 

 

3.  Install a pressure relief valve on a tee connection from the hot water outlet piping from the water 

heater.  Refer to the piping diagrams (fig. 2-5) and the warning for the Pressure Relief Valve at 
the end of Section V on Water Connections. 

 

4.  In cold climates where piping can freeze during an extended power failure, drain solenoid valves 

should be installed on the cold and hot water supply lines to allow water to drain from the water 
heater when power is interrupted.  Refer to the piping diagram “Recommended Piping for Power 
Failure Freeze Protection” (fig. 3) at the end of this Water Connections Section and contact your 
Bradford White dealer if assistance is needed. 

 

5.  If this water heater is installed in a closed water supply system, such as the one having a back-

flow preventer in the cold water supply, provisions must be made to control thermal expansion.  

DO NOT

 operate this water heater in a closed system without provisions for controlling thermal 

expansion.  Warranties do not cover damages from thermal expansions such as pressure bulges 
and/or deformities.  Your water supplier or local plumbing inspector should be contacted on how 
to control this situation. 

 

6.  Purge the cold water line prior to connecting to the water heater to remove debris.  Debris will 

clog the mesh strainer of the inlet filter.  The inlet strainer prevents debris from damaging the flow 
sensor or clogging the coil.  It may need to be cleaned periodically and should be cleaned after 
the installation.  

DO NOT operate the water heater without the filter in place

 

7.  After installation of the water lines, open the main water supply valve and fill the water heater.  

While the water heater is filling, open several hot water faucets to allow air to escape from the 
water system.  When a steady stream of water flows through the faucets, close them and check 
all water connections for possible leaks. 

 

8.  This water heater may also be connected to a circulating pump or storage tank for increased flow 

capacity during high demand periods.  Refer to the suggested piping diagrams (fig. 4-5) at the 
end of Section V on Water Connections to be used as a guide. 

 

9.  Commercial installations may require more than one water heater piped together in a manifold to 

supply enough capacity for high temperature and high water flow applications.  Special controls 
are available from your Bradford White supplier for operating more than one water heater 
together.  These controls stage the operation of the water heaters for the flow rates and control 
the amount of flow through each water heater.  Order part# 239-44511-00 for the electronic 
manifold control for the first and second water heater and part# 239-44512-00 for the wiring 
harness for each additional water heater to be controlled.  Instructions are included with these 
parts.  Use the piping diagram in figure 5 in Section V as a guide.   

 

    

NOTICE

 

Take care when using pipe dope or thread sealant tape to avoid clogging the inlet screen and water 
flow sensor.  Wipe off excess pipe dope from threads before connecting to the water heater. 
Commercial dishwashers will require either more than one water heater or a storage tank to supply a 
sufficient volume of hot water. 

 

 

 
 
 
 
 
 

Содержание Everhot IGE-199C Series

Страница 1: ...hbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or...

Страница 2: ...installed in accordance with local codes In the absence of local codes it must be installed in compliance with the National Fuel Gas Code ANSI Z223 1 Latest Edition or in Canada CAN CGA B149 1 Natural...

Страница 3: ...damage personal injury or loss of life Failure to follow all instructions in the proper order can cause personal injury or death Read and understand all instructions including all those provided with...

Страница 4: ...r heater materials of construction products of combustion and the fuel contain carbon monoxide nitrogen oxides aldehydes and or other toxic or harmful substances which can cause death or serious injur...

Страница 5: ...Input Rating Btu hr Temp Rise 40 F 60 F 80 F 100 F 120 F 140 F IGE 199R 10N IGE 199R 10X IGE 199C 5N IGE 199C 5X 199 000 15 000 Flow Rate Gal Min 7 3 5 9 4 2 3 3 2 8 2 4 First Hour Supply Gal Hr 438...

Страница 6: ...ximum input 0 9 Minimum input Venting System Forced Combustion external vent For Outdoor Installation Only Setpoint Temperature Without remote temperature control 140 F Commercial models 120 F Residen...

Страница 7: ...ds 23 kg and can be installed by 1 person The burners ignite within 3 seconds of water flow 1 2 gallon minute 1 9 L m minimum by direct spark ignition There is no standing pilot A variable speed combu...

Страница 8: ...inish in intensity or fade and not be as readily detectable If you have a diminished sense of smell or are in any way unsure of the presence of gas immediately contact your gas supplier from a telepho...

Страница 9: ...nimum installation clearances before choosing a final location for the water heater 2 The water heater must be installed on a wall capable of supporting at least 50 pounds 23 Kg Locate the water heate...

Страница 10: ...overhangs windows doors etc Also avoid locations where there is heavy water runoff from roofs Determine the proper height and location for the water heater to be installed Consider the water and gas...

Страница 11: ...0 3 ppm Up to 0 05 ppm Up to 5 ppm Lime Condition Warning Signal If the EVERHOT water heater is operated under hard water conditions without a water conditioner the error code LC may flash on the rem...

Страница 12: ...is Debris will clog the mesh strainer of the inlet filter The inlet strainer prevents debris from damaging the flow sensor or clogging the coil It may need to be cleaned periodically and should be cle...

Страница 13: ...13 Recommended Piping for a Basic Installation Fig 2...

Страница 14: ...lowing illustration The drain solenoids are recommended for very cold climates to prevent water heater freeze damage where power failures from ice and windstorms occur The electrical connections for t...

Страница 15: ...15 Recommended Piping for a Circulation System Fig 4...

Страница 16: ...16 Recommended Piping for Back up Storage System For hotels motels and other high flow applications Fig 5 Note The Primary Circulator for the water heating loop must be sized for 21 GPM 35 Ft Head...

Страница 17: ...stall the pressure relief valve into a tee connection from the hot water outlet of the water heater Note Some models may already be equipped or supplied with an installed pressure relief valve Verify...

Страница 18: ...urred such as through improper testing of gas lines or emergency malfunction of the supply system the gas valve must be checked for safe operation Make sure that the outside vents on the supply regula...

Страница 19: ...125 150 175 200 3 6 9 12 15 18 21 24 27 30 38 45 53 61 278 190 152 130 115 105 96 90 84 79 72 64 59 55 1 520 350 285 245 215 195 180 170 160 150 130 120 110 100 1 1050 730 590 500 440 400 370 350 320...

Страница 20: ...around the plugs 7 Replace the front control panel Restore electrical power to the water heater NOTICE If the gas supply pressure is below the specified value check the gas piping to insure that it is...

Страница 21: ...ted by local code then provide a three wire GFI grounding type receptacle within reach of the control box Provide a grounded line cord and connect to the black and white power supply and green ground...

Страница 22: ...22 Wiring Diagram WARNING DO NOT adjust any dipswitch settings on PC board...

Страница 23: ...23 Wiring Diagram Schematic...

Страница 24: ...ature for sanitizing purposes Always check water temperature by hand before entering the shower or bath The temperature may have been changed Test the temperature of the water with your hand or elbow...

Страница 25: ...le for the cable using a 6 4 mm drill bit 3 Run the cable from the control to the water heater or another control which ever is closer or more convenient 4 Remove the face plate from the remote contro...

Страница 26: ...ture setting is 140 F In addition the control will display fault codes in the event the water heater needs service Up to two additional optional remote controls may be purchased and installed if desir...

Страница 27: ...trols with the power on to the water heater There are 120 volt terminals and wiring next to the remote control connections inside the unit All servicing and wiring must be performed by a qualified ins...

Страница 28: ...service professional 1 Flooding to or above the level of the burner or controls 2 External firing 3 Damage 4 Firing without water 5 Sooting NEVER OPERATE THE WATER HEATER WITHOUT FIRST BEING CERTAIN I...

Страница 29: ...iately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department OPERATING INSTRUCTIONS 1 STOP Read the safet...

Страница 30: ...water lines A licensed plumbing professional or local plumbing authority should be consulted CAUTION This water heater when set at a lower temperature setting is not capable of producing hot water of...

Страница 31: ...p to 9 error codes if any stored in memory that has been experienced Any error codes will be displayed on the digital monitor in sequence starting with the most recent code 7 To display the water flow...

Страница 32: ...utomatically start heating water whenever a hot water faucet is opened The remote temperature control s will indicate hot water use with the green IN USE indicator 5 All controls can also display diag...

Страница 33: ...child in the bath or shower Do not leave a child or an infirm person in the bath unsupervised This water heater can deliver scalding temperature water at any faucet in the system Be careful whenever...

Страница 34: ...isplayed Fault Remedy 10 Air supply or exhaust blockage Check for a restriction in the exhaust vent 11 No Ignition Check to make sure the gas supply is on to the water heater 12 Flame Failure groundin...

Страница 35: ...3 Check the front vent outlet for any obstructions 4 All electric motors are permanently lubricated and do not need oiling Remove the combustion air blower and clean wheel and housing with soft brush...

Страница 36: ...r out the lime deposits Use the following procedure and diagram fig 13 to flush the heat exchanger and remove the lime scale 1 Disconnect power to the water heater 2 Close valves in the cold water inl...

Страница 37: ...operate the water heater To remedy this situation either increase the total water flow from the tap or using the remote temperature controller decrease the setpoint temperature of the water heater to...

Страница 38: ...38 SCHEMATIC DIAGRAM OF INTERNAL PARTS...

Страница 39: ...39 SECTION X PARTS LIST Cabinet Note Can purchase additional controls for remote locations...

Страница 40: ...40 Internal Components...

Страница 41: ...41 Internal Components...

Страница 42: ...42 Electrical Components...

Страница 43: ...amber Front Plate 1 116 Spark Electrode 1 117 Flame Sense Rod 1 118 Electrode Gasket 1 119 Electrode Holder 1 120 Upper Combustion Chamber Gasket 1 122 Fan Casing Assembly 1 123 Blower Motor 1 127 Blo...

Страница 44: ...Frost Sensing Switch 1 733 120V Anti Frost Heater Assembly 1 734 Sensor Harness 2 1 735 Water Flow Sensor 1 801 Screw 4 802 Washer 4 803 Screw 3 804 Screw 1 805 Screw 3 806 Screw 4 807 Washer 4 808 Sc...