background image

13 

TROUBLESHOOTING 

(In addition to instruction manual.) 

 

LED Status

Control Status

Probable Cause

None (LED not  on 

or flashing)

Elect rical pow er not  

present

1. Cont rol pow er sw it ch in " OFF"  posit ion
2. Supply volt age int errupted

One short  f lash 

every f our 

seconds

St and-by mode, 

Thermost at  is sat isf ied (no 

f aults)

Temperat ure demand is sat isf ied (no call f or 
heat )

Alt ernat es bright  

and dim 

(heart beat )

Thermost at  calling f or heat 

(no f ault )

Tank t emperat ure below  set point  of  
t hermost at

Short f lash once 

every second

Weak pilot  signal on last  

call f or heat

1. Unst able pilot
2. Pilot  t ube block or rest rict ed
3. Oxidat ion build-up on pilot  elect rode
4. Wire damage t o pilot  assembly or bad 
connect ion at gas valve

Tw o f lashes, 
t hree second 

pause

Relay not  w orking

Fault y relay

Three f lashes, 

t hree second 

pause

Relay not  w orking

Fault y relay

Four f lashes, 
t hree second 

pause

Excessive t ank 

temperat ure, syst em must  

be reset

1. Thermal w ell sensor out of  calibrat ion
2. Fault y gas valve

Five f lashes, 

t hree second 

pause

False pilot  f lame present

Pilot  valve stuck in open posit ion

Six f lashes, one 

f lash, t hree 

second pause 

(Sof t Lockout )

Failed t o light  pilot , 

syst em reset s af t er (5) 

minut es

1. Unst able pilot
2. Pilot  t ube block or rest rict ed
3. Oxidat ion build-up on pilot  elect rode
4. Wire damage t o pilot  assembly or bad 
connect ion at gas valve

 

Содержание Defender Safety System 238-48248-00

Страница 1: ...on Resistant System In the event of improper usage or storage of gasoline or other flammable materials in the location where the water heater is installed the technology will resist ignition of the fl...

Страница 2: ...must be installed on top of a metal or wood panel or equivalent extending beyond the full width and depth of the water heater by at least 3 in 7 6 cm in any direction or if the appliance is to be ins...

Страница 3: ...ance if any part has been under water Immediately call a qualified technician to inspect the appliance and to replace any part of the control system and any gas control which has been under water a fi...

Страница 4: ...lockwise to decrease the temperature setting Rotate the thermostat dial clockwise to increase the temperature setting Adjust the dial until the minimum acceptable temperature is achieved DANGER Hotter...

Страница 5: ...adjusting air mixture and do not have an adjustable air shutter See Figure 3 At periodic intervals a visual check of the main burner and pilot flames should be made to determine if they are burning p...

Страница 6: ...6 INSTALLATION FOR POTABLE WATER Replaces pg 28 in instruction manual Figure 4...

Страница 7: ...7 PARTS LIST DRAWING Replaces pg 29 in instruction manual Figure 5 1 3 4 5 6 7 8 9 10 12 13 14 15 16 15A 19 20 21 22 23 24 25 27 28 11 26 2 18 17...

Страница 8: ...ccessory Module 4 Jacket 18 Junction box wire harness 5 Heat trap outlet 19 Thermal well 6 Anode Outlet Device 20 Gas control 7 Heat trap inlet 21 FV sensor RTS wire harness 8 Baffle 22 FV sensor clip...

Страница 9: ...emicals such as those used for boiler treatment must not be introduced into potable water used for space heating 2 This water heater must not be connected to an existing heating system or component s...

Страница 10: ...ed with a flammable vapor water heater control will shut down the water heater and display a code of 7 flashes and then a 3 second pause If a 7 flash error code is present check to see if flammable va...

Страница 11: ...d Accessory Module If wiring in conduit is required cut the flexible line cord at least 6 in 15 2 cm from the bushing Unscrew and remove the Setback Control Junction Box Assembly lid Pull the cord int...

Страница 12: ...REPLACED WITH APPLIANCE WIRE MATERIAL WITH A MINIMUM TEMPERATURE RATING OF 105 C AND A MINIMUM SIZE OF NO 18 AWG ELECTRICAL RATING HOT LOW HOT VERY A C B Honeywell W PILO SETBACK GAS R B W B G Y POWER...

Страница 13: ...t 2 Pilot tube block or restricted 3 Oxidation build up on pilot electrode 4 Wire damage to pilot assembly or bad connection at gas valve Two flashes three second pause Relay not working Faulty relay...

Страница 14: ...r exposed to excessive moisture 3 Flammable vapor sensor exposed to extreme ambient temperature 4 Resettable thermal switch open Eight flashes one flash three second pause Flammable vapor sensor out o...

Страница 15: ...sends power to the relay which then closes the relay contacts 4 The control starts the ignition process by providing a spark at the pilot electrode and allowing gas to flow to the pilot 5 When the pil...

Страница 16: ...16 Notes...

Отзывы: