GENERAL

This  “Three Phase Thermostatic” water heating unit is specifically designed to take in
cold or pre-heated  water and heat it to temperatures suitable for commercial washing,
sluicing or processing, up to a maximum temperature of 180° F (82° deg. C). To obtain
optimum performance and energy savings, this unit should be located as near as possible
to the point of use. This unit must only be installed in a vertical position with the inlet
and outlet at the bottom. The power is activated by individual electronic flow switches located
in each of the three heating modules. These will be damaged by excessive heat, do not solder
any pipes that are in contact with the heater.  Also ensure pipes are clear of installation debris 
before connecting the water heating unit, otherwise the flow  switches could jam in the

“on” position. This unit must be connected to its own individual electric circuit protected by

a suitably rated three pole breaker. The maximum voltage which can be applied across any
heating module is 277 volts.  It is recommended that a Pressure Relief Valve be installed
as close as possible to the heater outlet of the unit ( per code).

WARNING

Improper installation, adjustment, alteration, service or maintenance can cause DEATH,
SERIOUS BODILY INJURY OR PROPERTY DAMAGE. Refer to this manual for
assistance or consult the local electric utility for further information.

This  unit is supplied with compression rings and nuts suitable for direct coupling to
standard 1/2 “ ( 5/8 “ outside diameter ) copper or plastic piping. There is no need for 
additional screwed fittings and under no circumstances shall a blow torch be used on pipe 
connected to the unit  (serious damage to the electronic flow switch will result). 

WARNING

Failure to ground the system may result in death or serious injury. 

2

ELECTRICAL SHOCK HAZARD! BEFORE REMOVING THE COVER OR SERVICING THE 
WATER HEATER, MAKE SURE THE ELECTRICAL SUPPLY TO THE WATER HEATING
UNIT IS  TURNED “OFF”. FAILURE TO DO SO CAN RESULT IN

DEATH, SERIOUS 

BODILY INJURY, OR PROPERTY DAMAGE

.

Содержание EFT-18000-2-T-10

Страница 1: ...R INSTALLATION AND OPERATION THE WARRANTY SHALL BE VOID IF THE DESIGN HAS BEEN ALTERED IN ANY WAY WHATSOEVER THE MANUFACTURER OF THIS UNIT WILL NOT BE LIABLE FOR ANY DAMAGES BECAUSE OF FAILURE TO COMP...

Страница 2: ...bly rated three pole breaker The maximum voltage which can be applied across any heating module is 277 volts It is recommended that a Pressure Relief Valve be installed as close as possible to the hea...

Страница 3: ...ing system in such a way that there is no tendency for the unit to be starved of water for example by an excessive draw off of cold water just before the unit Also do not fit an unrestricted hot water...

Страница 4: ...l valve type on both inlet and outlet pipes This allows the unit to be isolated for maintenance purposes 4 When all plumbing is complete inspect the system for water leaks at all plumbing connections...

Страница 5: ...OCKETS OR PREMATURE FAILURE OF THE ELEMENT WILL OCCUR TO DO THIS OPEN ALL HOT WATER OUTLETS ONE AT A TIME FOR A MINUTE OR TWO UNTIL THE WATER FLOW IS CONTINUOUS AND FREE FROM GULPING AND FROM VISIBLE...

Страница 6: ...s point water temperature may not be hot 5 Using the OUTLET BALL VALVE slowly reduce water flow until desired water temperature is achieved at hot water outlet NOTE The water temperature is regulated...

Страница 7: ...at the set temperature Check that the temperature is what is required The thermostat is now set and the water temperature will remain constant when the indicator light is pulsing 6 Check the performa...

Страница 8: ...6 7 OHMS 7 8 OHMS 10 11 OHMS IF RESISTENCE OF THE ELEMENT IS MUCH GREATER THAN THESE READINGS CALL TECHNICAL SUPPORT NO HAET OR LOW TEMERATURE INDICATOR LIGHT ON A WATER FLOW TOO HIGH REDUCE WATER FLO...

Страница 9: ......

Страница 10: ...connection with a maximum of 277 volts across each element REPLACEMENT PARTS DIAGRAM THERMOSTATIC PCB PART EX100 VOLTAGE HEATER CORE ASSEMBLY FOR TRIAC PART EX18 8 EFT 18000 T 10 277V EX1280 EFT 1800...

Отзывы: