ELECTRICAL HOOK-UP
WARNING
WATER HEATING UNITS EQUIPPED FOR ONE VOLTAGE ONLY: CHECK THE RATING
PLATE ON THE FRONT OF THE UNIT. DO NOT USE THIS WATER HEATER WITH ANY
VOLTAGE OTHER THAN THE ONE SHOWN ON THE MODEL RATING PLATE. FAILURE TO
DO SO CAN RESULT IN DEATH, SERIOUS BODILY INJURY, OR PROPERTY DAMAGE. IF
YOU HAVE ANY QUESTIONS OR DOUBTS CONSULT YOUR ELECTRIC COMPANY.
This unit must have its own independent circuit using five wires; three live,one neutral and
one ground of the appropriate rating protected by the correctly rated three pole breaker
IMPORTANT
BEFORE SWITCHING “ON” THE POWER AT THE MAIN CIRCUIT BREAKER PANEL MAKE
SURE THAT THE HOT WATER CIRCUIT IS FREE OF AIR POCKETS OR PREMATURE
FAILURE OF THE ELEMENT WILL OCCUR. TO DO THIS OPEN ALL HOT WATER OUTLETS
ONE AT A TIME FOR A MINUTE OR TWO UNTIL THE WATER FLOW IS CONTINUOUS AND
FREE FROM “GULPING” AND FROM VISIBLE AIR POCKETS.
RATINGS OF “ EFT” THREE PHASE MODELS
5
CURRENT
TEMPERATURE RISE IN DEGREES
MODEL
RATING(KW)
VOLTAGE(V) PER PHASE 1.5GPM 2.0GPM 2.5GPM 3.0GPM 3.5GPM 4.0GPM 5.0GPM
*EFT-18000-T-10
18 208/120 50A/PHASE
82
61
49
41
35
32
25
*EFT-24000-T-10
24 208/120 67A/PHASE
0
82
65
54
47
43
34
*EFT-18000-T-10
18
277 21.7A/PHASE
82
61
49
41
35
32
25
*EFT-24000-T-10
24
277 28.9A/PHASE
0
82
65
54
47
43
34
*EFT-32000-T-10
32
277 38.5A/PHASE
0
0
87
73
62
58
45
*EFT-28000-T-10
28
240 40A/PHASE
128
90
72
65
55
47
38
IF THE UNIT IS CONNECTED TO 460/265 THREE PHASE SYSTEM THE ABOVE OUTPUTS WILL BE REDUCED BY 8.5%
* UNIT MAY BE CONNECTED TO A 208V POWER SUPPLY, ABOVE OUTPUTS WILL BE REDUCED BY 25%